14) Outdoor temperature zone boundary temperature B
Setting required if changing of the outdoor temperature setting for heat pump only zone is required
when auxiliary heater control by outdoor temperature 1 is performed on the indoor unit. For details,
refer to “External heater output” in
Chapter 2-4. "Details of function"
Function number
Setting value
Setting description
Factory setting
67
00
42.8 °F (6 °C)
♦
01
14.0 °F (-10 °C)
02
17.6 °F (-8 °C)
03
21.2 °F (-6 °C)
04
24.8 °F (-4 °C)
05
28.4°F (-2 °C)
06
32.0 °F (0 °C)
07
35.6 °F (2 °C)
08
39.2 °F (4 °C)
09
42.8 °F (6 °C)
10
46.4 °F (8 °C)
11
50.0 °F (10 °C)
12
53.6 °F (12 °C)
13
57.2 °F (14 °C)
14
60.8 °F (16 °C)
15
64.4 °F (18 °C)
15) Heat insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment.
"Standard insulation" (00) allows system to rapidly respond to the cooling or heating load changes.
"High insulation" (01) is when the heat insulation structure of the building is high and does not re-
quire system to rapidly respond to cooling or heating load changes.
When "High insulation" (01) is selected:
• Overheating (overcooling) is prevented at the start-up.
• All room-temperature control settings (Function 30, 31, 35, and 36) will reset to "No correction
0.0 °F (0.0 °C)".
Function number
Setting value
Setting description
Factory setting
95
00
Standard insulation
♦
01
High insulation
NOTE:
When changing Function 95, perform this setting before other room-temperature control
settings (Function 30, 31, 35, and 36). If Function 95 is not set first, room-temperature con-
trol settings (Function 30, 31, 35, and 36) will be reset and you must re-do them again.
1-1. Function settings by using remote controller
- (05-8) -
1. Function settings
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AOUG09LZAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS024EF_03 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 10 12 SR_CH02_AS024EF_05 ...
Page 33: ...3 TROUBLESHOOTING 2022 10 12 SR_CH03_AS024EF_07 ...
Page 36: ......
Page 117: ...4 CONTROL AND FUNCTIONS 2022 10 12 SR_CH04_AS024EF_03 ...
Page 151: ...5 FILED WORKING 2022 10 12 SR_CH05_AS024EF_04 ...