En-3

(2) Multiple parallel unit arrangement

20 or more 

40 or more

100 or more

200 or more

30 or more

[OUTDOOR UNIT]

5 cm or over

INDOOR UNIT

•  Do not directly install it on the 

ground, otherwise it will cause 
failure.

•  To obtain better operation ef-

ficiency, when the outdoor unit 
is installed, be sure to open the 
front and left side.

 CAUTION

When the outdoor temperature is 0 

˚

C or less, do not use the accessory drain pipe 

and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may 
freeze in extreme cold weather. (Reverse cycle model only)

In the area with heavy snowfall, if the intake and outlet of outdoor unit is blocked with 
snow, it might become dif

fi

 cult to get warm and it is likely to cause of the breakdown. 

Please construct a canopy and a pedestal or place the unit on a high stand (local 
con

fi

 gured).

When an obstruction is present also in the upward area

  

(Unit: cm)

(1)  Obstacles at rear and above only

10 or more

Max. 20

60 or more

(2)  Obstacles at rear, sides, and above 

only 

60 or 
more

10 or 
more

25 or more

10 or more

Max. 20

4.1.2.   Multiple outdoor unit installation

•  Provide at least 25 cm of space between the outdoor units if multiple units are installed.
•  When routing the piping from the side of an outdoor unit, provide space for the piping.
•  No more than 3 units must be installed side by side. When 3 units or more are arranged 

in a line, provide the space as shown in the following example when an obstruction is 
present also in the upward area.

When the upward area is open 

 

 

(Unit: cm)

 

(1)  Obstacles at rear only

20 or more

(2) Obstacles at front only

100 or more

(3) Obstacles at front and rear only

30 or more

100 or more

When an obstruction is present also in the upward area

 

(Unit: cm)

•  Obstacles at rear and above only

150 or 
more

30 or more

Max. 30

4.1.3.   Outdoor units installation in multi row

 

(Unit: cm)

(1) Single parallel unit arrangement

20 or more

40 or more

80 or more

100 or more

54 cm

32 cm

Drain pipe

Outdoor unit bottom

Drain pipe

Drain caps

Without caps

With caps

Bolt

20 mm

Nut

Block

Fix securely with bolts on a solid block. (Use 4 sets of commercially available M10 bolt, 
nut and washer.)

9332809107-02_IM.indb   3

9332809107-02_IM.indb   3

11/27/2015   3:03:51 PM

11/27/2015   3:03:51 PM

Summary of Contents for AOYG18LBCA

Page 1: ...INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL Português EλληvIkά Ita...

Page 2: ...m used as the packaging material away from young children Contents 1 SAFETY PRECAUTIONS 1 2 ABOUT THIS PRODUCT 1 3 SELECTING THE MOUNTING POSITION 2 4 INSTALLATION DIAGRAM 2 5 INSTALLATION 4 6 PUMP DOWN 5 CAUTION Read carefully all safety information written in this manual before you install or use the air conditioner This unit must be installed by qualified personnel with a capacity certificate f...

Page 3: ...en using a connection pipe other than that in the table charge additional refrigerant with 20 g 1 m as the criteria For the additional amount see the table below Pipe length 15 m 20 m 25 m 30 m Rate Additional refrigerant None 100 g 200 g 300 g 20 g m CAUTION When adding refrigerant add the refrigerant from the charging port at the completion of work 2 7 Accessories The following installation acce...

Page 4: ...2 Obstacles at rear sides and above only 60 or more 10 or more 25 or more 10 or more Max 20 4 1 2 Multiple outdoor unit installation Provide at least 25 cm of space between the outdoor units if multiple units are installed When routing the piping from the side of an outdoor unit provide space for the piping No more than 3 units must be installed side by side When 3 units or more are arranged in a ...

Page 5: ...4 Outdoor unit wiring 1 Remove the outdoor unit connector cover 2 Bend the end of the cable as shown in the figure 3 Connect the end of the connection cable fully into the terminal block 4 Fasten the sheath with a cable clamp 5 Install the connector cover Connection cable Cable clamp N L 3 2 1 Cable clamp Earth screw N L 3 2 1 1 2 3 Outdoor unit terminal block Indoor unit terminal block Connection...

Page 6: ...2 MPa retighten the valve stem and disconnect the charge hose from the 3 way valve charging port If the stem of the 3 way valve is opened fully before the charge hose is disconnect ed it may be difficult to disconnect the charge hose 10 Fully open the valve stems of the 2 way valve and 3 way valve using a hexagon wrench After the valve stem begins to turn turn it with a torque of less than 2 9 N m...

Reviews: