En-2

Thicknesses of Annealed Copper Pipes

Nominal diameter

Outer 

diameter

Thickness

1/4 in

6.35 mm

0.8 mm

1/2 in

12.70 mm

0.8 mm

5/8 in

15.88 mm

1.0 mm

 WARNING

To install a unit that uses R410A refrigerant, use dedicated tools and piping materials 
that have been manufactured speci

fi

 cally for R410A use. Because the pressure of 

R410A refrigerant is approximately 1.6 times higher than R22, failure to use dedicated 
piping material or improper installation can cause rupture or injury. Furthermore, it can 
cause serious accidents such as water leakage, electric shock, or 

fi

 re.

2.3. Power

• The rated voltage

230 V   AC  50 Hz.

 WARNING

Before turning on the power, check if the voltage is within the 220 V -10 % to 240 V 
+10 % range.

Always use a special branch circuit and install a special receptacle to supply power to 
the room air conditioner.

Use a circuit breaker and receptacle matched to the capacity of the air conditioner.

Install a leakage circuit breaker in accordance with the related laws and regulations 
and electric company standards.

The circuit breaker is installed in the permanent wiring. Always use a circuit that can 
trip all the poles of the wiring and has an isolation distance of at least 3 mm between 
the contacts of each pole.

 CAUTION

The power source capacity must be the sum of the air conditioner current and the cur-
rent of other electrical appliances. When the current contracted capacity is insuf

fi

 cient, 

change the contracted capacity.
When the voltage is low and the air conditioner is dif

fi

 cult to start, contact the power 

company the voltage raised.

2.4. Electric requirement

•  Electric wire size and fuse capacity:

Cable

Conductor size [mm

2

]

Type

Power supply cable

4.0

Type60245 IEC57

Connection cable

MAX.

2.5

Type60245 IEC57

MIN.

1.5

Breaker capacity (A)

18 type

24 type

25

30

2.5. Limitation of refrigerant piping length

 CAUTION

The total maximum pipe lengths and height difference of this product are shown in the 
table.
If the units are further apart than this, correct operation cannot be guaranteed.

Pipe length

Maximum height

(between indoor and outdoor)

MAX.

MIN.

30 m

5 m

20 m

2.6. Additional charge

Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory.
When the piping is longer than 15 m, additional charging is necessary.
Between 15 m and 30 m, when using a connection pipe other than that in the table, charge 
additional refrigerant with 20 g/1 m as the criteria.
For the additional amount, see the table below.

Pipe length

15 m

20 m

25 m

30 m

Rate

Additional refrigerant

None

+100 g

+200 g

+300 g

20 g/m

 CAUTION

When adding refrigerant, add the refrigerant from the charging port at the completion 
of work.

2.7. Accessories

The following installation accessories are supplied.
Use them as required.

Drain pipe

1

Drain cap

3

Installation manual

1

One set of following parts are necessary installation of this product.

Name

Connection pipe assembly
Connection cable
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant

3.  SELECTING THE MOUNTING POSITION

•  Decide the mounting position with the customer as follows.
•  Do not set to a place where there is oily smoke, oil is used in the factory, the unit can 

contact sea breeze, sul

fi

 de gases will be generated in the hot spring area, corrosive 

gases will be generated, animal may urine on the unit and ammonia will be generated 
and a dusty place.

3.1. Outdoor unit

(1) If possible, do not install the unit where it will be exposed to direct sunlight. 

(If necessary, Install a blind that does not interfere with the air 

fl

 ow.)

(2)  Do not install the unit where a strong wind blows or where it is very dusty.
(3)  Do not install the unit where people pass.
(4)  Take you neighbors into consideration so that they are not disturbed by air blowing into their 

windows or by noise.

(5)  Provide the space shown in 

fi

 gure so that the air

fl

 ow is not blocked. Also for ef

fi

 cient 

operation, leave open three of the four directions front, rear, and both sides.

(6)  Install the unit where keep away more than 3 m from the antenna of TV set and Radio.
(7)  Outdoor unit should be set to a place where both drainage and itself will not be 

affected when heating.

 WARNING

Install at a place that can withstand the weight of the outdoor units and install positively 
so that the units will not topple or fall.

 CAUTION

Do not install where there is the danger of combustible gas leakage.
Do not install near heat sources.
If children under 10 years old may approach the unit, take preventive measures so that 
they cannot reach the unit.

4. INSTALLATION DIAGRAM

4.1.1.   Single outdoor unit installation

When the upward area is open 

 (Unit: 

cm)

(1)  Obstacles at rear only

10 or more

(2)  Obstacles at rear and sides only

10 or more

10 or 
more

25 or more

(3)  Obstacles at front only

60 or more

(4)  Obstacles at front and rear only

60 or more

10 or more

9332809107-02_IM.indb   2

9332809107-02_IM.indb   2

11/27/2015   3:03:51 PM

11/27/2015   3:03:51 PM

Summary of Contents for AOYG18LBCA

Page 1: ...INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL Português EλληvIkά Ita...

Page 2: ...m used as the packaging material away from young children Contents 1 SAFETY PRECAUTIONS 1 2 ABOUT THIS PRODUCT 1 3 SELECTING THE MOUNTING POSITION 2 4 INSTALLATION DIAGRAM 2 5 INSTALLATION 4 6 PUMP DOWN 5 CAUTION Read carefully all safety information written in this manual before you install or use the air conditioner This unit must be installed by qualified personnel with a capacity certificate f...

Page 3: ...en using a connection pipe other than that in the table charge additional refrigerant with 20 g 1 m as the criteria For the additional amount see the table below Pipe length 15 m 20 m 25 m 30 m Rate Additional refrigerant None 100 g 200 g 300 g 20 g m CAUTION When adding refrigerant add the refrigerant from the charging port at the completion of work 2 7 Accessories The following installation acce...

Page 4: ...2 Obstacles at rear sides and above only 60 or more 10 or more 25 or more 10 or more Max 20 4 1 2 Multiple outdoor unit installation Provide at least 25 cm of space between the outdoor units if multiple units are installed When routing the piping from the side of an outdoor unit provide space for the piping No more than 3 units must be installed side by side When 3 units or more are arranged in a ...

Page 5: ...4 Outdoor unit wiring 1 Remove the outdoor unit connector cover 2 Bend the end of the cable as shown in the figure 3 Connect the end of the connection cable fully into the terminal block 4 Fasten the sheath with a cable clamp 5 Install the connector cover Connection cable Cable clamp N L 3 2 1 Cable clamp Earth screw N L 3 2 1 1 2 3 Outdoor unit terminal block Indoor unit terminal block Connection...

Page 6: ...2 MPa retighten the valve stem and disconnect the charge hose from the 3 way valve charging port If the stem of the 3 way valve is opened fully before the charge hose is disconnect ed it may be difficult to disconnect the charge hose 10 Fully open the valve stems of the 2 way valve and 3 way valve using a hexagon wrench After the valve stem begins to turn turn it with a torque of less than 2 9 N m...

Reviews: