Type
Wall mounted
Inverter heat pump
Model name
ASUG09LZAS
ASUG12LZAS
ASUG15LZAS
Drain hose
Material
PP+LLDPE
Tip diameter
in (mm)
Ø7/32 (Ø13.8) (I.D.), Ø5/8 to 21/32 (Ø15.8 to 16.7) (O.D.)
Operation range
Cooling
°F (°C)
64 to 90 (18 to 32)
%RH
80 or less
Heating
°F (°C)
60 to 86 (16 to 30)
Remote controller type
Wireless (Wired, Mobile app*
5
[FGLair
™
] [option])
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80°FDB (26.67°CDB)/67°FWB (19.44°CWB), and outdoor temperature of 95°FDB (35°CDB)/75°FWB (23.9°CWB).
– Heating: Indoor temperature of 70°FDB (21.11°CDB)/59°FWB (15.56°CWB), and outdoor temperature of 47°FDB (8.33°CDB)/43°FWB (6.11°CWB).
– *1: Heating (17°F): Indoor temperature of 70°FDB (21.11°CDB)/60°FWB (15.56°CWB), and outdoor temperature of 17°FDB (-8.33°CDB)/15°FWB (-9.44°CWB).
– *2: Heating (5°F): Indoor temperature of 70°FDB (21.11°CDB)/60°FWB (15.56°CWB), and outdoor temperature of 5°FDB (-15.0°CDB)/4°FWB (-15.56°CWB).
– Test conditions are based on AHRI 210/240 2023.
– Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *3: Maximum current is maximum value when operated within the operation range.
• *4: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *5: Available on Google Play
™
store or on App Store
®
. Optional WLAN Adapter is also required. For details, refer to the setting manual.
M condition
Model name
ASUG09LZAS
ASUG12LZAS
ASUG15LZAS
Capacity
Cooling
Rated
kW
2.64
3.52
4.25
Btu/h
9,000
12,000
14,500
Min.—Max.
kW
0.91—3.52
0.91—3.99
0.91—5.39
Btu/h
3,100—12,000
3,100—13,600
3,100—18,400
Heating
Rated
kW
3.52
4.69
5.28
Btu/h
12,000
16,000
18,000
Min.—Max.
kW
0.91—6.45
0.91—6.48
0.91—7.00
Btu/h
3,100—22,000
3,100—22,100
3,100—23,900
Heating
(17°F)*
Rated
kW
2.17
2.93
3.28
Btu/h
7,400
10,000
11,200
Max.
kW
4.69
5.13
6.30
Btu/h
16,000
17,500
21,500
Input power
Cooling
Rated
kW
0.50
0.79
1.04
Min.—Max.
0.11—0.85
0.11—0.99
0.15—1.56
Heating
Rated
0.66
1.01
1.15
Min.—Max.
0.17—1.93
0.17—1.94
0.15—2.19
Heating
(17°F)*
Rated
0.60
0.88
1.01
Max.
2.06
2.59
Current
Cooling
Rated
A
2.5
3.8
4.8
Heating
3.3
4.7
5.2
EER
Cooling
kW/kW
5.28
4.46
4.09
Btu/hW
18.0
15.2
13.9
COP
Heating
kW/kW
5.34
4.64
4.60
Btu/hW
18.2
15.8
15.7
SEER
Cooling
Btu/hW
33.1
29.4
25.3
HSPF
Heating
Btu/hW
14.2
14.0
13.4
Power factor
Cooling
%
87
90
94
Heating
87
93
96
NOTES:
Specifications are based on the following conditions:
• Cooling: Indoor temperature of 80°FDB (26.67°CDB)/67°FWB (19.44°CWB), and outdoor temperature of 95°FDB (35°CDB)/75°FWB (23.9°CWB).
• Heating: Indoor temperature of 70°FDB (21.11°CDB)/59°FWB (15.56°CWB), and outdoor temperature of 47°FDB (8.33°CDB)/43°FWB (6.11°CWB).
• *: Heating (17°F): Indoor temperature of 70°FDB (21.11°CDB)/60°FWB (15.56°CWB), and outdoor temperature of 17°FDB (-8.33°CDB)/15°FWB (-9.44°CWB).
• Test conditions are based on AHRI 210/240 2017.
• Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
1-1. Indoor unit
- (01-2) -
1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION
Summary of Contents for AOUG09LZAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS024EF_03 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 10 12 SR_CH02_AS024EF_05 ...
Page 33: ...3 TROUBLESHOOTING 2022 10 12 SR_CH03_AS024EF_07 ...
Page 36: ......
Page 117: ...4 CONTROL AND FUNCTIONS 2022 10 12 SR_CH04_AS024EF_03 ...
Page 151: ...5 FILED WORKING 2022 10 12 SR_CH05_AS024EF_04 ...