21. VARIOUS PROTECTIONS
(1). DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
ASYA07/09/12/14/18LCC
104°C
101°C
110°C
ASYB09/12LDC
104°C
101°C
110°C
07/09LCC, 09LDC
12LCC, 12LDC
14/18LCC
07/09LCC, 09LDC
12LCC, 12LDC
14/18LCC
OT (Control / Release)
17°C
12°C
46°C
40°C
3.5A / 3.0A
4.0A / 3.5A
5.5A / 5.0A
4.0A / 3.5A
5.0A / 4.5A
6.5A / 6.0A
4.5A / 4.0A
6.0A / 5.5A
8.5A / 8.0A
6.5A / 6.0A
8.0A / 7.5A
8.0A / 7.5A
8.0A / 7.5A
6.5A / 6.0A
8.0A / 7.5A
8.5A / 8.0A
9.5A / 9.0A
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 20 Hz, and it continues to decrease the frequency for 20 Hz every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the control of the
compressor frequency is released.
When the discharge temperature becomes higher than Temperature
,the compressor is stopped
and the indoor unit LED starts blinking.
(Table 17 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
Temperature
Temperature
(2). CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit velue that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 18 : Current Release Operation Value / Release Value)
[ Heating ]
[ Cooling / Dry ]
OT : Outdoor Temperature
OT : Outdoor Temperature
OT (Control / Release)
5°C
05-17
7.0A / 6.5A
9.0A / 8.5A
10.5A / 10.0A
13.0A / 12.5A
OT (Control / Release)
17°C
12°C
5°C
OT (Control / Release)
17°C
12°C
5°C
46°C
40°C
OT (Control / Release)
46°C
40°C
OT (Control / Release)
Summary of Contents for AOYR07LCC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 13: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 17: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 22: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 41: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 79: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 80: ...REPLACEMENT PARTS 09 01 Models ASYA07LCC ASYA09LCC INVERTER ...
Page 81: ...REPLACEMENT PARTS 09 02 Models ASYA07LCC ASYA09LCC ...
Page 82: ...REPLACEMENT PARTS 09 03 Models AOYR07LCC AOYR09LCC ...
Page 83: ...REPLACEMENT PARTS 09 04 Models AOYR07LCC AOYR09LCC ...
Page 84: ...REPLACEMENT PARTS 09 05 Models AOYR07LCC AOYR09LCC ...
Page 85: ...REPLACEMENT PARTS 09 06 Models ASYA12LCC INVERTER ...
Page 86: ...REPLACEMENT PARTS 09 07 Models ASYA12LCC ...
Page 87: ...REPLACEMENT PARTS 09 08 Models AOYR12LCC ...
Page 88: ...REPLACEMENT PARTS 09 09 Models ASYA14LCC ASYA18LCC INVERTER ...
Page 89: ...REPLACEMENT PARTS 09 10 Models ASYA14LCC ASYA18LCC ...
Page 90: ...REPLACEMENT PARTS 09 11 Models AOYR14LCC AOYR18LCC ...
Page 91: ...REPLACEMENT PARTS 09 12 Models AOYR14LCC AOYR18LCC ...
Page 92: ...REPLACEMENT PARTS 09 13 Models ASYB09LDC ASYB12LDC INVERTER ...
Page 93: ...REPLACEMENT PARTS 09 14 Models ASYB09LDC ASYB12LDC ...
Page 94: ...REPLACEMENT PARTS 09 15 Models AOYS09LDC AOYS12LDC ...
Page 96: ...Process Model AOYR07 09LCC Connection of leads to inverter assy REPLACEMENT PARTS 09 17 ...
Page 97: ...Process Model AOYR07 09LCC Shaping of leads to inverter assy REPLACEMENT PARTS 09 18 ...
Page 98: ...Model AOYR07 09LCC 09 19 ...
Page 103: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 108: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS09022006 FEB 2006 Printed in Japan ...