2-7. E: 41. Room temperature sensor error (Indoor unit)
Indicator
Indoor unit
Operation indicator
4 time flash
Timer indicator
1 time flash
Economy indicator
Continuous flash
Error code
E: 41
Detective actuator
Indoor unit main PCB
Room temperature thermistor is open or short is
detected always.
Room temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
•
For the room thermistor resistance value, refer to
"Thermistor resistance values"
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of each indoor unit and check terminal voltage at thermis-
tor (DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-18.
(09-12 model: CN11)
If the voltage does not appear, replace main PCB.
↓
End
2-7. E: 41. Room temperature sensor error (Indoor unit)
- (03-11) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AOUH09LPAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 18 SR_CH01_AS050EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 15 SR_CH02_AS050EF_02 ...
Page 39: ...3 TROUBLESHOOTING 2021 07 XX SR_CH03_AS050EF_01 ...
Page 41: ...5 2 Outdoor unit 03 43 CONTENTS continued ...
Page 42: ......
Page 87: ...4 CONTROL AND FUNCTIONS 2021 07 XX SR_CH04_AS050EF_01 ...
Page 123: ...5 FILED WORKING 2021 06 28 SR_CH05_AS050EF_03 ...