Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : AS*G30LFCA
[Condition]
Ambient
temperature
Indoor 15, 20, 23 C, Outdoor 2, 7, 12 C
Refrigerant
amount
Standard amount
Piping
7.5m (Height difference 1m)
Power
voltage
50Hz - 240V
Operation
condition
TEST mode (Heating), Hi Fan, One step up from lower direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*G30LFCA
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
outdoor unit overall current with the current clamp meter at Power Cable.
length
03-08
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.4
0
2
4
6
8
10
12
14
High-pressure of outdoor unit [MPa]
[50Hz-240V]
Outdoor ambient temperature [ C]
9.0
9.5
10.0
10.5
11.0
11.5
12.0
12.5
13.0
[50Hz-240V]
23 C
20 C
15 C
Indoor ambient
temperature[ C]
Outdoor ambient temperature [ C]
Outdoor total electric current [A]
0
2
4
6
8
10
12
14
14.0
13.5
AS*G30LFCA
23 C
20 C
15 C
Indoor ambient
temperature[ C]
Summary of Contents for AO*G24LFLAO*G24LFCC
Page 3: ......
Page 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 25: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 63: ......
Page 64: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Page 75: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Oct 2012 Printed in Japan ...