background image

En-17

Test operation setting method

Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the indoor unit PC board to 
configure settings according to the procedures below.

Settings for starting test run 
operation

Settings for stopping test run 
operation

Press the “ENTER” button for 
more than 3 seconds.

Press the “ENTER” button for more than 3 seconds.

Press the “ENTER” button for 
more than 3 seconds.

This will be displayed when the cooling operation mode is 
canceled.

This will be displayed 
when the cooling test 
operation is complete.

This will be displayed 
when the heating test 
operation is complete.

This will be displayed after 5 seconds.

This will be displayed after 5 seconds.

First 2 digits Last 2 digits

Set to Function mode [F3].
(When [F4] to [F9] are displayed, continue to press 
the “SELECT” button until [F3] is displayed.)

For heating operation, press the “SELECT” 
button until “01” is displayed.

Function settings

EXIT

After the test operation is complete, turn off the power. Attach the cover of the electrical 
component box and the front panel of the outdoor unit.

NOTES:

• Check that the indoor and outdoor units connected to the same refrigerant system are 

operating normally.

• When indoor or outdoor units are not operating, or when the indoor and outdoor units 

of other refrigerant systems are operating, the indoor/outdoor unit address are not 
configured correctly.

• The system will not operate normally with an incorrect DIP switch setting.

Stop the system immediately and recheck the DIP switch setting.

9.4. Checklist

Check description

Check method

Criteria

1

High and low pressure values 
are normal.

Check it with a pres-
sure gauge.

Cooling: low pressure ap-
prox. 0.8 MPa
Heating: high pressure 
approx. 3.0 MPa

2

Drain water is discharged 
smoothly through the drain 
hose.

Check it by pouring 
water.

3

Indoor and outdoor unit fans 
are operating.

Check them visually.

4

Compressor operates after 
the indoor unit operates.

Check the operating 
sound.

5

Difference between inlet and 
outlet temperatures is normal.

Measure the inlet and 
outlet temperatures.

Temperature difference 
10 degrees

6

Error is not displayed.

Check the 7 segment 
display.

Error blinking or no error 
code display

9.1.3 Error displays

• When error occurs, “Err” and “Number of errors occurred” are alternately displayed on 

the 7 segment display every 1 second.

• For the content of error, please refer to the “10.2. Error codes”.
• When error codes are displayed, all the error codes can be confirmed by pressing the 

“SELECT” button.

Example:

When “Indoor unit capacity error [E221]” and “Indoor unit duplicate address error [E261]” 
occurred.

(*1)  When the address of the overlap indoor unit is 

displayed, press and hold the “ENTER” button 
for more than 3 seconds.

(*2)  When errors other than the address of the 

overlap indoor unit exist, press “SELECT” but-
ton to switch to the next error.

If error occurs, it will display “-”.

[Ad + address number]

9.2.  Pre-check for test run

Before the test operation, check the following items.
(1)  Is there a gas leakage? (At pipe connections {flange connections and brazed areas})
(2)  Is the system charged with the specified volume of refrigerant?
(3)  Is the refrigerant circuit address correct?
(4)  Is a breaker installed at the power supply cable of outdoor unit?
(5)  Are the cable connected to the terminals without looseness, and in accordance with 

the specifications?

(6)  Are the initial settings of the switches of the outdoor unit correctly configured?
(7)  Is the 3-way valve of the outdoor unit open? (Gas pipe and liquid pipe)
(8)  Is power supplied to the crank case heater for more than 12 hours? Electricity current 

in short period of time may result in compressor damage.

(9)  Are all the indoor units within the same coolant system connected to the power? Op-

erating indoor units which are not connected to the power may result in malfunctions.

(10)  Is Indoor unit connection check performed? Test run doesn't operate if Indoor unit 

connection check is not performed.

After checking that the above items are all in order, refer to 
“9.3. Test run method” to test operation the unit.
If there are problems, adjust immediately and recheck.

9.3.  Test run method

Be sure to configure test run settings only when the outdoor unit has stopped operating.

• Depending on the communication status between the indoor and outdoor units, it may 

take several minutes for the system to start operating after settings for the test run are 
complete.

• After the test run settings are complete, the outdoor unit and the connected indoor 

units will start operating. Room temperature control will not activate during test opera-
tion (continuous operation).

• If a knocking sound can be heard in the liquid compression of the compressor, stop 

the unit immediately and then energize the crank case heater for a sufficient length of 
time before restarting the operation.

Perform test operation for each refrigerant system.
You can set “cooling test operation" or “heating test operation” with the push button on the 
outdoor unit PC board.

9380545200-03_IM.indb   17

9380545200-03_IM.indb   17

4/6/2017   3:20:35 PM

4/6/2017   3:20:35 PM

Summary of Contents for AJH072LELAH

Page 1: ...English INSTALLATION MANUAL OUTDOOR UNIT For authorized service personnel only PART No 9380545200 03 AJY072LELAH AJY090LELAH AJY108LELAH AJH072LELAH AJH090LELAH AJH108LELAH Original instructions ...

Page 2: ...rminals electric shock or fire Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the...

Page 3: ...itioning with power breaker Other wise it may cause malfunction or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operatio...

Page 4: ...transmission cable and remote control cable at least 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not b...

Page 5: ...e 600 or more 1000 or more 2000 or more 500 or more 600 or more 1500 or more 3000 or more 3 4 Transporting the unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor uni...

Page 6: ...COPPER 2 JIS H3300 C1220T H or equivalent Please select the pipe size in accordance with local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration d...

Page 7: ...10 0 11 2 12 5 14 0 18 0 22 4 25 0 28 0 In the case of ARXD07GALH equivalent to model code of indoor unit Model code 07 Capacity 2 2kW 4 3 Protection of pipes Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing ...

Page 8: ...ening valves Operating the valves Use a hexagon wrench size 3 16 in 4 mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening dir...

Page 9: ...reaker in a location that is not exposed to high temperatures If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a mal...

Page 10: ...it Indoor unit Terminal resistor Fig 2 Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the sig...

Page 11: ... transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circuit Use one side of the twisted pair cable Connect both ends o...

Page 12: ...erminal This is the output signal for base heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static elect...

Page 13: ...ed set the rotary switch REF AD as shown in the table below Refrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant circuit address 0 99 Setting example 63 0 0 0 1 0 1 2 0 2 REF AD 10 REF AD 1 Rotary Switch REF AD 1 Factory setting 0 Rotary Switch REF AD 10 Factory setting 0 98 9 8 99 9 9 7 4 Push button setting Various functions can be set Se...

Page 14: ...nt display display ERROR lamp Blinking 2 Setting method Use the MODE EXIT SELECT and ENTER buttons to configure settings according to the proce dures below If no setting is made the factory default setting will be displayed Press the MODE EXIT button Press the SELECT button Press the ENTER button Press the ENTER button for more than 3 seconds 1 Function setting 7 segment LED display LED 105 LED 10...

Page 15: ...e as signed in the order when they are installed Refer to the indoor unit installation manual for the procedures to check the addresses 7 6 2 Procedures to enable automatic address setting on indoor units Check that the rotary switch IU AD on the indoor unit PC board is set to 00 If it is not set to 00 it means the address of that device is not set Factory default is 00 Turn on the power of the in...

Page 16: ...by monitoring with a vacuum gauge Evacuation procedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 75...

Page 17: ...ar electrical components in the service panel If the outdoor unit is installed at a level that is higher than the indoor unit the water that has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units 9 TEST RUN 9 1 Indoor unit connection check Normal oper...

Page 18: ... codes When error codes are displayed all the error codes can be confirmed by pressing the SELECT button Example When Indoor unit capacity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELEC...

Page 19: ...tdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchroniza tion E 9 7 1 Outdoor unit fan motor 1 lock error E 9 7 4 Outdoor unit fan motor 1 undervoltage error E 9 7 5 Outdoor unit fan motor...

Reviews: