Fujitsu aoyg18lac2 Installation Manual Download Page 6

En-5

Transportation of the unit

3. 4. 

 WARNING

Do not touch the 

fi

 ns. Otherwise, personal injury could result.

 CAUTION

When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or 

fi

 ngers may be pinched.

Be sure to hold the handles on the sides of the unit. Otherwise, holding the suction grille 

• 

on the sides of the unit may cause deformation.

Handle

Installation of the unit

3. 5. 

Install 4 anchor bolts at the locations indicated with arrows in the 

fi

 gure.

• 

To reduce vibration, do not install the unit directly on the ground. Install it on a secure 

• 

base (such as concrete blocks).
The foundation shall support the legs of the unit and have a width of 50mm or more.

• 

Depending on the installation conditions, the outdoor unit may spread its vibration during 

• 

operation, which may cause noise and vibration. Therefore, attach damping materials 
(such as damping pads) to the outdoor unit during installation.
Install the foundation, making sure that there is enough space for installing the connection 

• 

pipes.
Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially 

• 

available M10 bolts, nuts, and washers.)
The bolts should protrude 20mm. (Refer to the 

fi

 gure.)

• 

If overturning prevention is required, purchase the necessary commercially available 

• 

items.

AIR

Bottom side

540 mm

320 mm

Fix securely with bolts on a solid block. (Use 4 sets of commercially available M10 bolt, 
nut and washer.)

Bolt

Nut 

Block

PIPE INSTALLATION I

4. 

Flare connection (pipe connection)

4. 1. 

 CAUTION

Do not use mineral oil on a 

fl

 ared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

While welding the pipes, be sure to blow dry nitrogen gas through them.

The maximum lengths of this product are shown in the table. If the units are further 
apart than this, correct operation cannot be guaranteed.

Flaring

Use special pipe cutter and 

fl

 are tool exclusive for R410A.

• 

Cut the connection pipe to the necessary length with a pipe cutter.

(1) 

Hold the pipe downward so that the cuttings will not enter the pipe and remove any 

(2) 

burrs.
Insert the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor and outdoor units 

(3) 

respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool. Leakage 

of refrigerant may result if other 

fl

 are nuts are used.

Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

(4) 

entering the pipes.

L

Check if [L] is 

fl

 ared uniformly

and is not cracked or scratched.

Pipe

A

B

Die

Pipe outside 

diameter [mm (in.)]

Dimension A (mm)

Dimension B   0

- 0.4 [mm]

Flare tool for R410A, 

clutch type

6.35 (1/4)

0 to 0.5 

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional 

fl

 are tools to 

fl

 are R410A pipes, the dimension A should be 

• 

approximately 0.5mm more than indicated in the table (for 

fl

 aring with R410A 

fl

 are tools) to 

achieve the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the dimension A.

Pipe outside diameter 

[mm (in.)]

Width across 

fl

 ats of Flare nut 

[mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

Width across 

fl

 ats

Bending pipes

4. 1. 1. 

 CAUTION

To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of 
curvature of 100mm or more.

If the pipe is bent repeatedly at the same place, it will break.

If pipes are shaped by hand, be careful not to collapse them.

• 

Do not bend the pipes at an angle of more than 90°.

• 

When pipes are repeatedly bent or stretched, the material will harden, making it dif

fi

 cult to 

• 

bend or stretch them any more.
Do not bend or stretch the pipes more than 3 times.

• 

Pipe connection

4. 1. 2. 

 CAUTION

Be sure to install the pipe against the port on the indoor unit and the outdoor unit 
correctly. If the centering is improper, the 

fl

 are nut cannot be tightened smoothly. 

If the 

fl

 are nut is forced to turn, the threads will be damaged.

Do not remove the 

fl

 are nut from the outdoor unit pipe until immediately before 

connecting the connection pipe.

After installing the piping, make sure that the connection pipes do not touch the 
compressor or outer panel. If the pipes touch the compressor or outer panel, they will 
vibrate and produce noise.

9379342070-02_IM.indb   5

9379342070-02_IM.indb   5

2011-12-21   11:14:09

2011-12-21   11:14:09

Summary of Contents for aoyg18lac2

Page 1: ...AZIONE ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ MANUAL DE INSTALAÇÃO РУКОВОДСТВО ПО УСТАНОВКЕ MONTAJ KILAVUZU PART NO 9379342070 02 For authorized personnel only Nur für autorisiertes Personal Pour le personnel agréé uniquement Solo para personal autorizado Ad uso esclusivo del personale autorizzato Για εξουσιοδοτημένο προσωπικό σέρβις Apenas para técnicos autorizados Для уполномоченного персонала Yetkili servis p...

Page 2: ...ibly result in personal harm to the user or damage to property Read carefully all security information before use or install the air conditioner Do not attempt to install the air conditioner or a part of the air conditioner by yourself This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation p...

Page 3: ...shape Q ty Description Installation Manual 1 This manual Drain pipe 1 For outdoor unit drain piping work Heat Cool model Reverse cycle only Adapter assy 9 52 mm 12 7 mm 1 For use when connecting model 14 to outdoor port A or B 18 type only System configuration 2 4 Layout example for the indoor units and outdoor unit OUTDOOR UNIT 18 TYPE H1 H2 H1 a b Outdoor unit Indoor unit Unit B 7 14 Connection ...

Page 4: ...t and fall off of the balcony CAUTION Do not install the outdoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit...

Page 5: ...er do not install the unit with it tilted towards the side containing the compressor When installing the outdoor unit where it may exposed to strong wind fasten it securely Decide the mounting position with the customer as follows 1 Install the outdoor unit in a location which can withstand the weight of the unit and vibration and which can install horizontally 2 Provide the indicated space to ens...

Page 6: ...to the necessary length with a pipe cutter 1 Hold the pipe downward so that the cuttings will not enter the pipe and remove any 2 burrs Insert the flare nut always use the flare nut attached to the indoor and outdoor units 3 respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used Protect the pipes by pinching them...

Page 7: ... condenser may overheat Before servicing the unit turn the power supply switch OFF Then do not touch electric parts for 5 minutes due to the risk of electric shock Make sure to perform grounding work Improper grounding work can cause electric shocks CAUTION The primary power supply capacity is for the air conditioner itself and does not include the concurrent use of other devices Do not use crosso...

Page 8: ...acuum pump gauge manifold and charge hose for R410A exclusively Using the same vacuum for different refrigerants may damage the vacuum pump or the unit After connecting the piping check the joints for gas leakage with gas leak detector or soapy water CHECKING GAS LEAKAGE AND PURGING AIR 6 1 1 Gas leak checks are performed using either vacuum or nitrogen gas so select the proper one depending on th...

Page 9: ...aker in accordance with the related laws and regulations and electric company standards CAUTION When the voltage is low and the air conditioner is difficult to start contact the power company the voltage raised TEST RUN 8 The test run method may be different for each indoor unit that is connected Refer to the installation Manual included with each indoor unit CAUTION Always turn on the power 12 ho...