CAPACITY COMPENSATION RATE FOR PIPE LENGTH
2-5.
AND HEIGHT DIFFERENCE
This table is created using the maximum capacity.
MODEL
: AO
A45L
COOLING
Pipe length (m)
5
7.5
10
20
30
40
50
Height
difference H
(m)
1
Indoor unit is upper
than outdoor unit.
30
–
–
–
–
0.893
0.890
0.870
20
–
–
–
0.919
0.908
0.905
0.885
10
–
–
0.979
0.934
0.923
0.920
0.899
7.5
–
0.988
0.983
0.938
0.927
0.924
0.903
5
1.001
0.992
0.987
0.942
0.931
0.927
0.907
0
1.009
1.000
0.995
0.949
0.938
0.935
0.914
2
Indoor unit is under
than outdoor unit
-5
1.009
1.000
0.995
0.949
0.938
0.935
0.914
-7.5
–
1.000
0.995
0.949
0.938
0.935
0.914
-10
–
–
0.995
0.949
0.938
0.935
0.914
-20
–
–
–
0.949
0.938
0.935
0.914
-30
–
–
–
–
0.938
0.935
0.914
HEATING
Pipe length (m)
5
7.5
10
20
30
40
50
Height
difference H
(m)
1
Indoor unit is upper
than outdoor unit.
30
–
–
–
–
0.971
0.950
0.927
20
–
–
–
0.985
0.971
0.950
0.927
10
–
–
1.016
0.985
0.971
0.950
0.927
7.5
–
1.000
1.016
0.985
0.971
0.950
0.927
5
0.978
1.000
1.016
0.985
0.971
0.950
0.927
0
0.978
1.000
1.016
0.985
0.971
0.950
0.927
2
Indoor unit is under
than outdoor unit
-5
0.973
0.995
1.011
0.980
0.966
0.945
0.923
-7.5
–
0.993
1.009
0.978
0.963
0.943
0.920
-10
–
–
1.006
0.975
0.961
0.940
0.918
-20
–
–
–
0.966
0.951
0.931
0.909
-30
–
–
–
–
0.942
0.921
0.899
Outdoor unit
Indoor unit
Connection pipe
2 Indoor unit is under than outdoor unit.
H
Indoor unit
Outdoor unit
Connection pipe
1 Indoor unit is upper than outdoor unit.
H
Height difference H
Summary of Contents for AO*A45LBTL
Page 2: ...1 INDOOR UNIT D2D_AU041E 04 2011 03 01 CASSETTE TYPE AU A45LCLU AU A54LCLU ...
Page 44: ...D2D_AO052E 01 2009 04 30 SINGLE TYPE AO A45LBTL 2 OUTDOOR UNIT ...
Page 48: ... 02 03 OUTDOOR UNIT AO A45L OUTDOOR UNIT AO A45L REFRIGERANT CIRCUIT 22222 MODEL AO A45L ...
Page 49: ... 02 04 OUTDOOR UNIT AO A45L OUTDOOR UNIT AO A45L WIRING DIAGRAMS 22222 MODEL AO A45L ...
Page 57: ...DTR_AO081E_01 2011 03 01 SINGLE TYPE AO A45LCTL AO A54LCTL 2 OUTDOOR UNIT ...