En-2
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts. The use of non-prescribed parts can cause serious accidents
such as the unit falling, water leakage, electric shock, or fire.
The following installation parts are supplied. Use them as required.
•
Keep the Installation Manual in a safe place and do not discard any other accessories
•
until the installation work has been completed.
Name and shape
Q’ty
Description
Installation Manual
1
This manual
Drain pipe
1
For outdoor unit drain piping work
(May not be supplied, depending on
the model.)
Drain cap
2
Binder
3
For binding power supply cable and
connection cable
One-touch bush
2
For power supply cable and connection
cable installation
3. INSTALLATION WORK
3.1. Selecting an installation location
WARNING
Securely install the outdoor unit at a location that can withstand the weight of the unit.
Otherwise, the outdoor unit may fall and cause injury.
Be sure to install the outdoor unit as prescribed, so that it can withstand earthquakes
and typhoons or other strong winds. Improper installation can cause the unit to topple
or fall, or other accidents.
Do not install the outdoor unit near the edge of a balcony. Otherwise, children may
climb onto the outdoor unit and fall off of the balcony.
CAUTION
Do not install the outdoor unit in the following areas:
Area with high salt content, such as at the seaside. It will deteriorate metal parts,
•
causing the parts to fail or the unit to leak water.
Area filled with mineral oil or containing a large amount of splashed oil or steam,
•
such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit
to leak water.
Area that generates substances that adversely affect the equipment, such as
•
sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed
joints to corrode, which can cause refrigerant leakage.
Area containing equipment that generates electromagnetic interference. It will
•
cause the control system to malfunction, preventing the unit from operating
normally.
Area that can cause combustible gas to leak, contains suspended carbon fibers or
•
flammable dust, or volatile inflammables such as paint thinner or gasoline. If gas
leaks and settles around the unit, it can cause a fire.
Area that has heat sources, vapors, or the risk of the leakage of flammable gas in
•
the vicinity.
Area where small animals may live. It may cause failure, smoke or fire if small
•
animals enter and touch internal electrical parts.
Area where animals may urinate on the unit or ammonia may be generated.
•
Do not tilt the outdoor unit more than 3 degrees.
Install the outdoor unit in a well-ventilated location away from rain or direct sunlight.
2. ABOUT THE UNIT
2.1. Precautions for using R410A refrigerant
WARNING
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other
areas. Touching the refrigerant directly can cause frostbite.
If a refrigerant leak occurs during operation, immediately vacate the premises and
thoroughly ventilate the area. If the refrigerant comes in contact with a flame, it produces
a toxic gas.
The basic installation work procedures are the same as conventional refrigerant models.
However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of conventional refrigerant
•
(R22) models, some of the piping and installation and service tools are special. (See
the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new
refrigerant R410A model, always replace the conventional piping and flare nuts with
the R410A piping and flare nuts.
Models that use refrigerant R410A have a different charging port thread diameter
•
to prevent erroneous charging with conventional refrigerant (R22) and for safety.
Therefore, check beforehand. [The charging port thread diameter for R410A is
1/2 UNF 20 threads per inch.]
Be careful that foreign matter (oil, water, etc.) does not enter the piping than with
•
refrigerant models. Also, when storing the piping, securely seal the openings by
pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition
•
of the gas and liquid phases. And always charge from the liquid phase where
refrigerant composition is stable.
2.2. Special tools for R410A
WARNING
To install a unit that uses R410A refrigerant, use dedicated tools and piping materials that
have been manufactured specifically for R410A use. Because the pressure of R410A
refrigerant is approximately 1.6 times higher than R22, failure to use dedicated piping
material or improper installation can cause rupture or injury. Furthermore, it can cause
serious accidents such as water leakage, electric shock, or fire.
Tool name
Contents of change
Gauge manifold
Pressure is high and cannot be measured with a conventional
gauge. To prevent erroneous mixing of other refrigerants, the
diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa
(-1 to 53 bar) for high pressure. –0.1 to 3.8 MPa (-1 to 38 bar)
for low pressure.
Charge hose
To increase pressure resistance, the hose material and base
size were changed.
Vacuum pump
A conventional vacuum pump can be used by installing a
vacuum pump adapter.
Gas leakage
detector
Special gas leakage detector for HFC refrigerant R410A.
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of re-
sidual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed
or discolored portion (especially on the interior surface). Otherwise, the expansion valve
or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using conventional
refrigerant, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table. Never use cop
-
per pipes thinner than that in the table even when it is available on the market.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter [mm (in.)]
Thickness [mm]
6.35 (1/4)
0.80
9.52 (3/8)
0.80
12.70 (1/2)
0.80
15.88 (5/8)
1.00
19.05 (3/4)
1.20
9379069380_IM.indb 2