Fujitsu aoyg18lac2 Installation Manual Download Page 7

En-6

Detach the caps and plugs from the pipes.

(1) 

Center the pipe against the port on the outdoor unit, and then turn the 

fl

 are nut by hand.

(2) 

To prevent gas leakage, coat the 

fl

 are 

surface with alkylbenzene oil (HAB).

Do not use mineral oil.

Attach the connection 

(3) 

pipe.

Flare nut

Connection pipe 

(Liquid)

UNIT B

UNIT A

Connection pipe (Gas)

Flare nut

3-way valve (Gas)

2-way valve (Liquid)

When the 

fl

 are nut is 

(4) 

tightened properly by your 
hand, use a torque wrench 
to 

fi

 nally tighten it.

Holding spanner

Torque wrench

Body side

 CAUTION

Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order to 

tighten the 

fl

 are nut correctly.

Outer panel may be distorted if fastened only with a wrench. Be sure to 

fi

 x the elementary 

• 

part with a holding wrench (spanner) and fasten with a torque wrench (refer to below 
diagram). Do not apply force to the blank cap of the valve or hang a wrench, etc., on the 
cap. If blank cap is broken, it may cause leakage of refrigerant.

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1100)

How to use adapter (Connection ports of outdoor unit)

4. 1. 3. 

When using the ADAPTER, be careful not to overtighten the nut, or the smaller pipe may 

• 

be damaged.
Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit where 

• 

the 

fl

 are nut comes in.

Use appropriate wrenches to avoid damaging the connection thread by overtightening the 

• 

fl

 are nut.

Apply wrenches on both of 

fl

 are nut (local part), and ADAPTER to tighten them.

• 

Adapter type [mm]

Tightening torque [N·m (kgf·cm)]

ø9.52 

 ø12.7

32 to 42 (320 to 420)

ELECTRICAL WIRING

5. 

The precautions of electrical wiring

5. 1. 

 WARNING

Wiring connections must be performed by a quali

fi

 ed person in accordance with 

speci

fi

 cations.

The rated supply of this product is 50Hz, 230V. Use a voltage within the range of 
198-264V.

Before connecting the wires, make sure the power supply is OFF.

 WARNING

Be sure to install a breaker of the speci

fi

 ed capacity. When selecting breaker, please 

comply with the laws and the regulations of each country. One breaker must be installed 
on the power supply of the outdoor unit. Wrong selection and setup of the breaker will 
cause electric shock or 

fi

 re.

Be sure to install an earth leakage breaker. Otherwise, it will cause electric shock or 

fi

 re.

Do not connect AC power supply to the transmission line terminal board.
Improper wiring can damage the entire system.

Connect the connector cable securely to the terminal.
Faulty installation can cause a 

fi

 re.

Make sure to secure the insulation portion of the connector cable with the cable clamp. 
A damaged insulation can cause a short circuit.

Never install a power factor improvement condenser. Instead of improving the power 
factor, the condenser may overheat.

Before servicing the unit, turn the power supply switch OFF. Then, do not touch electric 
parts for 5 minutes due to the risk of electric shock.

Make sure to perform grounding work. Improper grounding work can cause electric 
shocks.

 CAUTION

The primary power supply capacity is for the air conditioner itself, and does not include 
the concurrent use of other devices.

Do not use crossover power supply wiring for the outdoor unit.

If the electrical power is inadequate, contact your electric power company.

Install a breaker in a location that is not exposed to high temperatures.
If the temperature surrounding the breaker is too high, the amperage at which the 
breaker cuts out may decrease.

This system uses an inverter which means that it must be used an earth leakage 
breaker that can handle harmonics in order to prevent malfunctioning of the earth 
leakage breaker itself.

When the electrical switchboard is installed outdoors, place it under lock and key so 
that it is not easily accessible.

Do not fasten the power supply cable and connection cable together.

Always keep to the maximum length of the connection cable. Exceeding the maximum 
length may lead to erroneous operation.

The static electricity that is charged to the human body can damage the control PC 
Board when handling the control PC Board for address setting, etc.
Please keep caution to the following points.
Provide the grounding of Indoor unit, Outdoor unit and Option equipment.
Cut off the power supply (breaker).
Touch the metal section (such as the unpainted control box section) of the indoor or 
outdoor unit for more than 10 seconds. Discharge the static electricity in your body.
Never touch the component terminal or pattern on the PC Board.

Electrical requirement

5. 2. 

 CAUTION

Be sure to install a breaker of the speci

fi

 ed capacity.

Regulation of cables and breaker differs from each locality, refer in accordance with 

local rules.

Voltage rating

1

Φ

 230V (50Hz)

Operating range

198-264V

Cable

Cable size 

(mm

2

*1

Type

Remarks 

Power supply cable

2.5

Type 60245 IEC 57

2 cable + Earth (Ground), 

1 Ø 230V

Connection cable

1.5

Type 60245 IEC 57

3 cable + Earth (Ground), 

1 Ø 230V

*1

   Selected sample: Select the correct cable type and size according to the country or 

region’s regulations.
Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the 

wire diameter when the wire length is long.

Breaker

Speci

fi

 cation

*2

Circuit breaker (over current)

Current : 15 (A)

Earth leakage breaker

Leakage current : 30mA 0.1sec or less

*

3

*2

   Select the appropriate breaker of the described speci

fi

 cation according to the national 

or regional standards.

*3

   Select the breaker that enough load current can pass through it.

Before starting work check that power is not being supplied to all poles of the indoor unit 

• 

and outdoor unit.

Install all electrical works in accordance to standard.

• 

Install the disconnect device with a contact gap of at least 3mm in all poles nearby the 

• 

units. (Both indoor unit and outdoor unit)

Wiring size must comply with the applicable local and national code.

• 

9379342070-02_IM.indb   6

9379342070-02_IM.indb   6

2011-12-21   11:14:14

2011-12-21   11:14:14

Summary of Contents for aoyg18lac2

Page 1: ...AZIONE ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ MANUAL DE INSTALAÇÃO РУКОВОДСТВО ПО УСТАНОВКЕ MONTAJ KILAVUZU PART NO 9379342070 02 For authorized personnel only Nur für autorisiertes Personal Pour le personnel agréé uniquement Solo para personal autorizado Ad uso esclusivo del personale autorizzato Για εξουσιοδοτημένο προσωπικό σέρβις Apenas para técnicos autorizados Для уполномоченного персонала Yetkili servis p...

Page 2: ...ibly result in personal harm to the user or damage to property Read carefully all security information before use or install the air conditioner Do not attempt to install the air conditioner or a part of the air conditioner by yourself This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation p...

Page 3: ...shape Q ty Description Installation Manual 1 This manual Drain pipe 1 For outdoor unit drain piping work Heat Cool model Reverse cycle only Adapter assy 9 52 mm 12 7 mm 1 For use when connecting model 14 to outdoor port A or B 18 type only System configuration 2 4 Layout example for the indoor units and outdoor unit OUTDOOR UNIT 18 TYPE H1 H2 H1 a b Outdoor unit Indoor unit Unit B 7 14 Connection ...

Page 4: ...t and fall off of the balcony CAUTION Do not install the outdoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit...

Page 5: ...er do not install the unit with it tilted towards the side containing the compressor When installing the outdoor unit where it may exposed to strong wind fasten it securely Decide the mounting position with the customer as follows 1 Install the outdoor unit in a location which can withstand the weight of the unit and vibration and which can install horizontally 2 Provide the indicated space to ens...

Page 6: ...to the necessary length with a pipe cutter 1 Hold the pipe downward so that the cuttings will not enter the pipe and remove any 2 burrs Insert the flare nut always use the flare nut attached to the indoor and outdoor units 3 respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used Protect the pipes by pinching them...

Page 7: ... condenser may overheat Before servicing the unit turn the power supply switch OFF Then do not touch electric parts for 5 minutes due to the risk of electric shock Make sure to perform grounding work Improper grounding work can cause electric shocks CAUTION The primary power supply capacity is for the air conditioner itself and does not include the concurrent use of other devices Do not use crosso...

Page 8: ...acuum pump gauge manifold and charge hose for R410A exclusively Using the same vacuum for different refrigerants may damage the vacuum pump or the unit After connecting the piping check the joints for gas leakage with gas leak detector or soapy water CHECKING GAS LEAKAGE AND PURGING AIR 6 1 1 Gas leak checks are performed using either vacuum or nitrogen gas so select the proper one depending on th...

Page 9: ...aker in accordance with the related laws and regulations and electric company standards CAUTION When the voltage is low and the air conditioner is difficult to start contact the power company the voltage raised TEST RUN 8 The test run method may be different for each indoor unit that is connected Refer to the installation Manual included with each indoor unit CAUTION Always turn on the power 12 ho...