- 40 -

WA

LL

 MOUN

TED

AOY

G

09-

14LZ

CAN

 3. Installation space

3-1. Models: AOYG09LZCAN, AOYG12LZCAN, and 

AOYG14LZCAN

Space requirement

Provide sufficient installation space for product safety.

Single outdoor unit installation

When the upper space is open:

When there is an obstruction in the upper space:

Unit: mm

When there are obstacles at the rear only.

When there are obstacles at the rear and sides.

When there are obstacles at the front only.

When there are obstacles at the front and rear.

Unit: mm

When there are obstacles at the rear and 
above.

When there are obstacles at the rear, sides, and 
above.

100 or more

250 or more

100 or more

100 or more

600 or more

600 or more

100 or more

100 or more

Max. 200

600 or more

600 or more

100 or more

250 or more

100 or more

Max. 200

Summary of Contents for AOYG09LZCAN

Page 1: ...DESIGN TECHNICAL MANUAL AIR CONDITIONER Wall mounted type INDOOR ASYG09LZCA ASYG12LZCA ASYG14LZCA OUTDOOR AOYG09LZCAN AOYG12LZCAN AOYG14LZCAN DR_AS020EF_01 2016 06 21 ...

Page 2: ...roduct specifications and design are subject to change without notice for future improvement For further details please check with our authorized dealer Copyright 2016 Fujitsu General Limited All rights reserved ...

Page 3: ...eating capacity 15 7 Fan performance 16 7 1 Air velocity distributions 16 7 2 Airflow 18 8 Operation noise sound pressure 20 8 1 Noise level curve 20 8 2 Sound level check point 22 9 Safety devices 23 10 External input and output 24 10 1 External input 24 10 2 External output 26 11 Function settings 28 11 1 Function settings by using remote controller 29 11 2 Custom code setting for wireless remot...

Page 4: ...9LZCAN and AOYG12LZCAN 45 5 2 Model AOYG14LZCAN 46 6 Capacity compensation rate for pipe length and height difference 47 6 1 Models AOYG09LZCAN and AOYG12LZCAN 47 6 2 Model AOYG14LZCAN 48 7 Additional charge calculation 49 7 1 Models AOYG09LZCAN and AOYG12LZCAN 49 7 2 Model AOYG14LZCAN 49 8 Airflow 50 8 1 Model AOYG09LZCAN 50 8 2 Model AOYG12LZCAN 50 8 3 Model AOYG14LZCAN 50 9 Operation noise soun...

Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG09LZCA ASYG12LZCA ASYG14LZCA ...

Page 6: ...detects the presence or absence of human in a room by sensing movement of occupants and suppress both of the air conditioner operation and energy con sumption ASYG09LZCA ASYG12LZCA ASYG14LZCA AOYG09LZCAN AOYG12LZCAN AOYG14LZCAN 20 minutes continuous operation by maximum airflow and maximum compressor speed is possible Rapid cooling and heating makes the room comfortable quickly Example Cooling ope...

Page 7: ...ates in large capacity operation noise of the outdoor unit will be suppressed In case of the room temperature being close to the set temperature operation noise might not decrease Economy operation is energy saving as the set temperature of indoor unit is shifted by 1 C and the maximum electric value of the outdoor unit is suppressed Example Cooling operation Weekly timer can be easily set by wire...

Page 8: ...s the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping 5 mode timer setup on off weekly program and sleep available Easy operation Easy to change custom code max 4 custom code Can be used jointly with wired remote controllers Cooling operation Dry operation When the sleep timer is set the set temperature automatically rises 1 C ev...

Page 9: ... 14LZCA Switching remote controller custom code Code selector switch eliminates unit being wrongly switched Up to 4 codes can be set I U Indoor unit A B C D A B C D Mixed up I U I U I U I U I U I U I U I U After code change ...

Page 10: ...ignal transmitter 10 C HEAT button TEMP button POWERFUL button Start Stop button TIMER SETTING button SEND button SELECT button NEXT button BACK button OUTDOOR UNIT LOW NOISE button SWING button SET button WEEKLY button ON OFF button SLEEP button MODE button SENSOR button FAN button RESET button CLOCK ADJUST button ECONOMY button Mode indicator ENERGY SAVING mode indicator LOW NOISE mode indicator...

Page 11: ...ller Holder Unit mm Size H W D mm 205 61 17 Weight g 122 without batteries Unit mm Size H W D mm 150 69 3 26 2 Weight g 27 Top view Front view Side view 205 17 61 48 5 5 5 26 2 69 3 6 5 Front View Side View Bottom View Ø 3 5 Hole 150 106 8 Hole 3 5 2 R ...

Page 12: ...4 QUIET 23 26 Heating HIGH 41 44 MED 35 39 LOW 31 33 QUIET 23 27 Heat exchanger type Dimensions H W D mm Main 384 720 30 Sub 1 84 720 13 3 Sub 2 126 720 13 3 Fin pitch Main 1 2 Sub 1 and Sub 2 1 4 Rows Stages Main 3 24 Sub 1 1 4 Sub 2 1 6 Pipe type Copper tube Fin type Aluminum Enclosure Material Polystyrene Color White Approximate color of MUNSELL 5PB 9 25 0 5 Dimensions H W D Net mm 295 940 270 ...

Page 13: ...eating Average A A A Pdesign Cooling kW 2 5 35 C 3 5 35 C 4 2 35 C Heating Average 2 5 10 C 3 5 10 C 4 2 10 C SEER Cooling kWh kWh 9 51 8 60 7 92 SCOP Heating Average 5 31 4 93 4 44 Annual energy consumption QCE kWh a 92 142 186 QHE Average 659 993 1322 Sound power level Cooling HIGH dB A 56 56 59 Heating 56 56 59 ...

Page 14: ...L MOUNTED ASYG09 14LZCA 4 Dimensions 4 1 Models ASYG09LZCA ASYG12LZCA and ASYG14LZCA Unit mm 375 for pipe inlet Ø 65 for pipe inlet Ø 65 387 Outline of unit 470 470 270 43 295 295 940 940 387 83 77 393 40 9 43 ...

Page 15: ...SYG09 14LZCA Installation space requirement Provide sufficient installation space for product safety Outline of unit Unit mm 50 or more 127 or more 50 or more 133 or more 1 500 or more 50 or more 84 or more 1 800 or more ...

Page 16: ... 12 WALL MOUNTED ASYG09 14LZCA 5 Wiring diagrams 5 1 Models ASYG09LZCA ASYG12LZCA and ASYG14LZCA ...

Page 17: ...7 2 28 2 03 0 47 2 43 2 12 0 48 2 50 2 29 0 48 2 65 2 28 0 49 2 80 2 33 0 49 40 0 1 76 1 59 0 43 1 96 1 73 0 44 2 03 1 81 0 44 2 16 1 88 0 45 2 23 2 04 0 45 2 36 2 03 0 45 2 50 2 08 0 45 46 0 1 51 1 50 0 43 1 69 1 60 0 44 1 74 1 68 0 44 1 85 1 75 0 45 1 92 1 89 0 45 2 03 1 88 0 45 2 13 1 93 0 45 AFR m3 h 830 Indoor temperature CDB 18 21 23 25 27 29 32 CWB 12 15 16 18 19 21 23 Outdoor temperature C...

Page 18: ...4 10 0 3 46 2 72 0 43 3 85 3 03 0 43 4 05 3 06 0 43 4 25 3 34 0 45 4 38 3 45 0 44 4 64 3 65 0 44 4 90 3 86 0 45 15 0 3 40 2 67 0 45 3 79 2 98 0 46 3 98 3 00 0 46 4 18 3 28 0 48 4 31 3 38 0 47 4 56 3 59 0 47 4 82 3 79 0 48 20 0 3 91 3 29 0 73 4 35 3 31 0 75 4 50 3 46 0 75 4 80 3 60 0 75 4 95 3 90 0 75 5 24 3 87 0 76 5 54 4 14 0 76 25 0 3 72 3 13 0 82 4 15 3 15 0 83 4 29 3 29 0 84 4 57 3 44 0 85 4 7...

Page 19: ... 2 17 4 99 2 21 4 87 2 25 4 63 2 34 4 50 2 39 10 11 5 55 2 13 5 42 2 18 5 29 2 22 5 03 2 31 4 89 2 35 5 7 6 00 2 10 5 85 2 14 5 71 2 18 5 42 2 27 5 28 2 31 0 2 6 17 2 07 6 02 2 11 5 87 2 15 5 58 2 23 5 43 2 28 5 3 7 52 1 88 7 34 1 92 7 16 1 96 6 80 2 04 6 62 2 08 7 6 7 77 1 86 7 58 1 90 7 40 1 94 7 03 2 02 6 84 2 06 10 8 8 58 1 85 8 38 1 89 8 18 1 93 7 77 2 00 7 56 2 04 15 10 8 90 1 64 8 68 1 68 8...

Page 20: ...w direction louver Up Horizontal airflow direction louver Left Right Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 1 2 Unit m s m m 0 1 2 3 4 5 6 7 8 9 2 0 1 0 0 5 3 2 1 0 1 2 3 Unit m s m m 0 1 2 3 4 5 6 7 8 9 2 0 2 0 1 0 1 0 0 5 0 5 2 0 0 5 1 0 3 2 1 0 Uni...

Page 21: ... airflow direction louver Left Right Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 1 0 1 2 Unit m s m m 0 1 2 3 4 5 6 7 8 9 2 0 1 0 0 5 2 0 2 0 1 0 1 0 0 5 0 5 3 2 1 0 1 2 3 Unit m s m m 0 1 2 3 4 5 6 7 8 9 2 0 1 0 0 5 3 2 1 0 Unit m s m m 0 1 2 3 4 5 6 7 8 9 2 ...

Page 22: ...g Heating Fan speed Airflow HIGH m3 h 830 l s 231 CFM 489 MED m3 h 680 l s 189 CFM 400 LOW m3 h 580 l s 161 CFM 341 QUIET m3 h 380 l s 106 CFM 224 Fan speed Airflow HIGH m3 h 830 l s 231 CFM 489 MED m3 h 680 l s 189 CFM 400 LOW m3 h 580 l s 161 CFM 341 QUIET m3 h 380 l s 106 CFM 224 ...

Page 23: ...speed Airflow HIGH m3 h 900 l s 250 CFM 530 MED m3 h 780 l s 217 CFM 459 LOW m3 h 630 l s 175 CFM 371 QUIET m3 h 440 l s 122 CFM 259 Fan speed Airflow HIGH m3 h 900 l s 250 CFM 530 MED m3 h 780 l s 217 CFM 459 LOW m3 h 630 l s 175 CFM 371 QUIET m3 h 500 l s 139 CFM 294 ...

Page 24: ... 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 HIGH QUIET NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 HIGH QU...

Page 25: ...evel dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 HIGH QUIET NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 HIGH QUIET ...

Page 26: ... 22 WALL MOUNTED ASYG09 14LZCA 8 2 Sound level check point Microphone Microphone 1 m 0 8 m ...

Page 27: ...rinted Circuit Board Type of protection Protection form Model ASYG09LZCA ASYG12LZCA ASYG14LZCA Circuit protection Current fuse PCB 250 V 3 15 A Fan motor protection Thermal protector program Activate 105 10 C Fan motor stop Reset 90 10 C Fan motor restart ...

Page 28: ...al on off switch to a connector on the external control PCB and turning it on Circuit diagram example When function setting is Operation Stop mode Connector Input Output Remarks CNA01 Control input See external input output settings for details CNB01 Operation status output CNB02 Error status output Unit operation Initial setting after power is on Starting mode other than initial setting Operation...

Page 29: ...oup Optional part For operating the external function the wall mounted type requires the communication kit in addition to the wire UTY XWZXZ5 Part name Model name Exterior External connect kit UTY XWZXZ5 External input wire Communication kit UTY TWBXF1 Remote controller On On On Input signal Indoor unit Command Remote control operation invalidity On Off Operation Stop Forced stop Normal On Input O...

Page 30: ...ithin 10 m Relay spec Max DC 24 V 10 mA to less than 500 mA Optional part For operating the external function the wall mounted type requires the communication kit in addition to the wire UTY XWZXZ5 Part name Model name Exterior External connect kit UTY XWZXZ5 External output wire Communication kit UTY TWBXF1 Locally purchased Optional parts Example Display Indoor unit control PCB Communication kit...

Page 31: ...nction the wall mounted type requires the communication kit in addition to the wire UTY XWZXZ5 Part name Model name Exterior External connect kit UTY XWZXZ5 External output wire Communication kit UTY TWBXF1 Locally purchased Optional parts Example Display Indoor unit control PCB Communication kit Connected unit Example Relay unit 1 2 Signal Relay power supply V Connector 10 m DC 24 V On Off Error ...

Page 32: ...SYG09 14LZCA 11 Function settings To adjust the functions of this product according to the installation environment various types of function settings are available NOTE Incorrect settings can cause a product malfunction ...

Page 33: ...al enclosed with the remote controller CAUTION After disconnecting the power supply wait 30 seconds or more before reconnecting it The func tion setting will not become active unless the power supply is disconnected and then reconnect ed NOTES The air conditioner custom code is set to prior to shipment If you do not know the air conditioner custom code setting try each of the custom codes until yo...

Page 34: ...the installed environment correction of the room temperature sensor may be re quired Select the appropriate control setting according to the installed environment Function no Functions 1 11 Filter sign 2 30 Room temperature sensor control for cooling 3 31 Room temperature sensor control for heating 4 40 Auto restart 5 42 Room temperature sensor switching 6 44 Remote controller custom code 7 46 Ext...

Page 35: ...opriate custom code 7 External input control Operation Stop mode or Forced stop mode can be selected 8 Room temperature sensor switching Aux To use the temperature sensor on the wired remote controller only change the setting to Wired remote controller 01 This function will only work if the function setting 42 is set at Both 01 When the setting value is set to Both 00 more suitable control of the ...

Page 36: ...on when the outdoor unit is stopped during cooling operation 00 When the outdoor unit is stopped the indoor unit fan operates continuously following the setting on the remote controller 01 When the outdoor unit is stopped the indoor unit fan operates intermittently at a very low speed Function number Setting value Setting description Factory setting 49 00 Disable 01 Enable ...

Page 37: ...mote controller cannot be used to operate for the air conditioner NOTES If no button is pressed within 30 seconds after the custom code is displayed the system returns to the original clock indicator In this case start again from step 1 The air conditioner custom code is set to prior to shipment To change the custom code contact your retailer If you do not know the assigned code for the air condit...

Page 38: ... Celsius To change temperature unit do as follows 1 Press the TEMP Up button for at least 5 seconds to display the current temperature unit Factory setting F 2 Press the TEMP buttons to switch the temperature unit between F and C 3 With either of pressing the START STOP button or no additional button operation for 30 seconds in step 2 the temperature unit currently selected will be set ...

Page 39: ...rt name Exterior Q ty Operating manual 1 Cloth tape 1 Installation manual 1 Tapping screw large M4 25 mm 5 Wall hook bracket 1 Tapping screw small M3 12 mm 2 Remote controller 1 Air cleaning filter 2 Battery 2 Filter holder 2 Remote controller holder 1 Seal A for 14 model 1 ...

Page 40: ...rature can be controlled by detecting the temperature accurately with built in thermo sensor Wire type Polar 3 wire Optional communication kit is necessary for installation Simple remote controller UTY RSNYM Compact remote controller concentrates on the basic functions such as Start Stop fan control temperature setting and operation mode Wire type Polar 3 wire Optional communication kit is necessa...

Page 41: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG09LZCAN AOYG12LZCAN AOYG14LZCAN ...

Page 42: ...sure Material Steel sheet Color Beige Approximate color of MUNSELL 10YR7 5 1 0 Dimensions H W D Net mm 620 790 290 Gross 713 945 395 Weight Net kg 39 40 Gross 43 Connection pipe Size Liquid mm in Ø 6 35 Ø 1 4 Gas Ø 9 52 Ø 3 8 Ø 12 7 Ø 1 2 Method Flare Pre charge length m 15 Max length 20 Max height difference 15 Operation range Cooling C 10 to 46 Heating 25 to 24 Drain hose Material LDPE Size mm Ø...

Page 43: ...odels AOYG09LZCAN AOYG12LZCAN and AOYG14LZCAN 790 Top view Front view Side view 18 62 290 18 20 20 9 110 620 209 352 175 320 4 ø11 3 mm hole 540 Airflow ø20 hole Bottom view 6x20 120 6x20 120 25 23 25 23 55 55 10 10 10 20 20 hole 17 5 25 10 10 hole 102 ...

Page 44: ...upper space Unit mm When there are obstacles at the rear only When there are obstacles at the rear and sides When there are obstacles at the front only When there are obstacles at the front and rear Unit mm When there are obstacles at the rear and above When there are obstacles at the rear sides and above 100 or more 250 or more 100 or more 100 or more 600 or more 600 or more 100 or more 100 or mo...

Page 45: ...n obstruction in the upper space Unit mm When there are obstacles at the rear only When there are obstacles at the front only When there are obstacles at the front and rear Unit mm When there are obstacles at the rear and above 200 or more 1 000 or more 200 or more 1 000 or more 1 500 or more 200 or more Max 300 ...

Page 46: ...n of the lower unit When the outdoor temperature is 0 C or less do not use the accessory drain pipe and drain cap If the drain pipe and drain cap are used the drain water in the pipe may freeze in extremely cold climate For reverse cycle model only In area with heavy snowfall if the inlet and outlet of the outdoor unit is blocked with snow it might become difficult to get warm and it is likely to ...

Page 47: ...rainer 3 way valve Muffler Muffler Acccumlator 4 way valve Expansion valve Heat exchanger INDOOR Heat exchanger OUTDOOR Compressor Cooling Heating ThD ThR ThPI ThHO ThO ThR ThPI ThD ThO ThHO Thermistor Room temp Thermistor Pipe temp Thermistor Discharge temp Thermistor Outdoor temp Thermistor Heat exchanger out temp ...

Page 48: ...Thermistor Room temp Thermistor Pipe temp Thermistor Discharge temp Thermistor Outdoor temp Thermistor Heat exchanger out temp ThO ThHO Compressor Muffler Muffler Heat exchanger INDOOR Heat exchanger OUTDOOR 3 Way valve 2 Way valve Cooling Heating Receiver Strainer Strainer Expansion valve ...

Page 49: ... 45 WALL MOUNTED AOYG09 14LZCAN 5 Wiring diagrams 5 1 Models AOYG09LZCAN and AOYG12LZCAN ...

Page 50: ... 46 WALL MOUNTED AOYG09 14LZCAN 5 2 Model AOYG14LZCAN ...

Page 51: ...than outdoor unit 2 5 1 025 1 000 0 971 0 906 0 902 7 5 1 000 0 971 0 906 0 902 10 0 971 0 906 0 902 15 0 906 0 902 HEATING Pipe length m 5 7 5 10 15 20 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 933 0 925 10 0 981 0 933 0 925 7 5 1 000 0 981 0 933 0 925 5 1 017 1 000 0 981 0 933 0 925 0 1 017 1 000 0 981 0 933 0 925 Indoor unit is lower than outdoor unit 2 5 1 012 0 995 ...

Page 52: ... 1 002 1 000 0 995 0 983 0 982 Indoor unit is lower than outdoor unit 2 5 1 002 1 000 0 995 0 983 0 982 7 5 1 000 0 995 0 983 0 982 10 0 995 0 983 0 982 15 0 983 0 982 HEATING Pipe length m 5 7 5 10 15 20 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 994 0 979 10 1 012 0 994 0 979 7 5 1 000 1 012 0 994 0 979 5 0 969 1 000 1 012 0 994 0 979 0 0 969 1 000 1 012 0 994 0 979 Ind...

Page 53: ...N Refrigerant charge 7 2 Model AOYG14LZCAN Refrigerant charge Refrigerant type R410A Refrigerant amount g 1 300 Total pipe length m 15 or less 20 Max 20 g m Additional charge g 0 100 Refrigerant type R410A Refrigerant amount g 1 400 Total pipe length m 15 or less 20 Max 20 g m Additional charge g 0 100 ...

Page 54: ...CAN Cooling Heating 8 2 Model AOYG12LZCAN Cooling Heating 8 3 Model AOYG14LZCAN Cooling Heating m3 h 1 350 l s 375 CFM 795 m3 h 1 840 l s 511 CFM 1083 m3 h 1 680 l s 467 CFM 989 m3 h 1 840 l s 511 CFM 1083 m3 h 2 050 l s 569 CFM 1206 m3 h 1 840 l s 511 CFM 1083 ...

Page 55: ...C 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65...

Page 56: ...d pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 ...

Page 57: ...UNTED AOYG09 14LZCAN 9 2 Sound level check point NOTE Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above 1 m Microphone Microphone Rear Airflow Rear view Side view ...

Page 58: ...ker differ in each country or region select appropriate devices complied to the regional standard 3 Limit voltage drop to less than 2 If voltage drop is 2 or more increase cable conductor size Model name AOYG09LZCAN AOYG12LZCAN AOYG14LZCAN Power supply Voltage V 230 Frequency Hz 50 Max operating current 1 A 11 9 14 9 Starting current A 2 9 4 0 5 3 Wiring spec 2 Circuit breaker current A 15 20 Powe...

Page 59: ...0 A 250 V 5 A 250 V 5 A Current fuse Filter PCB 250 V 20 A 250 V 5 A Current fuse Main PCB 250 V 15 A 250 V 5 A 250 V 3 15 A 250 V 3 15 A Fan motor protection Thermal protection program Activate 110 15 C Fan motor stop Reset 95 10 C Fan motor restart Compressor protection Thermal protection program Discharge temp Activate 110 C Compressor stop Reset After 7 minutes Compressor restart ...