2-21. E: A1. Discharge temperature error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
10 time flash
Timer indicator
1 time flash
Economy indicator
Continuous flash
Error code
E: A1
Detective actuator
Outdoor unit main PCB
Protection stop by discharge temperature ≥ 230 °F
(110 °C) during compressor operation generated 2 times
within 24 hours.
Discharge temperature thermistor
Forecast of cause
3-way valve not opened
EEV or capillary tube defective, strainer clogged
Outdoor unit operation failure, foreign matter on heat
exchanger
Discharge temperature thermistor failure
Insufficient refrigerant
Main PCB failure
Check point 1. Check if 3-way valve is open
If the 3-way valve is closed, open the 3-way valve and check operation.
NOTE:
For cooling operation, check gas side of the 3-way valve.
For heating operation, check liquid side of the 3-way valve.
↓
Check point 2. Check any of the electronic expansion valve (EEV), capillary tube, or strainer, or all
•
Check if EEV open or there is a capillary tube defect.
Refer to outdoor unit Electrronic Expansion Valve (EEV) or Capillary tube in
•
Check the strainer clogging.
↓
Check point 3. Check the outdoor unit fan and heat exchanger
•
Check for foreign object at heat exchanger
•
Check if fan can be rotated by hand.
•
Check the motor. (Refer to outdoor unit fan motor in
↓
Check point 4. Check the discharge thermistor
The discharge temperature thermistor characteristics check. (Check by disconnecting thermistor
from PCB.)
NOTE:
For the characteristics of the thermistor, refer to
"Thermistor resistance values"
↓
2-21. E: A1. Discharge temperature error (Outdoor unit)
- (03-27) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AOUH09LPAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 18 SR_CH01_AS050EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 15 SR_CH02_AS050EF_02 ...
Page 39: ...3 TROUBLESHOOTING 2021 07 XX SR_CH03_AS050EF_01 ...
Page 41: ...5 2 Outdoor unit 03 43 CONTENTS continued ...
Page 42: ......
Page 87: ...4 CONTROL AND FUNCTIONS 2021 07 XX SR_CH04_AS050EF_01 ...
Page 123: ...5 FILED WORKING 2021 06 28 SR_CH05_AS050EF_03 ...