En-9
6.5. Optional parts wiring
6.5.1 Connector and DIP switch position
Output terminal (CNB01)
SW4
SW3
SW2
SW1
DIP switch
(SET 2)
Apply voltage terminal
Dry contact
terminal
(CNA01)
(CNA04)
(CNA02)
(CNA03)
ON OFF
Controller PCB
Name
Application
CNA01
Apply voltage terminal
For external input
CNA03
CNA02
Dry contact terminal
CNA04
DIP switch SET 2 (SW2)
Input signal type switching
CNB01
Output terminal
For external output
6.5.2 Connection methods
Wire modification
(1) Remove insulation from wire at-
tached to wire kit connector.
(2) Remove insulation from field
supplied cable. Use crimp type
insulated butt connector to join field
cable and wire kit wire.
(3) Connect the wire with connecting
wire with solder.
IMPORTANT:
Be sure to insulate the connection between the
wires.
Locally purchased
Solder and insulate the connected parts.
Wire kit connector
(optional parts)
Connection terminals and wiring arrangement
In following figure, all the possible connectors are connected for description.
In actual installation, you cannot connect all the connectors at once.
CNA01
CNA04
CNA02
CNA03
CNB01
Controller PCB
Cable tie
(Locally purchased)
Connecting cables
6.6. External input and external output (Optional parts)
6.6.1 External input
• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
PCB CNA01 or CNA02.
• “Operation/Stop” mode, “Emergency stop” mode or “Forced stop” mode can be selected
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 492 ft (150
m).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
6.4. Wiring
Connect the end of the connection cable fully into the terminal block.
Screw
Conduit holder
Lock nut
Conduit connector
Wired remote controller
cable and optional parts
cables (if necessary)
Transmission cables
(The grommet edging is not used.)
Wired remote controller
cable connection terminal
Wired remote
controller cable
L1, L2(N):
Power supply
cable
Power supply
earth (ground)
cable
X1, X2:
Transmission
cable
Cable tie (Accessories)
Earth (ground)
terminal for wired
remote controller
(if necessary)
• Fix the conduit with the supporters as shown below.
Conduit (Power supply cable)
Indoor unit
Supporter
30 in
(756 mm)
or less
54 in
(1,361 mm)
or less
54 in
(1,361 mm)
or less
54 in
(1,361 mm)
or less