4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 67°C or greater,
the compressor is stopped and trouble display is performed.
5. HIGH TEMPERATURE AND HIGH PRESSURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor
heat exchanger temperature sensor.
Indoor heat exchange
temperature
[ Control System ]
It returns to the normal operation
Compressor is stopped
53°C
55°C
63°C
50°C
The compressor frequency is
decreased 4rps(24L), 2rps(30L)
every 120seconds.
The compressor frequency is
decreased 25rps(24L), 15rps(30L)
every 120seconds.
6. COMPRESSOR TEMPERATURE PROTECTION
When the compressor temperature sensor detects higher than
110°C(24L),108°C(30L), the compressor is stopped.
The protection is released when the compressor temperature sensor detects 80°C
after 3 minutes of compressor stop.
7. HIGH PRESSURE PROTECTION
When the pressure switch becomes OFF (Open : higher than 4.2 MPa),
the compressor is stopped.
It is released when the pressure switch becomes ON (Close : lower than 3.2 MPa)
after 3 minutes of compressor stop.
For AO*G24LFL / LFCC / 30LFT
23. COMPRESSOR STOP CONTROL
When the detection value of outdoor temperature sensor is lower than Temp in the table below,
the compressor is stopped.
( Table 22 : Operation temperature of compressor stop control )
Temperature
AO*G24LFL / LFCC / 30LFT
Cooling
Heating
-15°C
Stable zone
Summary of Contents for AO*G24LFLAO*G24LFCC
Page 3: ......
Page 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 25: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 63: ......
Page 64: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Page 75: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Oct 2012 Printed in Japan ...