1. Specifications
1-1. Models: ARXG09KLLAP, ARXG12KLLAP, ARXG14KLLAP,
and ARXG18KLLAP
Type
Duct
Inverter heat pump
Model name
ARXG09KLLAP
ARXG12KLLAP
ARXG14KLLAP
ARXG18KLLAP
Power supply
230 V ~ 50 Hz
Power supply intake
Outdoor unit
Available voltage range
198—264 V
Capacity
Cooling
Rated
kW
2.5
3.5
4.3
5.2
Btu/h
8,500
11,900
14,700
17,700
Min.—Max.
kW
0.90—2.70
0.90—3.70
0.90—4.50
0.90—5.40
Btu/h
3,100—9,200
3,100—12,600
3,100—15,300
3,100—18,400
Heating
Rated
kW
3.2
4.1
5.0
6.0
Btu/h
10,900
14,000
17,000
20,500
Min.—Max.
kW
0.90—3.90
0.90—4.40
0.90—5.30
0.90—6.30
Btu/h
3,100—13,300
3,100—15,000
3,100—18,000
3,100—21,400
Input power
Cooling
Rated
kW
0.69
1.09
1.37
1.66
Max.
1.59
1.78
2.12
2.33
Heating
Rated
0.88
1.17
1.42
1.71
Max.
1.59
1.78
2.12
2.33
Current
Cooling
Rated
A
3.4
5.2
6.4
7.6
Heating
4.4
5.8
6.6
7.9
Power factor
Cooling
%
88.2
91.1
93.1
95.0
Heating
87.0
87.7
93.5
94.1
EER
Cooling
kW/kW
3.62
3.21
3.14
3.13
COP
Heating
3.64
3.50
3.52
3.51
Moisture removal
L/h (pints/h)
0.7 (1.2)
1.3 (2.3)
1.5 (2.6)
2.0 (3.5)
Maximum operating current *1
Cooling
A
6.9
7.7
9.2
10.1
Heating
6.9
7.7
9.2
10.1
Fan
Airflow rate
Cooling
HIGH
m
3
/h
600
650
800
940
MED
550
600
700
880
LOW
500
550
600
820
QUIET
450
480
750
Heating
HIGH
600
650
800
940
MED
550
600
700
880
LOW
500
550
600
820
QUIET
450
480
750
Type × Q'ty
Sirocco fan × 2
Sirocco fan × 3
Motor output
W
81
Recommended static pressure range
Pa
0 to 90
Sound pressure level *2
Cooling
HIGH
dB (A)
28
29
32
MED
27
28
30
LOW
26
28
29
QUIET
25
26
27
Heating
HIGH
28
29
32
MED
26
28
30
LOW
25
26
28
29
QUIET
24
25
27
Heat exchanger type
Dimensions (H × W × D)
mm
294 × 500 × 39.9
294 × 700 × 39.9
Fin pitch
1.3
Rows × Stages
3 × 14
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
Steel sheet
Color
—
Dimensions
(H × W × D)
Net
mm
198 × 700 × 620
198 × 900 × 620
Gross
276 × 968 × 772
276 × 1,168 × 772
Weight
Net
kg
17
20
Gross
22
26
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas
Ø 9.52 (Ø 3/8)
Ø 12.70 (Ø 1/2)
Method
Flare
Drain hose
Material
PVC
Size
mm
Ø 25 (I.D.), Ø 32 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote control (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
™
)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Standard static pressure: 25 Pa
– Pipe length: 5.0 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
1-1. Models: ARXG09KLLAP, ARXG12KLLAP, ARXG14KLLAP, and ARXG18KLLAP
- (01-1) -
1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION