6. ELECTRICAL 

WIRING

6.1.  The precautions of electrical wiring

 WARNING

Wiring connections must be performed by a qualified person in accordance with speci-
fications.
The rated supply of this product is 50 Hz, 400 V of 3-phase, 4-wire. Use a voltage within 
the range of 342 to 456 V.

Make sure to perform earthing (grounding) work. Improper earthing (grounding) work 
can cause electric shocks.

Before connecting the cables, make sure the power supply is OFF.

Be sure to install an earth (ground) leakage breaker. Otherwise, it will cause electric 
shock or fire.

Select a breaker (Included with earth leakage circuit breaker) of appropriate capacity 
and install one at every power supply of an outdoor unit. Wrong selection of breakers or 
transition wiring will lead to electric shock and fire.

Do not connect AC power supply to the transmission line terminal board.
Improper wiring can damage the entire system.

Install a breaker (Included with earth leakage circuit breaker) in accordance with the 
related laws and regulations.

Connect the connector cord securely to the terminal.
Faulty installation can cause a fire.

Make sure to secure the insulation portion of the connector cable with the cord clamp. A 
damaged insulation can cause a short circuit.

Never install a power factor improvement condenser. Instead of improving the power 
factor, the condenser may overheat.

Before servicing the unit, turn the power supply switch OFF. Then, do not touch electric 
parts for 10 minutes due to the risk of electric shock.

Always use a separate power supply line protected by a circuit breaker operating on all 
cables with a distance between contact of 3 mm for this unit.

Do not modify power cable, use extension cable or branch wiring. Improper use may 
cause electric shock or fire by poor connection, insufficient insulation or over current.

Use ring terminals and tighten the terminal screws to the specified torques, otherwise, 
abnormal overheating may be produced and possibly cause serious damage inside the 
unit.

Securely install the electrical box cover on the unit. An improperly installed service 
panel can cause serious accidents such as electric shock or fire through exposure to 
dust or water.

If the supply cable is damaged, it must be replaced by the manufacturer, its service 
agent or similarly qualified persons in order to avoid a hazard.

 CAUTION

The primary power supply capacity is for the air conditioner itself, and does not include 
the concurrent use of other devices.

Connect the power cables in positive phase sequence. If there is a missing phase con-
nection, the unit will not operate normally.

Do not use crossover power supply wiring for the outdoor unit.

If the electrical power is inadequate, contact your electric power company.

Install a breaker (Included with earth leakage circuit breaker) in a location that is not 
exposed to high temperatures.
If the temperature surrounding the breaker is too high, the amperage at which the 
breaker cuts out may decrease.

Use a breaker (Included with earth leakage circuit breaker) that is capable of handling 
high frequencies. Because the outdoor unit is inverter controlled, a high-frequency earth 
leakage circuit breaker is necessary to prevent a malfunction of the breaker itself.

When the electrical switchboard is installed outdoors, place it under lock and key so that 
it is not easily accessible.

Never bundle the power supply cable and transmission cable, remote control cable 
together. Separate these cable by 50 mm or more. Bundling these cables together will 
cause miss operation or breakdown.

Always keep to the maximum length of the transmission cable. Exceeding the maximum 
length may lead to erroneous operation.

The static electricity that is charged to the human body can damage the control PC 
board when handling the control PC board for address setting, etc.
Please keep caution to the following points.
Provide the grounding of Indoor unit, Outdoor unit and Option equipment.
Cut off the power supply (breaker).
Touch the metal section (such as the unpainted control box section) of the indoor or 
outdoor unit for more than 10 seconds. Discharge the static electricity in your body.
Never touch the component terminal or pattern on the PC board.

6.2. Knockout 

hole

 CAUTION

Be careful not to deform or scratch the panel while opening the knockout holes.

After opening the knockout holes, remove burr on the edges, and attach the one-touch 
bush (accessory), grommet or conduit etc. to prevent damaging the cables.
It is recommended to apply rust proof paint on the edges to prevent rust.

Knockout holes are provided in front and lateral sides for wiring.

Unit: mm

Ø50

Ø50

Ø34.5

Ø34.5

Ø22.2

Ø22.2

L

Length of the grommet edging

Mounting the grommet edging

Grommet edging 
(accessories)

Knockout hole

Knockout hole 

diameter (mm)

Dimension 

L

 

(mm)

Ø 50

147

Ø 34.5

100

Ø 22.2

60

6.3.  Selecting power supply cable and breaker

 CAUTION

Regulation of cable size and circuit breaker differs from each locality, please refer in 
accordance with local rules.

Refer to the table for the wiring and breaker specifications of each installation condition.

MODEL

Breaker (Time delay fuse or circuit capacity)

Fuse capacity (A)

Leakage current

AJ*072LELAH

20

100 mA 

0.1 sec or less

AJ*090LELAH

20

AJ*108LELAH

25

MODEL

Outdoor unit power supply cable

Recommended cable size (mm²)

Limited wiring 

length (m)

Power cable

Earth cable

AJ*072LELAH

6

6

62

AJ*090LELAH

6

6

62

AJ*108LELAH

6

6

62

• These values are recommended data.
• Specification: Use conformed cord with Type 60245 IEC66
• Max. cable length: Set a length so that the voltage drop is less than 2%. Increase the 

cable diameter when the cable length is long.

In case of connected outdoor unit

Transmission cable

Breaker

400 V 3ø 50 Hz

Breaker

230 V 1ø 50 Hz

Outdoor unit
Power supply cable

Indoor unit
Power supply 
cable

9380545200-03_IM.indb   8

9380545200-03_IM.indb   8

4/6/2017   3:20:34 PM

4/6/2017   3:20:34 PM

Summary of Contents for AJH072LELAH

Page 1: ...English INSTALLATION MANUAL OUTDOOR UNIT For authorized service personnel only PART No 9380545200 03 AJY072LELAH AJY090LELAH AJY108LELAH AJH072LELAH AJH090LELAH AJH108LELAH Original instructions ...

Page 2: ...rminals electric shock or fire Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the...

Page 3: ...itioning with power breaker Other wise it may cause malfunction or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operatio...

Page 4: ...transmission cable and remote control cable at least 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not b...

Page 5: ...e 600 or more 1000 or more 2000 or more 500 or more 600 or more 1500 or more 3000 or more 3 4 Transporting the unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor uni...

Page 6: ...COPPER 2 JIS H3300 C1220T H or equivalent Please select the pipe size in accordance with local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration d...

Page 7: ...10 0 11 2 12 5 14 0 18 0 22 4 25 0 28 0 In the case of ARXD07GALH equivalent to model code of indoor unit Model code 07 Capacity 2 2kW 4 3 Protection of pipes Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing ...

Page 8: ...ening valves Operating the valves Use a hexagon wrench size 3 16 in 4 mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening dir...

Page 9: ...reaker in a location that is not exposed to high temperatures If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a mal...

Page 10: ...it Indoor unit Terminal resistor Fig 2 Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the sig...

Page 11: ... transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circuit Use one side of the twisted pair cable Connect both ends o...

Page 12: ...erminal This is the output signal for base heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static elect...

Page 13: ...ed set the rotary switch REF AD as shown in the table below Refrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant circuit address 0 99 Setting example 63 0 0 0 1 0 1 2 0 2 REF AD 10 REF AD 1 Rotary Switch REF AD 1 Factory setting 0 Rotary Switch REF AD 10 Factory setting 0 98 9 8 99 9 9 7 4 Push button setting Various functions can be set Se...

Page 14: ...nt display display ERROR lamp Blinking 2 Setting method Use the MODE EXIT SELECT and ENTER buttons to configure settings according to the proce dures below If no setting is made the factory default setting will be displayed Press the MODE EXIT button Press the SELECT button Press the ENTER button Press the ENTER button for more than 3 seconds 1 Function setting 7 segment LED display LED 105 LED 10...

Page 15: ...e as signed in the order when they are installed Refer to the indoor unit installation manual for the procedures to check the addresses 7 6 2 Procedures to enable automatic address setting on indoor units Check that the rotary switch IU AD on the indoor unit PC board is set to 00 If it is not set to 00 it means the address of that device is not set Factory default is 00 Turn on the power of the in...

Page 16: ...by monitoring with a vacuum gauge Evacuation procedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 75...

Page 17: ...ar electrical components in the service panel If the outdoor unit is installed at a level that is higher than the indoor unit the water that has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units 9 TEST RUN 9 1 Indoor unit connection check Normal oper...

Page 18: ... codes When error codes are displayed all the error codes can be confirmed by pressing the SELECT button Example When Indoor unit capacity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELEC...

Page 19: ...tdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchroniza tion E 9 7 1 Outdoor unit fan motor 1 lock error E 9 7 4 Outdoor unit fan motor 1 undervoltage error E 9 7 5 Outdoor unit fan motor...

Reviews: