3. 8.  Electrical wiring

 WARNING

• Electrical work must be performed in accordance with this Manual by a person 

certi

fi

 ed under the national or regional regulations. Be sure to use a dedicated circuit 

for the unit. 
An insuf

fi

 cient power supply circuit or improperly performed electrical work can cause 

serious accidents such as electric shock or 

fi

 re.

• Before starting work, check that power is not being supplied to the indoor unit and 

outdoor unit.

• Use the included connection cables and power cables or ones speci

fi

 ed by the 

manufacturer. Improper connections, insuf

fi

 cient insulation, or exceeding the 

allowable current can cause electric shock or 

fi

 re.

• For wiring, use the prescribed type of cables, connect them securely, making sure 

that there are no external forces of the cables applied to the terminal connections. 
Improperly connected or secured cables can cause serious accidents such as 
overheating the terminals, electric shock, or 

fi

 re.

• Do not modify the power cables, use extension cables, or use any branches in the 

wiring. Improper connections, insuf

fi

 cient insulation, or exceeding the allowable 

current can cause electric shock or 

fi

 re.

• Match the terminal board numbers and connection cable colors with those of the 

outdoor unit. Erroneous wiring may cause burning of the electric parts.

• Securely connect the connection cables to the terminal board. In addition, secure the 

cables with wiring holders. Improper connections, either in the wiring or at the ends of 
the wiring, can cause a malfunction, electric shock, or 

fi

 re.

• Always fasten the outside covering of the connection cable with the cable clamp. (If 

the insulator is chafed, electric leakage may occur.)

• Securely install the electrical box cover on the unit. An improperly installed electrical 

box cover can cause serious accidents such as electric shock or 

fi

 re through 

exposure to dust or water.

• Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 

could result.

• Install a ground leakage breaker. In addition, install the ground leakage breaker so 

that the entire AC main power supply is cut off at the same time. Otherwise, electric 
shock or 

fi

 re could result.

• Always connect the earth (ground) cable.

Improper earthing (grounding) work can cause electric shocks.

• Install the remote control cables so as not to be touched directly with your hand.
• Perform wiring work in accordance with standards so that the air conditioner can be 

operated safely and positively.

• Connect the connection cable 

fi

 rmly to the terminal board. Imperfect installation may 

cause a 

fi

 re.

 CAUTION

• Ground the unit.  

Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 
telephone earth (ground) cable. 
Improper earthing (grounding) may cause electric shocks.

• Do not connect power supply cables to the transmission or remote control terminals, 

as this will damage the product.

• Never bundle the power supply cable and transmission cable together. Bundling 

these cables together will cause miss operation.

• When handling PCB, static electricity charged in the body may cause malfunction of 

the PCB. Follow the cautions below:

 

– Establish a ground for the indoor and outdoor units and peripheral devices.

 

– Cut power (breaker) off.

 

– Touch metal part of the indoor and outdoor units for more than 10 seconds to dis-

charge static electricity charged in the body.

 

– Do not touch terminals of parts and patterns implemented on PCB.

3. 8. 1.  Wiring system diagram

 

Connection cable (to outdoor unit)

Earth (ground)

Power line

Control line

 

Wired remote controller cable

Red

White

2-wire type

or

3-wire type

Red

White
Black

3. 8. 2.  Connection cable preparation

 

Connection cable

 

Earth (ground) wire

Connection cable

Keep the earth (ground) wire longer than the other wires.

• Use a 4-core wire cable.

30 mm

70 mm or more

 

Remote controller cable

For 2-wire type

For 3-wire type

30 mm

30 mm

3. 8. 3.  How to connect wiring to the terminals. 

(1)  Use ring terminals with insulating sleeves as shown in the 

fi

 gure below to connect to 

the terminal block.

(2)  Securely crimp the ring terminals to the wires using an appropriate tool so that the 

wires do not come loose.

 

Strip 10 mm

Ring 
terminal

Sleeve

(3) Use the speci

fi

 ed wires, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws.

Do not use a screwdriver that is too small, otherwise, the screw heads may be 
damaged and prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(6)  See the table below for the terminal screw tightening torques.

 WARNING

Use ring terminals and tighten the terminal screws to the speci

fi

 ed torques, otherwise, 

abnormal overheating may be produced and possibly cause serious damage inside the 
unit.

Tightening torque [N·m (kgf·cm)]

M4 screw

1.2 to 1.8 (12 to 18)

M5 screw

2.0 to 3.0 (20 to 30)

Screw with 
special washer

Ring 
terminal

Terminal blocks

Wire

Wire

Screw with 
special 
washer

Ring 
terminal

3. 8. 4.  Connection wiring

 CAUTION

• Be careful not to mistake the power supply cable and connection wires when 

installing.

• Install so that the wires for the remote controller will not come in contact with other 

connection wires.

(1)  Remove the control box cover and install each connection wire.

Control box cover

Loosen the screws.(3 locations)

9381386215-01_IM.indb   10

9381386215-01_IM.indb   10

12/5/2018   2:57:36 PM

12/5/2018   2:57:36 PM

Summary of Contents for ARXG-KHTAP Series

Page 1: ...lation must be performed in accordance with regulations codes or standards for electrical wiring and equipment in each country region or the installation place Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or ...

Page 2: ...ance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Servicing shall be performed only as recommended by the manufacturer 2 2 Work Prior ...

Page 3: ...nce to electrical components shall include initial safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be con nected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is necessary to continue operation an adequate temporary solution shall be used This shall be reporte...

Page 4: ...ure 0 1 to 3 8 MPa 1 to 38 bar for low pressure Charge hose To increase pressure resistance the hose material and base size were changed R32 R410A Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Use of a vacuum pump with a series motor is prohibited Gas leakage detector Special gas leakage detector for HFC refrigerant R410A or R32 Copper pipes It is necessary...

Page 5: ...g such work with an insufficient number of people or with inadequate equip ment could result in dropping of the unit or personal injury CAUTION For installation details refer to the technical data 3 1 Selecting an installation location Decide the mounting position together with the customer as follows WARNING Install the indoor unit where is capable to support the weight of the unit Secure the uni...

Page 6: ...ent could result in dropping of the unit or personal injury If the job is done with the panel frame only there is a risk that the unit will come loose Please take care When fastening the hangers make the bolt positions uniform CAUTION Confirm the directions of the air intake and outlet before installing the unit The unit takes in air from the evaporator side and expels it from the fan side 3 3 1 P...

Page 7: ...pply Room Duct Field supply When connecting the duct perform duct insulation appropriate for the installing environment Inappropriate insulation work may cause condensation on the surface of the insulat ing material and may lead to condensation dripping 3 5 Drain installation CAUTION Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enoug...

Page 8: ...ing installation make sure that the refrigerant pipe is attached firmly before you run the compressor Do not operate the compressor under the condition of refrigerant piping not attached properly with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury During the pump down operation make sure that the compressor is turned off...

Page 9: ...are nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 1 Detach the caps and plugs from the pipes 2 Centering t...

Page 10: ... ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shocks Do not connect power supply cables to the transmission or remote control terminals as this will damage the product Never bundle the power supply cable and transmission cable together Bundling these cables together will cause miss operation When handling PCB s...

Page 11: ...ternal in out PCB CN47 External out This air conditioner can be connected with the following optional kits For details on how to install optional parts refer to the installation manual included in each item Connector No Option type CN48 IR Receiver UTY LBT M CN8 Remote sensor UTY XSZX CN47 1 Connect wire UTY XWZXZG CN65 2 External input and output PCB UTY XCSX 1 For external output terminal settin...

Page 12: ... is used The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry Setting for room temperature correction When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 30 Room temperature control for cooling to 00 Set Function Number 31 Room temperature control for heating to 01 5 REMO...

Page 13: ...on details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Function Number Setting Value Setting Description 11 00 Standard 2500 hours 01 Long interval 4400 hours 02 Short interval 1250 hours 03 No indication Room temp...

Page 14: ... outdoor unit is stopped the indoor unit fan operates intermittently at a very low speed 02 Enable or disable this function by remote controller setting When using a wired remote controller without Indoor unit fan control for energy saving for cooling function or when connecting a single split converter the setting cannot be made by using the remote controller Set to 00 or 01 To confirm if the rem...

Page 15: ...unded Is the connection cable the specified thickness Are the inlets and outlets free of any obstacles After installation is completed has the proper operation and handling been explained to the user Operate the unit according to the operating manual provided and check that it is operating normally 8 TEST RUN 8 1 Check items Is operation of each button on the remote control unit normal Does each l...

Page 16: ...ed remote controller error 4 1 Room temp sensor error 4 2 Indoor unit heat ex middle temp sensor error 4 4 Human sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 1 Outdoor unit reverse missing phase and wiring error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 6 2 Ou...

Reviews: