![Fujitsu AOYG09LZCAN Design & Technical Manual Download Page 42](http://html.mh-extra.com/html/fujitsu/aoyg09lzcan/aoyg09lzcan_design-and-technical-manual_2344249042.webp)
- 38 -
WA
LL
MOUN
TED
AOY
G
09-
14LZ
CAN
1. Specifications
Type
Inverter heat pump
Model name
AOYG09LZCAN
AOYG12LZCAN
AOYG14LZCAN
Power supply
230 V ~ 50 Hz
Available voltage range
198—264 V
Starting current
A
2.9
4.0
5.3
Fan
Airflow rate
Cooling
m
3
/h
1,350
1,680
2,050
Heating
1,840
Type × Q'ty
Propeller fan × 1
Motor output
W
115
Sound pressure level *1
Cooling
dB (A)
39
43
49
Heating
47
49
Sound power level
Cooling
dB (A)
52
57
61
Heating
58
59
61
Heat exchanger type
Dimensions
(H × W × D)
mm
588 × 881 × 36.4
Fin pitch
1.3
Rows × Stages
2 × 28
Pipe type
Copper
Fin type
Type (Material)
Corrugate (Aluminum)
Surface treatment
Corrosion resistance
Compressor
Type × Q'ty
Rotary × 1
Motor output
W
850
1,000
Refrigerant
Type (Global warming potential)
R410A
Charge
g
1,300
1,400
Refrigerant oil
Type
FREOL
α
68SZ
Amount
cm
3
350
Enclosure
Material
Steel sheet
Color
Beige
Approximate color of MUNSELL 10YR7.5/1.0
Dimensions
(H × W × D)
Net
mm
620 × 790 × 290
Gross
713 × 945 × 395
Weight
Net
kg
39
40
Gross
43
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas
Ø 9.52 (Ø 3/8)
Ø 12.7 (Ø 1/2)
Method
Flare
Pre-charge length
m
15
Max. length
20
Max. height difference
15
Operation range
Cooling
°C
-10 to 46
Heating
-25 to 24
Drain hose
Material
LDPE
Size
mm
Ø 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/ 19 °CWB, and outdoor temperature of 35 °CDB/ 24 °CWB.
– Heating: Indoor temperature of 20 °CDB/ 15 °CWB, and outdoor temperature of 7 °CDB/ 6 °CWB.
– Pipe length: 5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Summary of Contents for AOYG09LZCAN
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG09LZCA ASYG12LZCA ASYG14LZCA ...
Page 26: ... 22 WALL MOUNTED ASYG09 14LZCA 8 2 Sound level check point Microphone Microphone 1 m 0 8 m ...
Page 41: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG09LZCAN AOYG12LZCAN AOYG14LZCAN ...
Page 49: ... 45 WALL MOUNTED AOYG09 14LZCAN 5 Wiring diagrams 5 1 Models AOYG09LZCAN and AOYG12LZCAN ...
Page 50: ... 46 WALL MOUNTED AOYG09 14LZCAN 5 2 Model AOYG14LZCAN ...