background image

En-2

 

WARNING

Request your dealer or a professional installer to install the indoor unit in accordance with 
this Installation Manual. 
An improperly installed unit can cause serious accidents such as water leakage, electric 
shock, or 

fi

 re. 

If the indoor unit is installed in disregard of the instructions in the Installation Manual, it will 
void the manufacturer’s warranty.

Do not turn ON the power until all work has been completed. 
Turning ON the power before the work is completed can cause serious accidents such as 
electric shock or 

fi

 re.

If refrigerant leaks while work is being carried out, ventilate the area. 
If the refrigerant comes in contact with a 

fl

 ame, it produces a toxic gas.

Installation must be performed in accordance with the requirement of NEC (National Elec-
trical Code) and CEC (Canadian Electrical Code) by authorized personnel only.

Except for EMERGENCY, never turn off main as well as sub breaker of the indoor units 
during operation. It will cause compressor failure as well as water leakage.
First, stop the indoor unit by operating the control unit, converter or external input device 
and then cut the breaker. Make sure to operate through the control unit, converter or 
external input device. 
When the breaker is designed, locate it at a place where the users cannot start and stop in 
the daily work.

2.  ABOUT THIS PRODUCT

2.1  Precautions for using the R410A refrigerant

 WARNING

Do not introduce any substance other than the prescribed refrigerant into the refrigeration 
cycle. 
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become 
abnormally high and cause the piping to rupture.

If there is a refrigerant leakage, make sure that it does not exceed the concentration limit. 
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such as 
oxygen starvation.

Do not touch refrigerant that has leaked from the refrigerant pipe connections or other 
area. Touching the refrigerant directly can cause frostbite.

If a refrigerant leakage occurs during operation, immediately vacate the premises and 
thoroughly ventilate the area.
If the refrigerant comes in contact with a 

fl

 ame, it produces a toxic gas.

2.2  Special tool for R410A

 WARNING

To install a unit that uses the R410A refrigerant, use dedicated tools and piping materials 
that have been manufactured speci

fi

 cally for R410A use. 

Because the pressure of the R410A refrigerant is approximately 1.6 times higher than the 
R22, failure to use dedicated piping material or improper installation can cause rupture or 
injury. 
Furthermore, it can cause serious accidents such as water leakage, electric shock, or 

fi

 re.

Tool name

Changes

Gauge manifold

Pressure is huge and cannot be measured with a conventional 
(R22) gauge. To prevent erroneous mixing of other refrigerants, 
the diameter of each port has been changed.
It is recommended to use a gauge manifold with a high pressure 
display range 30 inHg to 768 psi (–0.1 to 5.3 MPa) and a low 
pressure display range 30 inHg to 551 psi (–0.1 to 3.8 MPa).

Charging hose

To increase pressure resistance, the hose material and base size 
were changed.

Vacuum pump

A conventional (R22) vacuum pump can be used by installing a 
vacuum pump adapter. 
Be sure that the pump oil does not back 

fl

 ow into the system. 

Use one capable for vacuum suction of 5 Torr, –755 mmHg 
(–100.7 kPa).

Gas leakage detector

Special gas leakage detector for R410A refrigerant.

2.3 Accessories

 

WARNING

For installation purposes, be sure to use the parts supplied by the manufacturer or other 
prescribed parts. 
The use of non-prescribed parts can cause serious accidents such as the unit to fall, water 
leakage, electric shock, or 

fi

 re.

The following installation parts are furnished. Use them as required.

Keep the Installation Manual in a safe place and do not discard any other accessories until 
the installation work has been completed.

Do not discard any accessories needed for installation until the installation work has been 
completed.

Name and shape

Q’ty

Application

Operating manual

1

Installation manual

1

(This book)

Cable tie (Medium)

1

For transmission and remote controller cable 
binding

Gas pipe heat insulation

1

For gas pipe at the unit inside

Plastic screws

2

For the filter panel fixing

2.4 Optional parts

Description

Model

Application

IR receiver unit

UTB-*WC

For the wireless remote controller.

Remote sensor 

UTY-XSZX

Room temperature sensor

External connect kit

UTY-XWZXZC

For output function
(Output terminal / CNB01)

UTY-XWZXZB

For control input function
(Apply voltage terminal / CNA01)

UTY-XWZXZD

For control input function
(Dry contact terminal / CNA02)

UTY-XWZXZ7

For forced thermostat off function
(Apply voltage terminal / CNA03)

UTY-XWZXZE

For forced thermostat off function
(Dry contact terminal / CNA04)

2.5  About unit of the length

This product is different from other Fujitsu General products and it is designed with United 
States customary unit. Metric units are provided for reference. When the exact dimensions and 
tolerances are required, refer to the United States customary units.

