En-4

 

CAUTION

If children under 10 years old may approach the unit, take preventive measures so that 
they cannot reach the unit.

• Decide the mounting position with the customer as follows:

(1)  Install the indoor unit in a location having suffi cient strength to support the weight of 

the indoor unit.

(2)  The inlet and outlet ports should not be obstructed; the air should be able to blow all 

over the room.

(3)  Leave the space required to service the air conditioner.

(4)  Locate where the air can be distributed evenly throughout the room by the unit.

(5)  Install the unit where connection to the outdoor unit is easy.

(6)  Install the unit where the connection pipe can be easily installed.

(7)  Install the unit where the drain pipe can be easily installed.

(8)  Install the unit where noise and vibration is not amplifi ed.

(9)  Take servicing, etc., into consideration and leave the spaces. Also install the unit 

where the fi lter can be removed.

3.2A. Installation dimensions (Ceiling concealed type)

Provide a Service access for inspection purposes. 
Do not place any wiring or illumination in the service space, as they will impede service.

Installation Dimensions

Left 
side

Strong and durable ceiling

Indoor unit

Right 
side

150 mm 
or more 

400 mm 
or more

Service access

Ceiling

2500 mm or more

(When no ceiling)

Floor

240 mm or more

20 mm or more

20 mm or more

300 mm or more

Adjust the wind direction in the room depending on the shape of blow out opening.

Service access

Unit

Control 
box

400 mm or 
more

100 mm 

or more

300 mm 

or more

Service space

3.2B.  Installation dimensions (Wall mounted type/Floor 

standing concealed type)

The wall mounted type/fl oor standing concealed type requires a temperature correction 
setting. Perform this in “7.3. Function setting ”.

Strong and 

durable floor

10 mm or 
less

Left side

Left side

150 mm 
or more

150 mm 
or more

150 mm or 
more

150 mm 
or more

150 mm 
or more

150 mm 
or more

20 mm 
or more

20 mm 
or more

20 mm or 
more

20 mm 
or more

400 mm 
or more

400 mm 
or more

Inlet air

Inlet air

Strong and 
durable floor

Strong and 
durable floor

10 mm or 
less

Right side 
(PIPE side)

Right side 
(PIPE side)

Grille

Duct

Grille

Strong and 

durable floor

3.3A. Installation the unit (Ceiling concealed type)

 

WARNING

Install the air conditioner in a location which can withstand a load do at least 5 times the 
weight of the main unit and which will not amplify sound or vibration. If the installation 
location is not strong enough, the indoor unit may fall and cause injuries.

If the job is done with the panel frame only, there is a risk that the unit will come loose. 
Please take care.

3.3A.1. UNIT INSTALLATION EXAMPLE (CEILING CONCEALED 

TYPE)

Connect the locally purchased duct.

(1) Inlet side
•  Connect the duct to the locally purchased inlet fl ange.
•  Connect the fl ange to the body with the locally purchased tapping screws.
•  Wind the inlet fl ange connecting to the duct with the aluminum tape etc. to avoid the 

air discharge.

 

CAUTION

When the duct is connected to inlet side, remove contained fi lter and surely attach 
locally purchased fi lter at inlet opening.

(2) Outlet side
•  Connect the duct with adjusting inside of outlet fl ange.
•  Wind the outlet fl ange connecting to the duct with the aluminum tape etc. to avoid the 

air discharge.

•  Insulate the duct to avoid the dew condensation.

 

CAUTION

Check that duct work does not exceed the range of external static pressure of 
equipment.  

Make sure to insulate ducts to avoid the dew condensation.

Make sure to insulate between ducts and walls if metal ducts are used.

Please explain handling and washing methods of locally purchased materials to the 
customer.

To prevent people from touching the parts inside the unit, be sure to install grilles on 
the inlet and outlet ports. The grilles must be designed in such a way that cannot be 
removed without tools.

When connecting the duct to the outlet port of the indoor unit, be sure to insulate the 
outlet port and the installation screws to prevent water from leaking around the port.

Set the static pressure outside the unit to 90 Pa or less (the allowable range is between 
0 and 90 Pa.)

9374342235-02_IM.indb   4

4/2/2012   2:35:36 PM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for ARYG18LLTB

Page 1: ...ΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύπος αγωγού Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό EλληvIkά РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙ МОДУЛЬ Канального типа Только для авторизованного обслуживающего персонала Русский MANUALE DI INSTALLAZIONE UNITÀ INTERNA Tipo di condotto Ad uso esclusivo del personale tecnico autorizzato Italiano MANUAL DE INSTALAÇÃO UNIDADE INTERIOR Tipo conduta Apenas pa...

Page 2: ...crease pressure resistance the hose material and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 1 SAFETY PRECAUTIONS Be sure to read this Manual thoroughly before installation The warnings and precautions indicated in this Manual contain important information p...

Page 3: ...g an installation location Especially the installation place is very important for the split type air conditioner be cause it is very difficult to move from place to place after the first installation WARNING Select installation locations that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install the unit in the following...

Page 4: ...air Inlet air Strong and durable floor Strong and durable floor 10 mm or less Right side PIPE side Right side PIPE side Grille Duct Grille Strong and durable floor 3 3A Installation the unit Ceiling concealed type WARNING Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installa...

Page 5: ...0 12000 14000 Btu h 18000 Btu h A 650 mm 850 mm B P200 2 400 mm P200 3 600 mm CAUTION Be sure to install the air inlet grille and the air outlet grille for air circulation The correct temperature cannot be detected Grills must be fixed so that man cannot touch indoor unit fan and exchanger and cannot be removed by only hand operation without tool Be sure to install the air filter in the air inlet ...

Page 6: ...sure to insulate between ducts and walls if metal ducts are used Please explain handling and washing methods of locally purchased materials to the customer To prevent people from touching the parts inside the unit be sure to install grilles on the inlet and outlet ports The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of th...

Page 7: ...h contaminants Improper pipe selection will degrade performance As an air conditioner using R410A incurs pressure higher than when using conventional refrigerant it is necessary to choose adequate materials Thicknesses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are available on the market Thicknesses of An...

Page 8: ...re nuts could break after a prolonged period causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a flame Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by...

Page 9: ...leeding Provide a downward gradient 1 100 or more Provide supporters when long pipes are installed Use an insulation material as needed to prevent the pipes from freezing Install the pipes in a way that allows for the removal of the control box 1 Ceiling concealed type Gap of 1 5 to 2 m 100 mm or more Downward gradient 2 5 5 0 mm Supporter Locally arranged pipe GOOD VP25 O D 32 mm or more Air blee...

Page 10: ...AUTION To prevent excessive force on Drain hose 1 avoid bends or twists To bend or twist may cause water leaks 4 After checking for drainage attach the Drain hose insulation B 3 to insulate following the instructions as in the figures To avoid space with Drain hose 1 and Hose band 2 press firmly the Drain hose insulation B 3 3 Drain hose insulation B Ensure there is no space STEP1 STEP3 Butt the i...

Page 11: ...nditioner can be operated safely and positively Connect the connection cable firmly to the terminal board Imperfect installation may cause a fire CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shock Install the remote controller cables so as not to be direct ...

Page 12: ...in 18 22 24 type only Connection cable Indoor unit Primary Indoor unit Secondary J u n c t i o n b o x Local purchase Outdoor unit Earth Ground line Control line Power line Earth Ground line Wired remote controller cable Indoor unit Primary Indoor unit Secondary Wired remote controller Remote controller cable Bus wire Local purchase Red White Black Earth Ground the remote controller if it has a ea...

Page 13: ...d will occur even if the air conditioner is running normally Locate where an average temperature for the room being air conditioned will be sensed Do not locate directly exposed to the outlet air from the air conditioner Locate out of direct sunlight Locate away from the influence of other heat sources Do not touch the remote controller PC board and PC board parts directly with your hands Do not w...

Page 14: ...lidity Validity Memory backup setting Set to ON to use batteries for the memory backup If batteries are not used all of the settings stored in memory will be deleted if there is a power failure Factory setting 7 3 Function setting This procedure changes the function settings used to control the indoor unit according to the installation conditions Incorrect settings can cause the indoor unit to mal...

Page 15: ... require a cor rection The settings may be selected as shown in the table below Factory setting Setting description Function number Setting value Standard 30 00 Slightly lower control 01 Lower control 02 Warmer control 03 When using floor console installation change the setting value to 01 4 Heating room temperature correction Depending on the installed environment the room temperature sensor may ...

Page 16: ...s pressed 7 4 Jumper wire setting 1 Drainage function setting JM1 If contained drain pump is not used set the drainage function to Invalid in the drainage function switching If contained drain pump is not use When used under WALL MOUNTED TYPE FLOOR STANDING CONCEALED TYPE When used in natural drainage under CEILING CONCEALED TYPE Factory setting JM1 Drainage function Connect Valid Disconnect Inval...

Page 17: ...ry Triple type 18 type only 00 01 02 00 01 01 R C address Primary Secondary setting DIP switch setting Function number 51 Out door unit Remote controller Transmission cable Power supply cable Power supply cable Bus wire Remote controller cable Indoor unit 1 Primary Indoor unit 2 Secondary Indoor unit 3 Secondary 7 5 2 Group control system CAUTION Group control cannot be used when using it by the f...

Page 18: ...ss setting Primary Secondary setting DIP switch setting Function number 02 Function number 51 Remote controller Transmission cable Power supply cable Power supply cable Bus wire Remote controller cable Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 Outdoor unit 4 Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7 7 5 3 Dual remote controllers 2 separate...

Page 19: ...fer to 6 ELECTRICAL WIRING and 7 REMOTE CONTROLLER SETTING 9 2 External input and external output Connection methods Wire modification Use a tool to cut off the terminal on the end of the wire and then remove the insulation from the cut end of the wire Connect the wire with connecting wire with solder Important Be sure to insulate the connection between the wires Connection terminals Output termin...

Page 20: ... cable insulation after opening a knockout hole remove any burrs from the edge of the hole 10 CUSTOMER GUIDANCE Explain the following to the customer in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote controller operations 2 Air filter removal and cleaning and how to use the air louvers 3 Give ...

Page 21: ...temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor error Sub cool Heat Ex gas outlet temp sensor error 8 3 Liquid pipe temp sensor error 8 4 Current sensor error 8 6 Discharge pressure sensor error Suction pressure sensor error High pressure switch error 9 4 T...