8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢
Models: AOUG09LZAS1 and AOUG12LZAS1
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
122.0°F (50°C) ≤ Ta
4.5 A
4.0 A
114.8°F (46°C) ≤ Ta < 122.0°F (50°C)
4.5 A
4.0 A
104.0°F (40°C) ≤ Ta < 114.8°F (46°C)
6.0 A
5.5 A
53.6°F (12°C) ≤ Ta < 104.0°F (40°C)
8.5 A
8.0 A
35.6°F (2°C) ≤ Ta < 53.6°F (12°C)
8.5 A
8.0 A
Ta < 35.6°F (2°C)
8.5 A
8.0 A
Heating
62.6°F (17°C) ≤ Ta
7.0 A
6.5 A
53.6°F (12°C) ≤ Ta < 62.6°F (17°C)
9.0 A
8.5 A
41.0°F (5°C) ≤ Ta < 53.6°F (12°C)
10.0 A
9.5 A
Ta < 41.0°F (5°C)
10.0 A
9.5 A
¢
Model: AOUG15LZAS1
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
50°C ≤ Ta
4.5 A
4.0 A
46°C ≤ Ta < 50°C
4.5 A
4.0 A
40°C ≤ Ta < 46°C
6.0 A
5.5 A
12°C ≤ Ta < 40°C
9.0 A
8.5 A
2°C ≤ Ta < 12°C
9.0 A
8.5 A
Ta < 2°C
9.0 A
8.5 A
Heating
17°C ≤ Ta
7.0 A
6.5 A
12°C ≤ Ta < 17°C
9.0 A
8.5 A
5°C ≤ Ta < 12°C
11.0 A
10.5 A
Ta < 5°C
12.5 A
12.0 A
8-4. Cooling pressure over-rise protection
When the outdoor unit heat exchanger temperature reaches trigger condition below, the compressor
is stopped and trouble display is performed.
Trigger condition
149.0°F (65°C)
8-5. Low outdoor temperature protection
When the outdoor temperature sensor detects lower than the trigger condition below, the compres-
sor is stopped.
Operation mode
Cooling/Dry
Trigger condition
-15°C
Release condition
-10°C
8-3. Current release control
- (04-30) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AOUG09LZAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS024EF_03 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 10 12 SR_CH02_AS024EF_05 ...
Page 33: ...3 TROUBLESHOOTING 2022 10 12 SR_CH03_AS024EF_07 ...
Page 36: ......
Page 117: ...4 CONTROL AND FUNCTIONS 2022 10 12 SR_CH04_AS024EF_03 ...
Page 151: ...5 FILED WORKING 2022 10 12 SR_CH05_AS024EF_04 ...