2-3. Combination of external input and output
By combining the function setting of the indoor unit and rotary switch setting of the External Input
and Output PCB, you can select various combinations of functions.
Combination examples of external input and output are as follows:
Mode
Function
setting
Rotary
SW
External input
Indoor unit
External Input and Output PCB
CN46
1
CN313
2
CN314
0-1
60—00
1
Operation/Stop
(Function setting 46-00)
or
Forced stop
(Function setting 46-02)
Operation/Stop
Not available
Operation
Stop
0-2
60-00
2
Forced thermostat Off
Not available
1
60-01
3
Mechanical cooling
Off
2
60-02
4
Forced thermostat Off
3
60-03
5
Mechanical cooling
On
4
60-04
6
Mechanical cooling
On
5
60-05
7
Forced thermostat Off
6
60-06
8
Forced thermostat Off
7
60-07
9
Mechanical cooling
Off
8
60-08
A
Forced thermostat Off
9
60-09
B
Forced thermostat Off
10
60-10
C
Forced thermostat Off
11
60-11
D
Forced thermostat Off
Mode
Function
setting
Rotary
SW
External output
Indoor unit
External Input and Output PCB
CN47
1
CN310
2
CN311
3
CN312
0-1
60-00
1
Operation/Stop
Operation/Stop
Error status
Indoor unit fan
operation status
0-2
60-00
2
Operation/Stop
Error status
Indoor unit fan
operation status
External heater
output
1
60-01
3
Cooling
thermostat On
Error status
Indoor unit fan
operation status
External heater
output
2
60-02
4
Cooling
thermostat On
Error status
Remote
controller output
External heater
output
3
60-03
5
Cooling
thermostat On
Cooling high/low
output
Remote
controller output
External heater
output
4
60-04
6
Cooling
thermostat On
Error status
Remote
controller output
Cooling high/low
output
5
60-05
7
Heating
thermostat On
Error status
Indoor unit fan
operation status
External heater
output
6
60-06
8
Operation/Stop
Error status
Indoor unit fan
operation status
Heating
thermostat On
7
60-07
9
Cooling
thermostat On
Error status
Heating
thermostat On
External heater
output
8
60-08
A
Cooling
thermostat On
Heating
thermostat On
Remote
controller output
External heater
output
9
60-09
B
Error status
Operation/Stop
Indoor unit fan
operation status
External heater
output
10
60-10
C
Indoor unit fan
operation status
Operation/Stop
Error status
External heater
output
2-3. Combination of external input and output
- (05-16) -
2. External input and output
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AOUH09LPAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 18 SR_CH01_AS050EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 15 SR_CH02_AS050EF_02 ...
Page 39: ...3 TROUBLESHOOTING 2021 07 XX SR_CH03_AS050EF_01 ...
Page 41: ...5 2 Outdoor unit 03 43 CONTENTS continued ...
Page 42: ......
Page 87: ...4 CONTROL AND FUNCTIONS 2021 07 XX SR_CH04_AS050EF_01 ...
Page 123: ...5 FILED WORKING 2021 06 28 SR_CH05_AS050EF_03 ...