1-5. Compressor frequency limitation by outdoor temperature
The minimum compressor frequency is limited by outdoor temperature as below.
•
Cooling/Dry mode
F zone
38°C
E zone
19°C
D zone
10°C
C zone
B zone
A zone
0°C
-10°C
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOUG09LMAS1
AOUG12LMAS1
A zone
35 rps
B zone
35 rps
C zone
35 rps
D zone
15 rps
E zone
15 rps
F zone
36 rps
•
Heating mode
F zone
19°C
E zone
5°C
D zone
0°C
C zone
B zone
A zone
-15°C
-25°C
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOUG09LMAS1
AOUG12LMAS1
A zone
37 rps
B zone
37 rps
C zone
36 rps
D zone
15 rps
E zone
15 rps
F zone
1 rps
1-5. Compressor frequency limitation by outdoor temperature
- (04-4) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS