1. SAFETY PRECAUTIONS

The warnings and precautions indicated in this manual contain important information 
pertaining to your safety. Be sure to observe them.

 WARNING

This mark indicates procedures which, if improperly per-
formed, might lead to the death or serious injury of the user.

 CAUTION

This mark indicates procedures which, if improperly 
performed, might possibly result in personal harm to the user, 
or damage to property.

 WARNING

For the air conditioner to operate satisfactorily, install it as outlined in this installation 
manual.

The appliance shall be installed in accordance with national wiring regulations.

Never touch electrical components immediately after the power supply has been 
turned off. Electrical shock may occur. After turning off the power, always wait 
5 minutes or more before touching electrical components.

Do not turn ON the power until all work has been completed. Turning ON the power 
before the work is completed can cause serious accidents such as electric shock or 

fi

 re.

If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant
comes in contact with a 

fl

 ame, it produces a toxic gas.

Connect the indoor unit and outdoor unit with the air conditioner piping and cable 
available standard parts.
This installation manual describes the correct connections using the installation set 
available from our standard parts.

Do not use an extension cable.

Do not purge the air with refrigerants but use a vacuum pump to vacuum the 
installation.

There is not extra refrigerant in the outdoor unit for air purging.

If the supply cable is damaged, it must be replaced by the manufacture, its service 
agent or similarly quali

fi

 ed persons in order to avoid a hazard.

 CAUTION

When installing pipes shorter than 5 m, sound of the outdoor unit will be transferred to 
the indoor unit, which will cause large operating sound or some abnormal sound.

This unit must be installed by quali

fi

 ed personnel with a capacity certi

fi

 cate for handling 

refrigerant 

fl

 uids. Refer to regulation and laws in use on installation place.

The unit must be correctly grounded and the supply line must be equipped with a 
differential breaker in order to protect the persons.

The units are not explosion proof and therefore should not be installed in explosive 
atmosphere.

This unit contains no user-serviceable parts. Always consult authorized service 
personnel to repairs.

Children should be monitored to ensure they do not play with the device.

Contents

1. SAFETY 

PRECAUTIONS 

.......................................................................................... 1

2. ABOUT 

THE 

UNIT 

..................................................................................................... 1

3.  SELECTING THE MOUNTING POSITION ............................................................... 3

4. INSTALLATION 

DIAGRAM 

........................................................................................ 3

5. INSTALLATION 

 

......................................................................................................... 4

6. PUMP 

DOWN 

............................................................................................................ 6

Notes:

•  This manual describes how to install the outdoor unit only. To install the indoor unit, 

refer to the installation manual included with the indoor unit.

•  Be sure to read this manual thoroughly before the installation.
•  Hand this manual, together with the operating manual, to the customer. Request the 

customer to keep them on hand for future use, such as for relocating or repairing the 
unit.

•  After the installation, explain correct operation to the customer by using the operating 

manual.

This product is not intended to be used by people (including children) with physical, 
sensory or mental disability, or persons lacking experience or knowledge unless they 
have been given by the through a person responsible for their safety, supervision or 
instruction concerning the use of the device.

Do not touch the aluminum 

fi

 ns of heat exchanger built-in the indoor or outdoor unit to 

avoid personal injury when you install or maintain the unit.

Do not place any other electrical products or household belongings under indoor unit 
or outdoor unit. Dripping condensation from the unit might get them wet, and may 
cause damage or malfunction of your property.

•  Be careful not to scratch the air conditioner when handling it.
•  After installation, explain correct operation to the customer, using the operating manual.

2.  ABOUT THE UNIT

2.1. Precautions for using R410A refrigerant

The basic installation work procedures are the same as conventional refrigerant (R22) 
models.
However, pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of conventional refrigerant 
(R22) models, some of the piping and installation and service tools are special. (See 
the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant 
R410A model, always replace the conventional piping and flare nuts with the R410A piping 
and 

fl

 are nuts.

Models that use refrigerant R410A have a different charging port thread diameter to pre-
vent erroneous charging with conventional refrigerant (R22) and for safety. Therefore, 
check beforehand. [The charging port thread diameter for R410A is 1/2 inch.]

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 
refrigerant (R22) models. Also, when storing the piping ,securely seal the opening by 
pinching, taping, etc.

When charging the refrigerant, take into account the slight change in the composition of 
the gas and liquid phases. And always charge from the liquid phase where refrigerant 
composition is stable.

2.2. Special tools for R410A

Tool name

Contents of change

Gauge manifold

Pressure is high and cannot be measured with a conven-
tional (R22) gauge. To prevent erroneous mixing of other 
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals -0.1 to 5.3 MPa 
(-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.

Charge hose

To increase pressure resistance, the hose material and base 
size were changed.

Vacuum pump

A conventional vacuum pump can be used by installing a 
vacuum pump adapter.

Gas leakage detector

Special gas leakage detector for HFC refrigerant R410A.

Copper pipes

It is necessary to use seamless copper pipes and it is desirable that the amount of residual 
oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or 
discolored portion (especially on the interior surface). Otherwise, the expansion value or 
capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is neces-
sary to choose adequate materials. 
Thicknesses of copper pipes used with R410A are as shown in table below. Never use 
copper pipes thinner than 0.8mm even when it is available on the market.

Thicknesses of Annealed Copper Pipes

Pipe outside diameter

Thickness

6.35 mm (1/4 in.)

0.80 mm

9.52 mm (3/8 in.)

0.80 mm

12.70 mm (1/2 in.)

0.80 mm

15.88 mm (5/8 in.)

1.00 mm

19.05 mm (3/4 in.)

1.20 mm

 WARNING

Do not use the existing (for R22) piping and 

fl

 are nuts.

If the existing materials are used, the pressure inside the refrigerant cycle will rise and 

cause failure, injury, etc. (Use the special R410A materials.)

When installing and relocating the air conditioner, do not mix gases other than 

the speci

fi

 ed refrigerant (R410A) to enter the refrigerant cycle.

If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to 

an abnormally high value and cause failure, injury, etc.

AIR CONDITIONER
OUTDOOR UNIT

INSTALLATION MANUAL

9377863133

9377863133_IM.indb   1

9377863133_IM.indb   1

11/25/2011   11:30:55 AM

11/25/2011   11:30:55 AM

Summary of Contents for AOYG12-14LBLA

Page 1: ... INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION...

Page 2: ... in the indoor or outdoor unit to avoid personal injury when you install or maintain the unit Do not place any other electrical products or household belongings under indoor unit or outdoor unit Dripping condensation from the unit might get them wet and may cause damage or malfunction of your property Be careful not to scratch the air conditioner when handling it After installation explain correct...

Page 3: ...Application Installation Manual 1 This manual Drain pipe 1 For outdoor unit drain piping work Adapter assy 12 7mm 9 52mm 1 For use when connecting 12 type only 2 6 Limitation of refrigerant piping length CAUTION The total maximum pipe lengths and height difference of this product are shown in the table If the units are further apart than this correct operation cannot be guaranteed Pipe length Maxi...

Page 4: ...imals may live It may cause failure smoke or fire if small ani mals enter and touch internal electrical parts Area where animals may urinate on the unit or ammonia may be generated 1 If possible do not install the unit where it will be exposed to direct sunlight If necessary Install a blind that does not interfere with the air flow 2 Do not install the unit where a strong wind blows or where it is...

Page 5: ...nnect them securely and fasten them so that there is 3 no stress placed on the terminals Use an appropriate screwdriver to tighten the terminal screws Do not use a 4 screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened Do not tighten the terminal screws too much otherwise the screws may break 5 See the table below for the termi...

Page 6: ...efrigerant must not be discharged into atmosphere After connecting the piping check the joints for gas leakage with gas leak detector Gas leak checks are performed using either vacuum or nitrogen gas so select the proper one depending on the situation Checking gas leaks with vacuum 1 Check if the piping connections are secure 2 Remove the cap of 3 way valve and connect the gauge manifold charge ho...

Page 7: ...he air purging of the charge hose by connecting the charging hose of gauge mani fold to the charging port of 3 way valve and opening the low pressure valve slightly 2 Close the valve stem of 2 way valve completely 3 Start the cooling operation or following forced cooling operation Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds The operation in dicator lamp and ...

Reviews: