(4) Press the SET TEMP. buttons (
) ( ) to select the setting value.
The display fl ashes as shown to the right during setting value selection.
Setting value
SU MO TU WE TH FR SA
(5) Press the TIMER SET button to confi rm the setting.
Press the TIMER SET button for a few seconds until the setting value stops fl ashing.
If the setting value display changes or if “- -” is displayed when the fl ashing stops, the
setting value has not been set correctly.
(An invalid setting value may have been selected for the indoor unit.)
(6) Repeat steps 2 to 5 to perform additional settings.
Press the SET TEMP. buttons (
) ( ) and FAN button simultaneously again for
more than 5 seconds to cancel the function setting mode. In addition, the func-
tion setting mode will be automatically canceled after 1 minute if no operation is
performed.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
• Function Details
(1) Filter Sign
The indoor unit has a sign to inform the user that it is time to clean the fi lter. Select the
time setting for the fi lter sign display interval in the table below according to the amount of
dust or debris in the room. If you do not wish the fi lter sign to be displayed, select the set-
ting value for “No indication”.
(
♦
... Factory setting)
Setting description
Function
number
Setting value
Standard (400 hours)
11
00
Long interval (1000 hours)
01
Short interval (200 hours)
02
♦
No indication
03
(2) Static pressure
Select appropriate static pressure according to the installation conditions.
(
♦
... Factory setting
)
Setting description
Function
number
Setting value
0 Pa
26
00
10 Pa
01
20 Pa
02
30 Pa
03
40 Pa
04
50 Pa
05
60 Pa
06
70 Pa
07
80 Pa
08
90 Pa
09
♦
25 Pa [Standard]
31
Range of static pressure is different from 1 model to other.
Range of static pressure
0 to 90 Pa
(3) Cooling room temperature correction
Depending on the installed environment, the room temperature sensor may require a cor-
rection.
The settings may be selected as shown in the table below.
(
♦
... Factory setting)
Setting description
Function
number
Setting value
♦
Standard
30
00
Slightly lower control
01
Lower control
02
Warmer control
03
When using fl oor console installation, change the setting value to “01”.
(4) Heating room temperature correction
Depending on the installed environment, the room temperature sensor
may require a cor-
rection.
The settings may be changed as shown in the table below.
(
♦
... Factory setting)
Setting description
Function
number
Setting value
♦
Standard
31
00
Lower control
01
Slightly warmer control
02
Warmer control
03
When using fl oor console installation, change the setting value to “01”.
(5) Auto restart
Enable or disable automatic system restart after a power outage.
(
♦
... Factory setting)
Setting description
Function
number
Setting value
♦
Yes
40
00
No
01
* Auto restart is an emergency function such as for power failure etc. Do not start and stop
the indoor unit by this function in normal operation. Be sure to operate by the control unit,
or external input device.
(6) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when using the Wired remote controller temperature
sensor.
(
♦
... Factory setting)
Setting description
Function
number
Setting value
♦
No
42
00
Yes
01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote
controller unit sensor.
(7) Wireless remote controller signal code
Change the indoor unit Signal Code, depending on the wireless remote controllers.
(
♦
... Factory setting)
Setting description
Function
number
Setting value
♦
A
44
00
B
01
C
02
D
03
(8) External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
(
♦
... Factory setting)
Setting description
Function
number
Setting value
♦
Operation/Stop mode
46
00
(Setting forbidden)
01
Forced stop mode
02
9374342235-02_IM.indb 15