FUNCTION SETTINGS
12.
INDOOR UNIT (Setting by remote controller)
12-1.
This procedure changes to the function settings used to control the indoor unit according to the
•
installation conditions. Incor settings can cause the indoor unit to malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the installation
•
conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value.
•
Settings will not be changed if invalid numbers or setting values are selected.
•
PREPARATION
Turn on the power.
•
* By turning on the power indoor units, so make sure the piping air-tight test and vacuuming have
been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the power.
FUNCTION SETTING METHOD (for Wireless remote controller)
Entering the Function Setting Mode
While pressing the FAN button and SET TEMP. (
•
) simultaneously, press the RESET button to enter the function
setting mode.
STEP 1
Setting the Remote controller Signal Code
Use the following steps to select the signal code of the remote controller. (Note
that the air conditioner cannot receive a signal code if the air conditioner has not
been set for the signal code.) The signal codes that are set through this process are
applicable only to the signals in the FUNCTION SETTING. For details on how to set
the signal codes through the normal process, refer to SELECTING THE REMOTE
CONTROLLER SIGNAL CODE.
Press the SET TEMP. (
1.
) ( ) button to change the signal code between
→
→ →
Match the code on the display to the air conditioner signal code. (initially
set to )
(If the signal code does not need to be selected, press the MODE button and
proceed to STEP 2.)
Press the TIMER MODE button and check that the indoor unit can receive signals
2.
at the displayed signal code.
Press the MODE button to accept the signal code, and proceed to STEP 2.
3.
The air conditioner signal code is set to A prior to shipment.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use a
signal code other than signal code A, reset the signal code after replacing the batteries.
If you do not know the air conditioner signal code setting, try each of the signal codes (
→ → →
) until you
find the code which operates the air conditioner.
STEP 2
Selecting the Function Number and Setting Value
Press the SET TEMP. (
1.
) ( ) buttons to select the function
number.
(Press the MODE button to switch between the left and right
digits.)
Press the FAN button to proceed to setting the value.
2.
Press the FAN button again to return to the function number
selection.)
Press the SET TEMP. (
3.
) ( ) buttons to select the setting
value.
(Press the MODE button to switch between the left and right
digits.)
Press the TIMER MODE button, and START/STOP button,
4.
in the order listed to confirm the settings.
Press the RESET button to cancel the function setting
5.
mode.
After completing the FUNCTION SETTING, be sure to turn
6.
off the power and turn it on again.
Function number
Setting value
CAUTION
After turning off the power, wait 10 seconds or more before turning on it again.
The Function Setting will not become active unless the power is turned off then on again.
Summary of Contents for AG G09LVCB series
Page 2: ...1 INDOOR UNIT FLOOR TYPE AG G09LVCB AG G12LVCB AG G14LVCB DTR_AG004E_03 2013 01 21 ...
Page 33: ...2 OUTDOOR UNIT SINGLE TYPE AO G09LVCN AO G12LVCN AO G14LVCN DTR_AO094E_02 2013 01 21 ...
Page 40: ... 02 06 OUTDOOR UNIT AO G09 14LVCN OUTDOOR UNIT AO G09 14LVCN MODEL AO G14LVCN ...
Page 47: ... 02 13 OUTDOOR UNIT AO G09 14LVCN OUTDOOR UNIT AO G09 14LVCN SOUND LEVEL CHECK POINT 88888 ...