4) Auto restart
Enable or disable automatic restart after a power interruption.
(
. . .Factory setting)
Function Number
Setting Value
Setting Description
40
00
Enable
01
Disable
* Auto restart is an emergency function such as for power outage etc.
Do not attempt to use this function in normal operation.
Be sure to operate the unit by remote controller or external device.
5) Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both" (01).
(
. . .Factory setting)
Function Number
Setting Value
Setting Description
42
00
Indoor unit
01
Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
*Remote controller sensor must be turned on by using the remote controller.
6) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
. . .Factory setting)
Function Number
Setting Value
Setting Description
46
00
Operation/Stop mode
01
(Setting prohibited)
02
Forced stop mode
7) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01). This function
will only work if the function setting 42 is set at "Both" (01).
(
. . .Factory setting)
Function Number
Setting Value
Setting Description
48
00
Both
01
Wired remote controller
Summary of Contents for AOGA18FBTAH
Page 2: ...1 INDOOR UNIT DTR_AR087E_02 2015 02 05 DUCT TYPE ARGA18FMTA ARGA25FMTA ...
Page 11: ... 01 08 DUCT TYPE ARGA18 25FMTA DUCT TYPE ARGA18 25FMTA WIRING DIAGRAMS 555 MODEL ARGA18FMTA ...
Page 12: ... 01 09 DUCT TYPE ARGA18 25FMTA DUCT TYPE ARGA18 25FMTA MODEL ARGA25FMTA ...
Page 35: ...DTR_AO202E_01 2015 01 19 SINGLE TYPE AOGA18FBTAH AOGA25FBTAH 2 OUTDOOR UNIT ...
Page 43: ... 02 07 OUTDOOR UNIT AOGA18 25FBTAH OUTDOOR UNIT AOGA18 25FBTAH MODEL AOGA25FBTAH ...
Page 49: ... 02 13 OUTDOOR UNIT AOGA18 25FBTAH OUTDOOR UNIT AOGA18 25FBTAH SOUND LEVEL CHECK POINT 88888 ...
Page 56: ...Part 1 INDOOR UNIT DUCT TYPE ARGA30FMTA ARGA36FMTA ARGA45FMTA ARGA60FHTA ...
Page 72: ... 17 DUCT TYPE ARGA30 60F 5 Wiring diagrams 5 1 Model ARGA30FMTA ...
Page 73: ... 18 DUCT TYPE ARGA30 60F 5 2 Models ARGA36FMTA and ARGA45FMTA ...
Page 74: ... 19 DUCT TYPE ARGA30 60F 5 3 Model ARGA60FHTA ...
Page 105: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOGA30FBTAS AOGA36FRTAS AOGA45FRTAS AOGA60FRTAS ...
Page 117: ... 62 OUTDOOR UNIT AOGA30 60F 3 2 Models AOGA36FRTAS AOGA45FRTAS and AOGA60 FRTAS ...
Page 118: ... 63 OUTDOOR UNIT AOGA30 60F 4 Wiring diagrams 4 1 Model AOGA30FBTAS ...
Page 119: ... 64 OUTDOOR UNIT AOGA30 60F 4 2 Models AOGA36FRTAS AOGA45FRTAS and AOGA60 FRTAS ...