11) Control switching of external heaters
Sets the control method for external heater to be used.
For details, refer to
Function
number
Setting value
Setting description
Factory
setting
61
00
Auxiliary heater control 1
♦
01
Auxiliary heater control 2
02
Heat pump prohibition control
03
Auxiliary heater control by outdoor temperature 1
04
Auxiliary heater control by outdoor temperature 2
12) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to
Function
number
Setting value
Setting description
Factory
setting
Heater: On
Heater: Off
62
00
-5.4 °F (-3 °C)
-1.8 °F (-1 °C)
♦
01
-3.6 °F (-2 °C)
-1.8 °F (-1 °C)
02
-3.6 °F (-2 °C)
-1.8 °F (-1 °C)
03
-5.4 °F (-3 °C)
-1.8 °F (-1 °C)
04
-7.2 °F (-4 °C)
-1.8 °F (-1 °C)
05
-9.0 °F (-5 °C)
-1.8 °F (-1 °C)
13) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to
Function number
Setting value
Setting description
Factory setting
66
00
-4.0 °F (-20 °C)
♦
01
-0.4 °F (-18 °C)
02
3.2 °F (-16 °C)
03
6.8 °F (-14 °C)
04
10.4 °F (-12 °C)
05
14.0°F (-10 °C)
06
17.6 °F (-8 °C)
07
21.2 °F (-6 °C)
08
24.8 °F (-4 °C)
1-1. Function settings by using remote controller
- (05-7) -
1. Function settings
FIELD
WORKING
FIELD
WORKING
Summary of Contents for AOUG09LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2019 12 20 SR_CH01_AS023EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 28 SR_CH02_AS023EF_01 ...
Page 33: ...3 TROUBLESHOOTING 2020 01 30 SR_CH03_AS023EF_02 ...
Page 77: ...4 CONTROL AND FUNCTIONS 2020 03 25 SR_CH04_AS023EF_02 ...
Page 107: ...5 FILED WORKING 2020 02 03 SR_CH05_AS023EF_01 ...