En-10

9. PUMP DOWN

PUMP DOWN (Refrigerant collecting operation)

Perform the following procedures to collect the refrigerant when moving the indoor unit or 

the outdoor unit.

(1)  Press the push-button switch on the circuit board once.

 

The LED on the circuit board starts lighting. This indicates the start of PUMP DOWN 

operation.

 

When the switch is pressed while the compressor is in operation, PUMP DOWN 

operation starts automatically.

 

When the switch is pressed while the compressor is in stop, the compressor starts to 

operate automatically, and then move on to PUMP DOWN operation.

(2)  PUMP DOWN operation continues for a bout 1 minute. When PUMP DOWN operation 

is completed, the compressor stops automatically. Then close the 2-way valve and 

3-way valve immediately.

(3)  Turn the power off.

PUMP DOWN SW

 

DANGER

This part (Choke coil) generates high voltages. Never touch this part.

9374995295_IM.indb   10

22/1/2556   16:12:23

Summary of Contents for AOYG30LETL

Page 1: ...vicio autorizado MANUALE DI INSTALLAZIONE UNITÀ ESTERNA A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE EXTERIOR Apenas para pessoal de assistência autorizado РУКОВОДСТВО ПО УСТАНОВКЕ ВНЕШНИЙ МОДУЛЬ Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU DIŞ ÜNİTE Yalnızca...

Page 2: ...r purging Use a vacuum pump for R410A exclusively Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit Use a clean gauge manifold and charging hose for R410A exclusively During the pump down operation make sure that the compressor is turned off before you remove the refrigerant piping Do not remove the connection pipe while the compressor is in operation wit...

Page 3: ...leak occurs during operation immediately vacate the premises and thoroughly ventilate the area If the refrigerant comes in contact with a flame it produces a toxic gas The basic installation work procedures are the same as conventional refrigerant models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 mo...

Page 4: ... place Since the drain water flows out of the outdoor unit during heating operation install the drain pipe and connect it to a commercial 16 mm hose Reverse cycle model only When installing the drain pipe plug all the holes other than the drain pipe mounting hole in the bottom of the outdoor unit with putty so there is no water leakage Reverse cycle model only Drain pipe mounting hole Base Drain p...

Page 5: ...the installation conditions the outdoor unit may spread its vibration during operation which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space for installing the connection pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commercially ...

Page 6: ...rect operation cannot be guaranteed 5 2 1 Flaring Use special pipe cutter and flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that the cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the...

Page 7: ...essure has not decreased When the outdoor air temperature changes 5 C the test pressure changes 0 05 MPa If the pressure has dropped the pipe joints may be leaking If a leak is found immediately repair it and perform the sealing test again After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly 5 4 Vacuum process CAUTION Perform a refrigerant lea...

Page 8: ...mmediately after the power supply has been turned off Electrical shock may occur After turning off the power always wait 5 minutes or more before touching electrical components Use a dedicated power supply circuit Insufficient power capacity in the electrical circuit or improper wiring may cause electric shock or fire Be sure to install a breaker of the specified capacity When selecting breaker pl...

Page 9: ... power supply wiring for the outdoor unit If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease When the electrical switchboard is installed outdoors place it under lock and key so that it is not easily accessible Start wiring work after closing branch switch and over current breaker Transmission cable between indoor unit and outdoor unit is...

Page 10: ...wn in the figure Fill in a gap at the entrance of the cables with insulation seal Cable clip Power supply cable and connection cable Insulation Seal CAUTION Fix cables so that cables do not make contact with the pipes especially on high pressure side Do not make power supply cable and connection cable come in contact with valve Gas Power supply cable and connection cable Valve Gas Gap 6 Put the se...

Page 11: ...switch is pressed while the compressor is in operation PUMP DOWN operation starts automatically When the switch is pressed while the compressor is in stop the compressor starts to operate automatically and then move on to PUMP DOWN operation 2 PUMP DOWN operation continues for a bout 1 minute When PUMP DOWN operation is completed the compressor stops automatically Then close the 2 way valve and 3 ...

Reviews: