Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : ASYA14LCC, ASYA18LCC
[Condition]
Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping
7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
ASYA14LCC
ASYA18LCC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
ASYA14LCC
ASYA18LCC
Measure the low pressure with the pressure meter at the service valve. Measure the
outdoor unit overall current with the current clamp meter at Power Cable.
0.8
0.9
1
1.1
1.2
1.3
1.4
15
20
25
30
35
In/Outdoor ambient temperature C
Outdoor
Low
P
ressure
(Mpa)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
3
3.5
4
4.5
15
20
25
30
35
In/Outdoor ambient temperature C
Outdoor
Total
Electric
Current
(A)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
0.7
0.8
0.9
1
1.1
1.2
1.3
15
20
25
30
35
In/Outdoor ambient temperature C
Outdoor
Low
Pressure
(Mpa)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
4
4.5
5
5.5
6
15
20
25
30
35
In/Outdoor ambient temperature C
Outdoor
Total
E
lectric
Current
(A)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
length
08-06
Summary of Contents for AOYR07LCC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 13: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 17: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 22: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 41: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 79: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 80: ...REPLACEMENT PARTS 09 01 Models ASYA07LCC ASYA09LCC INVERTER ...
Page 81: ...REPLACEMENT PARTS 09 02 Models ASYA07LCC ASYA09LCC ...
Page 82: ...REPLACEMENT PARTS 09 03 Models AOYR07LCC AOYR09LCC ...
Page 83: ...REPLACEMENT PARTS 09 04 Models AOYR07LCC AOYR09LCC ...
Page 84: ...REPLACEMENT PARTS 09 05 Models AOYR07LCC AOYR09LCC ...
Page 85: ...REPLACEMENT PARTS 09 06 Models ASYA12LCC INVERTER ...
Page 86: ...REPLACEMENT PARTS 09 07 Models ASYA12LCC ...
Page 87: ...REPLACEMENT PARTS 09 08 Models AOYR12LCC ...
Page 88: ...REPLACEMENT PARTS 09 09 Models ASYA14LCC ASYA18LCC INVERTER ...
Page 89: ...REPLACEMENT PARTS 09 10 Models ASYA14LCC ASYA18LCC ...
Page 90: ...REPLACEMENT PARTS 09 11 Models AOYR14LCC AOYR18LCC ...
Page 91: ...REPLACEMENT PARTS 09 12 Models AOYR14LCC AOYR18LCC ...
Page 92: ...REPLACEMENT PARTS 09 13 Models ASYB09LDC ASYB12LDC INVERTER ...
Page 93: ...REPLACEMENT PARTS 09 14 Models ASYB09LDC ASYB12LDC ...
Page 94: ...REPLACEMENT PARTS 09 15 Models AOYS09LDC AOYS12LDC ...
Page 96: ...Process Model AOYR07 09LCC Connection of leads to inverter assy REPLACEMENT PARTS 09 17 ...
Page 97: ...Process Model AOYR07 09LCC Shaping of leads to inverter assy REPLACEMENT PARTS 09 18 ...
Page 98: ...Model AOYR07 09LCC 09 19 ...
Page 103: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 108: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS09022006 FEB 2006 Printed in Japan ...