- 73 -
O
U
T
D
OOR UNIT
AOGA3
0
-60F
10. Safety devices
Type of
protection
Protection form
Model
AOGA30FBTAS
Circuit
protection
Current fuse (Near the terminal)
250 V, 5 A
Current fuse (Main PCB)
250 V, 6.3 A
Fan motor
protection
Thermal protection
program
Activate
150 ± 5 °C
Fan motor stop
Reset
96 ± 15 °C
Fan motor restart
High pressure
protection
High pressure switch
Activate
4.9 MPa
Compressor stop
Reset
3.8 MPa
Compressor restart
Compressor
protection
Internal inherent motor
protection
Activate
110 ± 5 °C Compressor stop
Reset
61 ± 9 °C Compressor restart
First cycle trip: 51 A
Pressure relief valve
(differential pressure
range)
Activate
3.9—4.2 MPa
Type of
protection
Protection form
Model
AOGA36FRTAS
AOGA45FRTAS
AOGA60FRTAS
Circuit
protection
Current fuse (Near the terminal)
250 V, 5 A
250 V, 10 A
Current fuse (Main PC board)
250 V, 6.3 A
Fan motor
protection
Thermal protection
program
Activate
150± 5 °C
Fan motor stop
Reset
96± 15 °C
Fan motor restart
High pressure
protection
High pressure switch
Activate
4.9 MPa
Compressor stop
Reset
3.8 MPa
Compressor restart
Compressor
protection
Thermal protection
program (Discharge
temp.)
Activate
120 °C
Compressor stop
Reset
After 3 minutes and 90 °C or less
Compressor restart
Internal inherent motor
protection
Activate
120 ± 5 °C
Compressor stop
145 ± 5 °C
Compressor stop
125 ± 5 °C
Compressor stop
Reset
61 ± 9 °C
Compressor
restart
First cycle trip: 37
A
61 ± 9 °C
Compressor
restart
First cycle trip: 41
A
61 ± 9 °C
Compressor
restart
First cycle trip: 51
A
Pressure relief valve
(differential pressure
range)
Activate
3.9—4.2 MPa
Summary of Contents for AOGA18FBTAH
Page 2: ...1 INDOOR UNIT DTR_AR087E_02 2015 02 05 DUCT TYPE ARGA18FMTA ARGA25FMTA ...
Page 11: ... 01 08 DUCT TYPE ARGA18 25FMTA DUCT TYPE ARGA18 25FMTA WIRING DIAGRAMS 555 MODEL ARGA18FMTA ...
Page 12: ... 01 09 DUCT TYPE ARGA18 25FMTA DUCT TYPE ARGA18 25FMTA MODEL ARGA25FMTA ...
Page 35: ...DTR_AO202E_01 2015 01 19 SINGLE TYPE AOGA18FBTAH AOGA25FBTAH 2 OUTDOOR UNIT ...
Page 43: ... 02 07 OUTDOOR UNIT AOGA18 25FBTAH OUTDOOR UNIT AOGA18 25FBTAH MODEL AOGA25FBTAH ...
Page 49: ... 02 13 OUTDOOR UNIT AOGA18 25FBTAH OUTDOOR UNIT AOGA18 25FBTAH SOUND LEVEL CHECK POINT 88888 ...
Page 56: ...Part 1 INDOOR UNIT DUCT TYPE ARGA30FMTA ARGA36FMTA ARGA45FMTA ARGA60FHTA ...
Page 72: ... 17 DUCT TYPE ARGA30 60F 5 Wiring diagrams 5 1 Model ARGA30FMTA ...
Page 73: ... 18 DUCT TYPE ARGA30 60F 5 2 Models ARGA36FMTA and ARGA45FMTA ...
Page 74: ... 19 DUCT TYPE ARGA30 60F 5 3 Model ARGA60FHTA ...
Page 105: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOGA30FBTAS AOGA36FRTAS AOGA45FRTAS AOGA60FRTAS ...
Page 117: ... 62 OUTDOOR UNIT AOGA30 60F 3 2 Models AOGA36FRTAS AOGA45FRTAS and AOGA60 FRTAS ...
Page 118: ... 63 OUTDOOR UNIT AOGA30 60F 4 Wiring diagrams 4 1 Model AOGA30FBTAS ...
Page 119: ... 64 OUTDOOR UNIT AOGA30 60F 4 2 Models AOGA36FRTAS AOGA45FRTAS and AOGA60 FRTAS ...