2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Indicator
Indoor unit
Operation indicator
1 time flash
Timer indicator
2 time flash
Economy indicator
Continuous flash
Error code
E: 12
Detective actuator
Indoor unit
Main PCB
When the indoor unit cannot receive the signal from
Wired remote controller more than 1 minute during
normal operation.
Wired remote control
Forecast of cause
Terminal connection abnormal
Wired remote control failure
Main PCB failure
Check point 1. Check the connection of terminal
After turning off the power, check & correct the
followings.
•
Check the connection of terminal between
remote controller and indoor unit, and check
if there is a disconnection of the cable.
↓
Check point 2. Check connection
•
If it is DC 5 V, remote controller is failure.
(Main PCB is normal)
–
Replace Remote Control
•
If it is DC 0 V, main PCB is failure. (Check
remote controller once again)
–
Replace main PCB
Check voltage at CN2 (terminal 1—3)
of UTY-TWBXF (Communication kit)..
(Power supply to the remote controller)
Upon correcting the removed connec-
tor or mis-wiring, reset the power.
↓
End
2-3. E: 12. Wired remote controller communication error (Indoor unit)
- (03-6) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AOYG09KHCAN
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 01 27 SR_CH01_AS032EF_01 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 27 SR_CH02_AS032EF_01 ...
Page 35: ...3 TROUBLESHOOTING 2020 03 19 SR_CH03_AS032EF_01 ...
Page 82: ...5 2 Outdoor unit 03 46 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 83: ...4 CONTROL AND FUNCTIONS 2020 04 07 SR_CH04_AS032EF_01 ...
Page 117: ...5 FILED WORKING 2020 04 07 SR_CH05_AS032EF_01 ...