Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : ASYA07/09/12LCC
[Condition]
Ambient
temperature
Indoor 15 - 23degC, Outdoor 2 - 12degC
Refrigerant
amount
Standard amount
Piping
7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*9LSACW series
ASYA12LCC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*9LSACW series
ASYA12LCC
outdoor unit overall current with the current clamp meter at Power Cable.
1.8
2
2.2
2.4
2.6
2.8
3
0
5
10
15
outdoor ambient temparature C
High-pressure
of
outdoor
unit
MPa
15 C
20 C(Indoor inlet tempe)
23 C
3.00
3.50
4.00
4.50
0
5
10
15
outdoor ambient temparature C
Outdoor
total
electric
current
A
15 C
20 C(Indoor inlet temp)
23 C
length
08-03
2
2.2
2.4
2.6
2.8
3
3.2
3.4
0
2
4
6
8
10
12
14
Outdoor ambient temparature [degC]
High-pressure
of
outdoor
unit
[MPa]
15degC
20degC
(Indoor ambient temp. )
23degC
4
4.5
5
5.5
6
6.5
7
0
2
4
6
8
10
12
14
Outdoor ambient temparature [degC]
Outdoor
total
electric
current
[A]
15degC
20degC
(Indoor ambient temp. )
23degC
Summary of Contents for AOYR07LCC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 13: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 17: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 22: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 41: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 79: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 80: ...REPLACEMENT PARTS 09 01 Models ASYA07LCC ASYA09LCC INVERTER ...
Page 81: ...REPLACEMENT PARTS 09 02 Models ASYA07LCC ASYA09LCC ...
Page 82: ...REPLACEMENT PARTS 09 03 Models AOYR07LCC AOYR09LCC ...
Page 83: ...REPLACEMENT PARTS 09 04 Models AOYR07LCC AOYR09LCC ...
Page 84: ...REPLACEMENT PARTS 09 05 Models AOYR07LCC AOYR09LCC ...
Page 85: ...REPLACEMENT PARTS 09 06 Models ASYA12LCC INVERTER ...
Page 86: ...REPLACEMENT PARTS 09 07 Models ASYA12LCC ...
Page 87: ...REPLACEMENT PARTS 09 08 Models AOYR12LCC ...
Page 88: ...REPLACEMENT PARTS 09 09 Models ASYA14LCC ASYA18LCC INVERTER ...
Page 89: ...REPLACEMENT PARTS 09 10 Models ASYA14LCC ASYA18LCC ...
Page 90: ...REPLACEMENT PARTS 09 11 Models AOYR14LCC AOYR18LCC ...
Page 91: ...REPLACEMENT PARTS 09 12 Models AOYR14LCC AOYR18LCC ...
Page 92: ...REPLACEMENT PARTS 09 13 Models ASYB09LDC ASYB12LDC INVERTER ...
Page 93: ...REPLACEMENT PARTS 09 14 Models ASYB09LDC ASYB12LDC ...
Page 94: ...REPLACEMENT PARTS 09 15 Models AOYS09LDC AOYS12LDC ...
Page 96: ...Process Model AOYR07 09LCC Connection of leads to inverter assy REPLACEMENT PARTS 09 17 ...
Page 97: ...Process Model AOYR07 09LCC Shaping of leads to inverter assy REPLACEMENT PARTS 09 18 ...
Page 98: ...Model AOYR07 09LCC 09 19 ...
Page 103: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 108: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS09022006 FEB 2006 Printed in Japan ...