Heat pump prohibition control
Perform heating by external heater only. Indoor unit is continuous thermostat off.
Operation
Condition
Heater on
Heater is on as shown in following diagram of heating temperature.
Heater off
•
Heater is off as shown in following diagram of heating temperature.
•
Other than heating mode
•
Error occurred
•
Forced thermostat off
• Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting “Thon”.
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts
Tr-Ts (=Thon) ≤ -0.9°F (-0.5°C)
Tr-Ts ≥ 0.9°F
(0.5°C)
•
Operation status
On
0.9°F (0.5°C)
-0.9°F (-0.5°C)
On
12 V
On
Off
Off
0 V
Off
Heating operation
Heater
Fan
Air conditioner
Room temperature
Set temp.
3 min or more
NOTE:
In following operations, compressor will be on.
• Other than heating
• Test run
2-4. Details of function
- (05-25) -
2. External input and output
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AOUH09LPAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 18 SR_CH01_AS050EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 15 SR_CH02_AS050EF_02 ...
Page 39: ...3 TROUBLESHOOTING 2021 07 XX SR_CH03_AS050EF_01 ...
Page 41: ...5 2 Outdoor unit 03 43 CONTENTS continued ...
Page 42: ......
Page 87: ...4 CONTROL AND FUNCTIONS 2021 07 XX SR_CH04_AS050EF_01 ...
Page 123: ...5 FILED WORKING 2021 06 28 SR_CH05_AS050EF_03 ...