background image

En-3

 CAUTION

8-Removal and evacuation

•  When breaking into the refrigerant circuit to make repairs – or for any other 

purpose –conventional procedures shall be used. 
However, it is important that best practice is followed since 

fl

 ammability is a consid-

eration. 
The following procedure shall be adhered to:

• remove refrigerant
•  purge the circuit with inert gas
• evacuate
•  purge again with inert gas
•  open the circuit by cutting or brazing

•  The refrigerant charge shall be recovered into the correct recovery cylinders. 
•  The system shall be “

fl

 ushed” with OFN to render the unit safe. 

•  This process may need to be repeated several times. 
•  Compressed air or oxygen shall not be used for this task.
•  Flushing shall be achieved by breaking the vacuum in the system with OFN and 

continuing to 

fi

 ll until the working pressure is achieved, then venting to atmosphere, 

and 

fi

 nally pulling down to a vacuum. 

•  This process shall be repeated until no refrigerant is within the system. 
• When the 

fi

 nal OFN charge is used, the system shall be vented down to atmospheric 

pressure to enable work to take place.

•  This operation is absolutely vital if brazing operations on the pipe work are to take 

place.

•  Ensure that the outlet for the vacuum pump is not close to any ignition sources and 

there is ventilation available.

9-Charging procedures

•  In addition to conventional charging procedures, the following requirements shall be 

followed.

-  Ensure that contamination of different refrigerants does not occur when using 

charging equipment. 
 Hoses or lines shall be as short as possible to minimize the amount of refrigerant 
contained in them.

-  Cylinders shall be kept upright.
-  Ensure that the refrigeration system is earthed prior to charging the system with 

refrigerant.

-  Label the system when charging is complete (if not already).
-  Extreme care shall be taken not to over

fi

 ll the refrigeration system.

•  Prior to recharging the system it shall be pressure tested with OFN. 
•  The system shall be leak tested on completion of charging but prior to commission-

ing. 

•  A follow up leak test shall be carried out prior to leaving the site.

10-Decommissioning

•  Before carrying out this procedure, it is essential that the technician is completely 

familiar with the equipment and all its details.

•  It is recommended good practice that all refrigerants are recovered safely.
•  Prior to the task being carried out, an oil and refrigerant sample shall be taken in 

case analysis is required prior to re-use of reclaimed refrigerant.

•  It is essential that electrical power is available before the task is commenced.

a)  Become familiar with the equipment and its operation.
b)  Isolate system electrically.
c)  Before attempting the procedure ensure that:

•  mechanical handling equipment is available, if required, for handling refriger-

ant cylinders;

•  all personal protective equipment is available and being used correctly; 
•  the recovery process is supervised at all times by a competent person; 
•  recovery equipment and cylinders conform to the appropriate standards.

d)  Pump down refrigerant system, if possible.
e)  If a vacuum is not possible, make a manifold so that refrigerant can be removed 

from various parts of the system.

f)   Make sure that cylinder is situated on the scales before recovery takes place.
g)  Start the recovery machine and operate in accordance with manufacturer’s 

instructions.

h)  Do not over

fi

 ll cylinders. (No more than 80 % volume liquid charge).

i)   Do not exceed the maximum working pressure of the cylinder, even temporarily.
j)   When the cylinders have been 

fi

 lled correctly and the process completed, make 

sure that the cylinders and the equipment are removed from site promptly and all 
isolation valves on the equipment are closed off.

k)  Recovered refrigerant shall not be charged into another refrigeration system un-

less it has been cleaned and checked.

11-Labelling

•  Equipment shall be labelled stating that it has been de-commissioned and emptied 

of refrigerant. 

•  The label shall be dated and signed. 
•  Ensure that there are labels on the equipment stating the equipment contains 

fl

 am-

mable refrigerant.

 CAUTION

2-8 Checks to electrical devices

•  Repair and maintenance to electrical components shall include initial safety checks 

and component inspection procedures.

•  If a fault exists that could compromise safety, then no electrical supply shall be con-

nected to the circuit until it is satisfactorily dealt with.

•  If the fault cannot be corrected immediately but it is necessary to continue operation, 

an adequate temporary solution shall be used.

•  This shall be reported to the owner of the equipment so all parties are advised.
•  Initial safety checks shall include.

-  That capacitors are discharged: this shall be done in a safe manner to avoid pos-

sibility of sparking.

-  That there no live electrical components and wiring are exposed while charging, 

recovering or purging the system.

-  That there is continuity of earth bonding.

3-Repairs to sealed components

•  During repairs to sealed components, all electrical supplies shall be disconnected 

from the equipment being worked upon prior to any removal of sealed covers, etc.

•  If it is absolutely necessary to have an electrical supply to equipment during servic-

ing, then a permanently operating form of leak detection shall be located at the most 
critical point to warn of a potentially hazardous situation.

•  Particular attention shall be paid to the following to ensure that by working on electri-

cal components, the casing is not altered in such a way that the level of protection is 
affected.

•  This shall include damage to cables, excessive number of connections, terminals not 

made to original speci

fi

 cation, damage to seals, incorrect 

fi

 tting of glands, etc.

•  Ensure that apparatus is mounted securely.
•  Ensure that seals or sealing materials have not degraded such that they no longer 

serve the purpose of preventing the ingress of 

fl

 ammable atmospheres.

•  Replacement parts shall be in accordance with the manufacturer’s speci

fi

 cations.

NOTE:   The use of silicon sealant may inhibit the effectiveness of some types of leak 

detection equipment.
Intrinsically safe components do not have to be isolated prior to working on 
them.

4-Repair to intrinsically safe components

•  Do not apply any permanent inductive or capacitance loads to the circuit without 

ensuring that this will not exceed the permissible voltage and current permitted for 
the equipment in use.

•  Intrinsically safe components are the only types that can be worked on while live in 

the presence of a 

fl

 ammable atmosphere. 

•  The test apparatus shall be at the correct rating.
•  Replace components only with parts speci

fi

 ed by the manufacturer.

•  Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

5-Cabling

•  Check that cabling will not be subject to wear, corrosion, excessive pressure, vibra-

tion, sharp edges or any other adverse environmental effects.

•  The check shall also take into account the effects of aging or continual vibration from 

sources such as compressors or fans.

6-Detection of 

fl

 ammable refrigerants

•  Under no circumstances shall potential sources of ignition be used in the searching 

for or detection of refrigerant leaks.

•  A halide torch (or any other detector using a naked 

fl

 ame) shall not be used.

7-Leak detection methods

•  Electronic leak detectors shall be used to detect 

fl

 ammable refrigerants, but the 

sensitivity may not be adequate, or may need re-calibration. (Detection equipment 
shall be calibrated in a refrigerant-free area.)

•  Ensure that the detector is not a potential source of ignition and is suitable for the 

refrigerant used.

•  Leak detection equipment shall be set at a percentage of the LFL of the refrigerant 

and shall be calibrated to the refrigerant employed and the appropriate percentage of 
gas (25 % maximum) is con

fi

 rmed.

• Leak detection 

fl

 uids are suitable for use with most refrigerants but the use of 

detergents containing chlorine shall be avoided as the chlorine may react with the 
refrigerant and corrode the copper pipe-work.

•  If a leak is suspected, all naked 

fl

 ames shall be removed/extinguished.

•  If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall 

be recovered from the system, or isolated (by means of shut off valves) in a part of 
the system remote from the leak. 
Oxygen free nitrogen (OFN) shall then be purged through the system both before 
and during the brazing process.

9381386215-01_IM.indb   3

9381386215-01_IM.indb   3

12/5/2018   2:57:35 PM

12/5/2018   2:57:35 PM

Summary of Contents for ARXG-KHTAP Series

Page 1: ...lation must be performed in accordance with regulations codes or standards for electrical wiring and equipment in each country region or the installation place Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or ...

Page 2: ...ance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Servicing shall be performed only as recommended by the manufacturer 2 2 Work Prior ...

Page 3: ...nce to electrical components shall include initial safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be con nected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is necessary to continue operation an adequate temporary solution shall be used This shall be reporte...

Page 4: ...ure 0 1 to 3 8 MPa 1 to 38 bar for low pressure Charge hose To increase pressure resistance the hose material and base size were changed R32 R410A Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Use of a vacuum pump with a series motor is prohibited Gas leakage detector Special gas leakage detector for HFC refrigerant R410A or R32 Copper pipes It is necessary...

Page 5: ...g such work with an insufficient number of people or with inadequate equip ment could result in dropping of the unit or personal injury CAUTION For installation details refer to the technical data 3 1 Selecting an installation location Decide the mounting position together with the customer as follows WARNING Install the indoor unit where is capable to support the weight of the unit Secure the uni...

Page 6: ...ent could result in dropping of the unit or personal injury If the job is done with the panel frame only there is a risk that the unit will come loose Please take care When fastening the hangers make the bolt positions uniform CAUTION Confirm the directions of the air intake and outlet before installing the unit The unit takes in air from the evaporator side and expels it from the fan side 3 3 1 P...

Page 7: ...pply Room Duct Field supply When connecting the duct perform duct insulation appropriate for the installing environment Inappropriate insulation work may cause condensation on the surface of the insulat ing material and may lead to condensation dripping 3 5 Drain installation CAUTION Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enoug...

Page 8: ...ing installation make sure that the refrigerant pipe is attached firmly before you run the compressor Do not operate the compressor under the condition of refrigerant piping not attached properly with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury During the pump down operation make sure that the compressor is turned off...

Page 9: ...are nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 1 Detach the caps and plugs from the pipes 2 Centering t...

Page 10: ... ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shocks Do not connect power supply cables to the transmission or remote control terminals as this will damage the product Never bundle the power supply cable and transmission cable together Bundling these cables together will cause miss operation When handling PCB s...

Page 11: ...ternal in out PCB CN47 External out This air conditioner can be connected with the following optional kits For details on how to install optional parts refer to the installation manual included in each item Connector No Option type CN48 IR Receiver UTY LBT M CN8 Remote sensor UTY XSZX CN47 1 Connect wire UTY XWZXZG CN65 2 External input and output PCB UTY XCSX 1 For external output terminal settin...

Page 12: ... is used The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry Setting for room temperature correction When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 30 Room temperature control for cooling to 00 Set Function Number 31 Room temperature control for heating to 01 5 REMO...

Page 13: ...on details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Function Number Setting Value Setting Description 11 00 Standard 2500 hours 01 Long interval 4400 hours 02 Short interval 1250 hours 03 No indication Room temp...

Page 14: ... outdoor unit is stopped the indoor unit fan operates intermittently at a very low speed 02 Enable or disable this function by remote controller setting When using a wired remote controller without Indoor unit fan control for energy saving for cooling function or when connecting a single split converter the setting cannot be made by using the remote controller Set to 00 or 01 To confirm if the rem...

Page 15: ...unded Is the connection cable the specified thickness Are the inlets and outlets free of any obstacles After installation is completed has the proper operation and handling been explained to the user Operate the unit according to the operating manual provided and check that it is operating normally 8 TEST RUN 8 1 Check items Is operation of each button on the remote control unit normal Does each l...

Page 16: ...ed remote controller error 4 1 Room temp sensor error 4 2 Indoor unit heat ex middle temp sensor error 4 4 Human sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 1 Outdoor unit reverse missing phase and wiring error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 6 2 Ou...

Reviews: