2. 3.  Pipe requirement

 CAUTION

Refer to the installation manual of the outdoor unit for description of the length of con-
necting pipe or for difference of its elevation.

Model

Diameter [mm (in)]

Gas pipe

Liquid pipe

12/14

9.52 (3/8)

6.35 (1/4)

18/22/24

12.70 (1/2)

6.35 (1/4)

30/36/45/54

15.88 (5/8)

9.52 (3/8)

•  Use pipe with water-resistant heat insulation.

 CAUTION

•  Wrap heat insulation around both gas pipe and liquid pipe.  

No heat-insulation work or incorrect heat-insulation work may cause water leaks.

•  In a reverse cycle model, use heat insulation with heat resistance above 120 °C.
•  If expected humidity of the installation location of refrigerant pipes is higher than 

70 %, wrap the heat insulation around the refrigerant pipes. 
If the expected humidity is between 70 % and 80 %, use heat insulation that has 
a thickness of 15 mm or more. 
If the expected humidity is higher than 80 %, use heat insulation that has a 
thickness of 20 mm or more.

•  The use of thinner heat insulation than speci

fi

 ed above, may cause a condensation 

on the surface of the insulation.  

•  Use heat insulation with thermal conductivity of 0.045 W/(m•K) or less, at 20 °C.

2. 4.   Electrical requirement

The indoor unit is powered from the outdoor unit. Do not power indoor unit from separate 
power source.

 WARNING

Standard for electrical wiring and equipment differs in each country or region. Before 
you start electrical working, con

fi

 rm related regulations, codes, or standards.

Cable

Conductor size 

(mm

2

)

Type

Remarks

Connection cable

1.5 (MIN.)

Type 60245 IEC57

3Wire+Earth (Ground), 

1

φ

 230V

Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage drop is 
2% or more.

Cable

Conductor size 

(mm

2

)

Type

Remarks

Remote controller 
cable
(2-wire type)

0.33 to 1.25

Sheathed PVC 

cable

Non-polar 2-wired, 

twisted pair

Remote controller 
cable 
(3-wire type)

0.33

Sheathed PVC 

cable

Polar 3-wired

2. 5.   Optional parts

Refer to each installation manual for the method of installing optional parts.

Parts name

Model No.

Application

Wired remote controller

UTY-RNR

Z

For air conditioner operation
(2-wired type)

UTY-RLR

UTY-RVN

M

For air conditioner operation
(3-wired type)

UTY-RNN

M

W-LAN interface

UTY-TFSXZ1

For wireless LAN control

IR receiver unit

UTY-LBT

M

For air conditioner operation

Remote sensor

UTY-XSZX

Room temperature sensor

External input and output 
PCB

UTY-XCSX

For connecting external 
devices

External input and output 
PCB bracket

UTZ-GXNA

For installing the External input 
and output PCB

External connect kit

UTY-XWZXZG

For control output port

Air 

fi

 lter kit

UTD-LFNA/B/C

LFNA : 36/45/54 model
LFNB : 18/22/24/30 model
LFNC : 12/14 model

3. INSTALLATION WORK

 WARNING

• Do not turn on the power until all installation work is complete.
•  Carrying and installation of the unit should be performed by a suf

fi

 cient number of 

people and with suf

fi

 cient equipment that is adequate for the weight of the unit.

Performing such work with an insuf

fi

 cient number of people or with inadequate equip-

ment could result in dropping of the unit or personal injury.

 CAUTION

For installation details, refer to the technical data.

3. 1.  Selecting an installation location

Decide the mounting position together with the customer as follows.

 WARNING

Install the indoor unit where is capable to support the weight of the unit. Secure the 
unit 

fi

 rmly so that the unit does not topple or fall.

 CAUTION

Do not install the unit in the following areas:

 

–  Area with high salt content, such as at the seaside. It will deteriorate metal parts, 

causing the parts to fail or the unit to leak water.

 

–  Area 

fi

 lled with mineral oil or containing a large amount of splashed oil or steam, 

such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit 
to leak water. 

 

–  Area where is close to heat sources. 

 

–  Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to 
corrode, which can cause refrigerant leakage.

 

–  Area that can cause combustible gas to leak, contains suspended carbon 

fi

 bers or 

fl

 ammable dust, or volatile in 

fl

 ammables such as paint thinner or gasoline.

 

–  If gas leaks and settles around the unit, it can cause a 

fi

 re.

 

–  Area where animals may urinate on the unit or ammonia may be generated.

•   Do not use the unit for special purposes, such as storing food, raising animals, grow-

ing plants, or preserving precision devices or art objects. It can degrade the quality of 

the preserved or stored objects.

•  Install the unit where drainage does not cause any trouble.

•  Install the indoor unit, outdoor unit, power supply cable, transmission cable, and re-

mote control cable at least 1 m away from a television or radio receivers. The purpose 

of this is to prevent TV reception interference or radio noise.

(Even if they are installed more than 1 m apart, you could still receive noise under 

some signal conditions.)

•  If children under 10 years old may approach the unit, take preventive measures so that 

they cannot reach the unit.

•  Install the unit where ambient temperature does not reach 60°C or more. 

Take a measure such as ventilation for an environment in which heat is retained.

(1)  The inlet and outlet ports should not be obstructed; the air should be able to blow all 

over the room.

(2)  Leave the space required to service the air conditioner.
(3) Install the unit where connection to the outdoor unit is easy.
(4)  Install the unit where the connection pipe can be easily installed.
(5)  Install the unit where the drain pipe can be easily installed.
(6) Install the unit where noise and vibrations are not ampli

fi

 ed.

(7) Take servicing, etc., into consideration and leave the spaces. Also install the unit where 

the 

fi

 lter can be removed.

(8)  Do not install the unit where it will be exposed to direct sunlight. 

Correct initial installation location is important because it is dif

fi

 cult to move unit after it is 

installed.

9381386215-01_IM.indb   5

9381386215-01_IM.indb   5

12/5/2018   2:57:36 PM

12/5/2018   2:57:36 PM

Summary of Contents for ARXG-KHTAP Series

Page 1: ...lation must be performed in accordance with regulations codes or standards for electrical wiring and equipment in each country region or the installation place Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or ...

Page 2: ...ance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Servicing shall be performed only as recommended by the manufacturer 2 2 Work Prior ...

Page 3: ...nce to electrical components shall include initial safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be con nected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is necessary to continue operation an adequate temporary solution shall be used This shall be reporte...

Page 4: ...ure 0 1 to 3 8 MPa 1 to 38 bar for low pressure Charge hose To increase pressure resistance the hose material and base size were changed R32 R410A Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Use of a vacuum pump with a series motor is prohibited Gas leakage detector Special gas leakage detector for HFC refrigerant R410A or R32 Copper pipes It is necessary...

Page 5: ...g such work with an insufficient number of people or with inadequate equip ment could result in dropping of the unit or personal injury CAUTION For installation details refer to the technical data 3 1 Selecting an installation location Decide the mounting position together with the customer as follows WARNING Install the indoor unit where is capable to support the weight of the unit Secure the uni...

Page 6: ...ent could result in dropping of the unit or personal injury If the job is done with the panel frame only there is a risk that the unit will come loose Please take care When fastening the hangers make the bolt positions uniform CAUTION Confirm the directions of the air intake and outlet before installing the unit The unit takes in air from the evaporator side and expels it from the fan side 3 3 1 P...

Page 7: ...pply Room Duct Field supply When connecting the duct perform duct insulation appropriate for the installing environment Inappropriate insulation work may cause condensation on the surface of the insulat ing material and may lead to condensation dripping 3 5 Drain installation CAUTION Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enoug...

Page 8: ...ing installation make sure that the refrigerant pipe is attached firmly before you run the compressor Do not operate the compressor under the condition of refrigerant piping not attached properly with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury During the pump down operation make sure that the compressor is turned off...

Page 9: ...are nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 1 Detach the caps and plugs from the pipes 2 Centering t...

Page 10: ... ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shocks Do not connect power supply cables to the transmission or remote control terminals as this will damage the product Never bundle the power supply cable and transmission cable together Bundling these cables together will cause miss operation When handling PCB s...

Page 11: ...ternal in out PCB CN47 External out This air conditioner can be connected with the following optional kits For details on how to install optional parts refer to the installation manual included in each item Connector No Option type CN48 IR Receiver UTY LBT M CN8 Remote sensor UTY XSZX CN47 1 Connect wire UTY XWZXZG CN65 2 External input and output PCB UTY XCSX 1 For external output terminal settin...

Page 12: ... is used The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry Setting for room temperature correction When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 30 Room temperature control for cooling to 00 Set Function Number 31 Room temperature control for heating to 01 5 REMO...

Page 13: ...on details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Function Number Setting Value Setting Description 11 00 Standard 2500 hours 01 Long interval 4400 hours 02 Short interval 1250 hours 03 No indication Room temp...

Page 14: ... outdoor unit is stopped the indoor unit fan operates intermittently at a very low speed 02 Enable or disable this function by remote controller setting When using a wired remote controller without Indoor unit fan control for energy saving for cooling function or when connecting a single split converter the setting cannot be made by using the remote controller Set to 00 or 01 To confirm if the rem...

Page 15: ...unded Is the connection cable the specified thickness Are the inlets and outlets free of any obstacles After installation is completed has the proper operation and handling been explained to the user Operate the unit according to the operating manual provided and check that it is operating normally 8 TEST RUN 8 1 Check items Is operation of each button on the remote control unit normal Does each l...

Page 16: ...ed remote controller error 4 1 Room temp sensor error 4 2 Indoor unit heat ex middle temp sensor error 4 4 Human sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 1 Outdoor unit reverse missing phase and wiring error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 6 2 Ou...

Reviews: