2-9. E: 51. Indoor unit fan motor error (Indoor unit)
Indicator
Indoor unit
Operation indicator
5 time flash
Timer indicator
1 time flash
Economy indicator
Continuous flash
Error code
E: 51
Detective actuator
Indoor unit
main PCB
When the condition that actual frequency of indoor fan is
below 1/3 of target frequency is continued more than 56
seconds.
Fan motor
Forecast of cause
Fan rotation failure
Fan motor winding open
Motor protection by surrounding temperature rise
Control PCB failure
Indoor unit fan motor failure
Check point 1. Check rotation of fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
→ If fan or bearing is abnormal, replace it.
↓
Check point 2. Check ambient temp. around motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat)
→ Upon the temperature coming down, restart operation.
↓
Check point 3. Check indoor unit fan motor
Check Indoor unit fan motor. (Refer to indoor unit fan motor in
03-34.)
→ If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
↓
Check point 4. Replace main PCB
If Check Point 1 to 3 do not improve the symptom, replace main PCB.
↓
End
2-9. E: 51. Indoor unit fan motor error (Indoor unit)
- (03-12) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AOUG09LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2019 12 20 SR_CH01_AS023EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 28 SR_CH02_AS023EF_01 ...
Page 33: ...3 TROUBLESHOOTING 2020 01 30 SR_CH03_AS023EF_02 ...
Page 77: ...4 CONTROL AND FUNCTIONS 2020 03 25 SR_CH04_AS023EF_02 ...
Page 107: ...5 FILED WORKING 2020 02 03 SR_CH05_AS023EF_01 ...