Summary of Contents for Airstage VR-II ARUV12TLAV

Page 1: ...9373870180 04 ARUV12TLAV ARUV18TLAV ARUV24TLAV ARUV30TLAV ARUV36TLAV ARUV48TLAV ARUV60TLAV TM Français Español MANUEL D INSTALLATION MANUAL DE INSTALACIÓN UNITÉ INTÉRIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado ...

Page 2: ... can cause dripping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting snow When Connecting Refrigerant Tubing Keep all tubing runs as short as possible Use the brazing met...

Page 3: ... approximately 1 6 times higher than the R22 failure to use dedicated piping material or improper installation can cause rupture or injury Furthermore it can cause serious accidents such as water leakage electric shock or fire Tool name Changes Gauge manifold Pressure is huge and cannot be measured with a conventional R22 gauge To prevent erroneous mixing of other refrigerants the diameter of each...

Page 4: ...follows 1 Install the indoor unit on a place having a sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 A place from where the air can be distributed evenly throughout the room by the unit 5 Install the unit...

Page 5: ...e application All externally insulated duct work must have an adequate vapor seal for summer operation This is particularly important where the duct is exposed to highly humid conditions in such places as attics vented crawl spaces unconditioned basements and utility rooms The vapor seal prevents condensation of moisture in the insulating material and subsequent loss of its insulating value 4 PIPE...

Page 6: ...d both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 9 16 i...

Page 7: ...made in the walls for wiring Otherwise a short circuit could result Use the included connection cables and power cables or ones specified by the manufacturer Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulatio...

Page 8: ...d Technical Manual to calculate the total amount of units that can be connected on a given breaker 6 1 1 Transmission and remote controller wiring specifications Follow the specifications below for the transmission and remote controller cable Cable size Wire type Remarks Transmission cable 22 AWG 0 33 mm LEVEL 4 NEMA non polar 2core twisted pair solid core diameter 0 026 in 0 65mm LONWORKS compati...

Page 9: ... supply L1 L2 N GND 11 to 16 lbf in 1 2 to 1 8 N m 6 3 2 Transmission and Remote controller cable Transmission cable 1 in 25 mm 1 3 8 in 35mm Shielded cable no film Remote controller cable 1 in 25 mm For 3 wire type 1 in 25 mm For 2 wire type When the 2 cables are attached Different diameter Connect to 1 side GOOD PROHIBITED WARNING Tighten the terminal screws to the specified torques otherwise ab...

Page 10: ...nal parts bind each connection cable with the transmission and remote controller cables 6 6 External input and external output optional parts 6 7 Remote sensor optional parts 6 8 IR receiver unit optional parts Fix the conduit with the supporters as shown below Conduit Power supply cable Supporter Indoor unit 30 in 756 mm or less 54 in 1 361 mm or less 54 in 1 361 mm or less 54 in 1 361 mm or less...

Page 11: ...ed load Do not impress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor unit...

Page 12: ... Thermostat off ON OFF Normal 6 6 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 82 ft 25 m Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 50mA Output select When indicator etc are connected directly Indicator 1 Indicator 2 Indic...

Page 13: ...umber to 02 Refer to 7 3 Function setting for details about Function Number and Setting Number 6 8 IR receiver unit optional parts For the installation method please refer to the installation manual of IR receiver unit Connection terminals IR receiver unit terminal CN18 Controller PCB Wiring arrangement Controller PCB Cable tie Medium Accessories Bind with the transmission and remote controller ca...

Page 14: ... 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 6 0 6 6 0 6 7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 1 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set...

Page 15: ... and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error re port target 47 00 All Change the target for reporting errors Errors can either be reported in all locations or only on the central remote controller 01 Display only on central remote controller Fan set ting when cooling thermostat off 49 00 Follow the setting on the remote controller When set to 01 the f...

Page 16: ...lamp Green Status contents Lit Lit when the power is turned on Flashing There is a fault with the communication board or the main board 0 1s ON 0 1s OFF Power indicator lamp green Controller PCB 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output erro...

Page 17: ...the Status Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller UTY RNKU 3 wire type UTY RNRU 2 wire type For details on marking the ERROR CODES please refer to the Manual of IR Receiver Unit or Wired Remote Controller ...

Reviews: