Installation and operating manual “1350-EN”
41
Heat pump, Split, single service
2920
S
With electrical utility lock (EX4)
Locked, Released
Released
Released
: HP = ON _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _ Boiler = ON
Locked
: HP = off _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _ Boiler = ON
Additional generator (Boiler connection)
3700
S
Release under outside temperature
--- , -50 … 50 °C
0,5 °C
2 °C
3705
I
Time delay on stopping
0 … 120 min
1 min
20
Domestic hot water (DHW) (Only with the DWH kit option)
5020
S
Overheight initial setting
0 … 30°C
1 °C
5 °C
5024
S
Differential
0 … 20°C
1 °C
7 °C
5030
S
Limitation on load duration
10 … 600 min
10 min
90 min
5060
S
Electrical resistance regime
Replacement, Summer,
Always, Cooling regime
Replacement
5061
S
Release of electrical resistance
24h/day, Release of DHW,
Programme 4/DHW
Release of
DHW
Installation configuration
5700
I
Pre-setting
1,2,3...12
1
1
This control enables you to choose one of the 8 pre-selected installation configurations. The hydraulic layouts for
the various configurations are detailed in the section: "Installation Configurations".
– Pre-setting 1 : 1 heating circuit
– Pre-setting 2 : 1 heating circuit and DHW tank.
– Pre-setting 3 : 2 heating circuits.
– Pre-setting 4 : 2 heating circuits and DHW tank.
– Pre-setting 5 : Boiler connection and 1 heating circuit.
– Pre-setting 6 : Boiler connection and 2 heating circuits
– Pre-setting 7 : Boiler connection, 1 heating circuit and DHW tank.
– Pre-setting 8 : Boiler connection, 2 heating circuits and DHW tank.
– Pre-setting 9 to 12 : Do not use for heat pump model "S". Reserved only for heat pump model "Duo"
5711
S
Cooling circuit 1
Off, System with 4 tubes,
System with 2 tubes
Off
5870
S
Combined DHW tank
no, yes
No
6046
I
Function input H2
1 - Operating mode change HCs + DHW
2 - Operating mode change HCs
3 - Operating mode change HC1
4 - Operating mode change HC2
6 - Error/alarm message
9 - Dew point monitoring
16 - Swimming pool release
1 … 16
1
9
6047
I
Contact type H2
NC - Normally-closed, NO - Normally-opened
NC, NO
NO
6100
S
Outside temperature sensor correction
-3 … 3 °C
0,1 °C
0 °C
6120
S
Installation frost-free mode
ON, Off
ON
6205
S
Re-initialise parameters
No, yes
No
6220
S
oftware version (RVS)
0...99
0
Error
6711
U
Heat pump Reset
No, yes
No
6740
S
Temperature alarm initiation CC1
---, 10… 240 min
10 min
---
Line
Function
Setting range
or display
Setting
increment
Basic