2-6. E: 41. Room temperature sensor error (Indoor unit)
Indicator
Indoor unit
Operation indicator
4 time flash
Timer indicator
1 time flash
Economy indicator
Continuous flash
Error code
E: 41
Detective actuator
Indoor unit main PCB
Room temperature thermistor is open or short is
detected always.
Room temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
•
For the room thermistor resistance value, refer to
"Thermistor resistance values"
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of each indoor unit and check terminal voltage at thermis-
tor (DC 5.0 V).
NOTE:
For details of thermistor connector, refer to "Wiring diagrams" in Chapter 2.
TECHNICAL DATA AND PARTS LIST.
If the voltage does not appear, replace main PCB.
↓
End
2-6. E: 41. Room temperature sensor error (Indoor unit)
- (03-9) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AOYG09KHCAN
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 01 27 SR_CH01_AS032EF_01 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 27 SR_CH02_AS032EF_01 ...
Page 35: ...3 TROUBLESHOOTING 2020 03 19 SR_CH03_AS032EF_01 ...
Page 82: ...5 2 Outdoor unit 03 46 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 83: ...4 CONTROL AND FUNCTIONS 2020 04 07 SR_CH04_AS032EF_01 ...
Page 117: ...5 FILED WORKING 2020 04 07 SR_CH05_AS032EF_01 ...