background image

En-7

6.1 Electrical requirement

Voltage rating

208 / 230 V

Operating range   

187 to 253 V

•  Select the power cable type and size in accordance with relevant local and national 

regulations.

• Speci

fi

 cations for local wiring power cord and branch wiring are in compliance with local 

code.

•  Select the correct cable type and size according to the country or region’s regulations.
•  Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is long.

Breaker should be installed at every refrigerant system. Do not use a breaker in a different 
refrigerant system.
Refer to the table for the breaker speci

fi

 cations of each installation condition. Perform the 

power crossover wiring within the range of the same refrigerant system. When the crossover 
wiring is done, make a connection for indoor units to satisfy conditions A and B below.

A. Current breaker requirements

Model

MCA

MAX. CKT. BKR 

(Fuse capacity)

ARUV12TLAV

1.75 A

15 A

ARUV18TLAV

2.14 A

ARUV24TLAV

2.81 A

ARUV30TLAV

3.38 A

ARUV36TLAV

4.45 A

ARUV48TLAV

5.24 A

ARUV60TLAV

6.98 A

MCA: Minimum Circuit Ampacity
MAX. CKT. BKR : Maximum Circuit Breaker
Breaker should be installed at every refrigerant system. Do not use a breaker in a different 
refrigerant system.

With this model, connect only one indoor unit to a current breaker. (Crossover wiring is 
prohibited.)
Select a minimum of 7 or more multiples of rated current under the condition time in seconds 
10ms (0.01 S) or less at the current breaker trip curves (time in seconds/multiples of rated 
current).

B. Ground Fault Equipment Breaker requirements

Breaker capacity

* Maximum connectable indoor units

(ARUV12/18/24/30/36/48/60TLAV model only)

30 mA, 0.1 sec or less

9 or less

100 mA, 0.1 sec or less

10 to 30 **

* Number of connected Heat pump type
**  If the 100 mA capacity breaker is not provided, split the quantity of the indoor units into 

small groups of 9 units or less and provide a breaker with capacity of 30 mA for each 
group.

When connecting different models on the above listed breaker in conjunction with the 
ARUV12/18/24/30/36/48/60TLAV, you might be able to connect more than 9 units. To 
determine the maximum amount of indoor units when using different models or Heat 
recovery type, reference each units Design and Technical Manual to calculate the total 
amount of units that can be connected on a given breaker. 

6.1.1.  Transmission and remote controller wiring speci

fi

 cations

Follow the speci

fi

 cations below for the transmission and remote controller cable.

Cable size

Wire type

Remarks

Transmission 
cable

22 AWG
(0.33 mm²)

LEVEL 4 (NEMA) 
non-polar 2core, 
twisted pair solid core 
diameter 0.026 in 
(0.65mm)

LONWORKS ® 
compatible cable

Remote 
controller cable 
(2-wire type)

22 AWG to 16 AWG
(0.33 to 1.25 mm²)

Sheathed PVC cable

Non polar 2 core, twisted 
pair

18 AWG

Thermostat cable 2 
core

Use sheathed non twisted 
pair cable

Remote 
controller cable 
(3-wire type)

22 AWG 
(0.33 mm²)

Sheathed PVC cable

Polar 3 core

6.2 Wiring method

Example

Outdoor unit or RB unit *1

Transmission

Transmission

Power supply

Breaker2

Breaker2

Breaker2

Breaker1

Breaker1

Breaker1

Power supply

Remote controller

(Master)

Remote controller

(Slave)

Remote controller

Indoor unit

Remote 

control

*2

*2

*2

Indoor unit

Indoor unit

Breaker 1:  Ground Fault Equipment

Breaker (GFEB)

Breaker 2:  Maximum Circuit Breaker

(MAX. CKT. BKR)

Breaker shall be located in sight from and readily accessible from all indoor units.
*1:  When connecting to the Heat Recovery System, refer to the installation manual of the RB 

unit.

*2: When connecting the 2-wire type remote controller, Y3 is not used.

6.3 Unit wiring

Before attaching the cable to terminal block.

6.3.1.  Power supply cable

Adjust the length of power supply cable to avoid excessive tension with referring 

fi

 gure and 

table below.

Conduit connector

Earth (Ground) wire

(2)

(1)

Model

(1): [in (mm)]

(2): [in (mm)]

ARUV12/18/24TLAV

5-1/2 (140)

6-11/16 (170)

ARUV30/36TLAV

7-7/8 (200)

9-1/16 (230)

ARUV48/60TLAV

9-7/16 (240)

10-5/8 (270)

A. For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping it 

around the end of the cable.

(2)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws. 
 

Do not use a screwdriver that is too small, otherwise, the screw heads may be damaged 
and prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(5)  See the table for the terminal screw tightening torques.
(6)  Please do not 

fi

 x 2 power supply cables with 1 screw.

Strip 1 in
(25 mm)

Loop

Screw with 
special washer 

Screw with 
special washer

Cable end 
(Loop)

Cable

Cable

Terminal block

Cable end (Loop)

Summary of Contents for Airstage VR-II ARUV12TLAV

Page 1: ...9373870180 04 ARUV12TLAV ARUV18TLAV ARUV24TLAV ARUV30TLAV ARUV36TLAV ARUV48TLAV ARUV60TLAV TM Français Español MANUEL D INSTALLATION MANUAL DE INSTALACIÓN UNITÉ INTÉRIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado ...

Page 2: ... can cause dripping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting snow When Connecting Refrigerant Tubing Keep all tubing runs as short as possible Use the brazing met...

Page 3: ... approximately 1 6 times higher than the R22 failure to use dedicated piping material or improper installation can cause rupture or injury Furthermore it can cause serious accidents such as water leakage electric shock or fire Tool name Changes Gauge manifold Pressure is huge and cannot be measured with a conventional R22 gauge To prevent erroneous mixing of other refrigerants the diameter of each...

Page 4: ...follows 1 Install the indoor unit on a place having a sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 A place from where the air can be distributed evenly throughout the room by the unit 5 Install the unit...

Page 5: ...e application All externally insulated duct work must have an adequate vapor seal for summer operation This is particularly important where the duct is exposed to highly humid conditions in such places as attics vented crawl spaces unconditioned basements and utility rooms The vapor seal prevents condensation of moisture in the insulating material and subsequent loss of its insulating value 4 PIPE...

Page 6: ...d both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 9 16 i...

Page 7: ...made in the walls for wiring Otherwise a short circuit could result Use the included connection cables and power cables or ones specified by the manufacturer Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulatio...

Page 8: ...d Technical Manual to calculate the total amount of units that can be connected on a given breaker 6 1 1 Transmission and remote controller wiring specifications Follow the specifications below for the transmission and remote controller cable Cable size Wire type Remarks Transmission cable 22 AWG 0 33 mm LEVEL 4 NEMA non polar 2core twisted pair solid core diameter 0 026 in 0 65mm LONWORKS compati...

Page 9: ... supply L1 L2 N GND 11 to 16 lbf in 1 2 to 1 8 N m 6 3 2 Transmission and Remote controller cable Transmission cable 1 in 25 mm 1 3 8 in 35mm Shielded cable no film Remote controller cable 1 in 25 mm For 3 wire type 1 in 25 mm For 2 wire type When the 2 cables are attached Different diameter Connect to 1 side GOOD PROHIBITED WARNING Tighten the terminal screws to the specified torques otherwise ab...

Page 10: ...nal parts bind each connection cable with the transmission and remote controller cables 6 6 External input and external output optional parts 6 7 Remote sensor optional parts 6 8 IR receiver unit optional parts Fix the conduit with the supporters as shown below Conduit Power supply cable Supporter Indoor unit 30 in 756 mm or less 54 in 1 361 mm or less 54 in 1 361 mm or less 54 in 1 361 mm or less...

Page 11: ...ed load Do not impress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor unit...

Page 12: ... Thermostat off ON OFF Normal 6 6 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 82 ft 25 m Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 50mA Output select When indicator etc are connected directly Indicator 1 Indicator 2 Indic...

Page 13: ...umber to 02 Refer to 7 3 Function setting for details about Function Number and Setting Number 6 8 IR receiver unit optional parts For the installation method please refer to the installation manual of IR receiver unit Connection terminals IR receiver unit terminal CN18 Controller PCB Wiring arrangement Controller PCB Cable tie Medium Accessories Bind with the transmission and remote controller ca...

Page 14: ... 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 6 0 6 6 0 6 7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 1 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set...

Page 15: ... and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error re port target 47 00 All Change the target for reporting errors Errors can either be reported in all locations or only on the central remote controller 01 Display only on central remote controller Fan set ting when cooling thermostat off 49 00 Follow the setting on the remote controller When set to 01 the f...

Page 16: ...lamp Green Status contents Lit Lit when the power is turned on Flashing There is a fault with the communication board or the main board 0 1s ON 0 1s OFF Power indicator lamp green Controller PCB 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output erro...

Page 17: ...the Status Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller UTY RNKU 3 wire type UTY RNRU 2 wire type For details on marking the ERROR CODES please refer to the Manual of IR Receiver Unit or Wired Remote Controller ...

Reviews: