4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote cintrol, operation starts in the optimum
mode from amoung the HEATING, COOLING, DRY and MONITORING modes. During operation, the
optimum mode is automatically swiched in accordance with temperature changes. The temperature
can be set between 18°C and 30°C in 1°C steps.
.When operation starts, only the indoor and outdoor fans are operated for 1 minute. After 1 minute,
the room temperature and outside air temperature are sensed and the operation mode is
selected in accordance with the table below.
C zone
32°C
B zone
10°C
A zone
( Table.4 Operation mode selection table)
Outside air temperature (TO)
Room temperature(TB)
A zone
B zone
C zone
TB > TS+2°C
Monitoring
Cooling
(automatic dry)
Cooling
(automatic dry)
TS+2°C
TB
TS - 2°C
Monitoring
Monitoring
Monitoring
TB TS- 2°C
Heating
Heating
Monitoring
.When COOING was selected at
, the air conditioner operates as follow:
The same operation as COOLING OPERATION of item 1 above is performed.
When the room temperature has remained at (set tempareure-1°C) for 8 minutes, operation is
automatically switched to DRY and the same operation as DRY OPERATION of item 3 above
is performed.
If the room temperature reaches (set temp2°C during DRY operation, operation returns to
COOLING operation.
.When HEATING was selected at
, the same operation as HEATING OPERATION of item 2
above is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the COOLING or HEATING operation mode was selected at
above, operation is switched
to MONITORING and the operation mode is selected again.
1
<
1
2
3
1
4
1
( Fig.5 : Outside air temperature zone selection )
05-04
Summary of Contents for AOYR07LCC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 13: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 17: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 22: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 41: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 79: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 80: ...REPLACEMENT PARTS 09 01 Models ASYA07LCC ASYA09LCC INVERTER ...
Page 81: ...REPLACEMENT PARTS 09 02 Models ASYA07LCC ASYA09LCC ...
Page 82: ...REPLACEMENT PARTS 09 03 Models AOYR07LCC AOYR09LCC ...
Page 83: ...REPLACEMENT PARTS 09 04 Models AOYR07LCC AOYR09LCC ...
Page 84: ...REPLACEMENT PARTS 09 05 Models AOYR07LCC AOYR09LCC ...
Page 85: ...REPLACEMENT PARTS 09 06 Models ASYA12LCC INVERTER ...
Page 86: ...REPLACEMENT PARTS 09 07 Models ASYA12LCC ...
Page 87: ...REPLACEMENT PARTS 09 08 Models AOYR12LCC ...
Page 88: ...REPLACEMENT PARTS 09 09 Models ASYA14LCC ASYA18LCC INVERTER ...
Page 89: ...REPLACEMENT PARTS 09 10 Models ASYA14LCC ASYA18LCC ...
Page 90: ...REPLACEMENT PARTS 09 11 Models AOYR14LCC AOYR18LCC ...
Page 91: ...REPLACEMENT PARTS 09 12 Models AOYR14LCC AOYR18LCC ...
Page 92: ...REPLACEMENT PARTS 09 13 Models ASYB09LDC ASYB12LDC INVERTER ...
Page 93: ...REPLACEMENT PARTS 09 14 Models ASYB09LDC ASYB12LDC ...
Page 94: ...REPLACEMENT PARTS 09 15 Models AOYS09LDC AOYS12LDC ...
Page 96: ...Process Model AOYR07 09LCC Connection of leads to inverter assy REPLACEMENT PARTS 09 17 ...
Page 97: ...Process Model AOYR07 09LCC Shaping of leads to inverter assy REPLACEMENT PARTS 09 18 ...
Page 98: ...Model AOYR07 09LCC 09 19 ...
Page 103: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 108: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS09022006 FEB 2006 Printed in Japan ...