EXTERNAL INPUT & OUTPUT
12.
EXTERNAL INPUT
12-1.
ON/OFF of the "Low noise mode" and "Peak cut mode" functions can be specified by external
signal.
LOW NOISE MODE
The following reduces the operating sound of the outdoor unit from the normal sound.
•
The air conditioner is set to the "Low noise mode" when closing the contact input of a commercial
timer or ON/OFF switch to a connector on the outdoor control PC board.
* Performance may drop depending on the outside air temperature condition, etc.
Circuit diagram example
z
Outdoor unit
control PC board
Connector
1
2
Signal
Field supply
*10m
Connected unit
Ex.) Switch
Contact capacity : 24VDC or more, 10mA or more.
* Make the distance from the PC board to the connected unit within 10m.
Use the following parts and construct a circuit as shown above.
•
Input Signal∙∙∙ON : Low noise mode, Input Signal∙∙∙OFF : Normal operation
•
* Set the "Low noise mode" level, refer to "13.FUNCTION SETTING".
ON
OFF
ON
OFF
Input Signal
Low noise mode
Parts (Optional)
z
Parts name
External connect kit
Model name
UTY-XWZXZ3
Input
Output
Connector
Remarks
Low noise mode
―
CN10
See external
input/output settings
for details.
Peak cut mode
―
CN11
―
Error status
CN12
―
Compressor status
CN13
Summary of Contents for AO*A45LBTL
Page 2: ...1 INDOOR UNIT D2D_AU041E 04 2011 03 01 CASSETTE TYPE AU A45LCLU AU A54LCLU ...
Page 44: ...D2D_AO052E 01 2009 04 30 SINGLE TYPE AO A45LBTL 2 OUTDOOR UNIT ...
Page 48: ... 02 03 OUTDOOR UNIT AO A45L OUTDOOR UNIT AO A45L REFRIGERANT CIRCUIT 22222 MODEL AO A45L ...
Page 49: ... 02 04 OUTDOOR UNIT AO A45L OUTDOOR UNIT AO A45L WIRING DIAGRAMS 22222 MODEL AO A45L ...
Page 57: ...DTR_AO081E_01 2011 03 01 SINGLE TYPE AO A45LCTL AO A54LCTL 2 OUTDOOR UNIT ...