13) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to “External heater output” in Chapter 8-4.
Function
number
Setting
value
Setting description
Factory
setting
Setting value of function 61:
00
01 to 09
Heater: On
Heater: Off
Heater: On
Heater: Off
62
00
-5.4 °F (-3 °C)
-1.8 °F (-1 °C)
-0.9 °F (-0.5 °C)
0.9 °F (0.5 °C)
♦
01
-3.6 °F (-2 °C)
-1.8 °F (-1 °C)
-1.8 °F (-1 °C)
0.9 °F (0.5 °C)
02
-3.6 °F (-2 °C)
-1.8 °F (-1 °C)
-3.6 °F (-2 °C)
0.9 °F (0.5 °C)
03
-5.4 °F (-3 °C)
-1.8 °F (-1 °C)
-5.4 °F (-3 °C)
0.9 °F (0.5 °C)
04
-7.2 °F (-4 °C)
-1.8 °F (-1 °C)
-7.2 °F (-4 °C)
0.9 °F (0.5 °C)
05
-9.0 °F (-5 °C)
-1.8 °F (-1 °C)
-9.0 °F (-5 °C)
0.9 °F (0.5 °C)
06
-5.4 °F (-3 °C)
-0.9 °F (-0.5 °C)
-0.9 °F (-0.5 °C)
0 °F (0 °C)
07
-3.6 °F (-2 °C)
-0.9 °F (-0.5 °C)
-1.8 °F (-1 °C)
0 °F (0 °C)
08
-3.6 °F (-2 °C)
-0.9 °F (-0.5 °C)
-3.6 °F (-2 °C)
0 °F (0 °C)
09
-5.4 °F (-3 °C)
-0.9 °F (-0.5 °C)
-5.4 °F (-3 °C)
0 °F (0 °C)
10
-7.2 °F (-4 °C)
-0.9 °F (-0.5 °C)
-7.2 °F (-4 °C)
0 °F (0 °C)
11
-9.0 °F (-5 °C)
-0.9 °F (-0.5 °C)
-9.0 °F (-5 °C)
0 °F (0 °C)
12
-5.4 °F (-3 °C)
0 °F (0 °C)
-0.9 °F (-0.5 °C)
-0.9 °F (-0.5 °C)
13
-3.6 °F (-2 °C)
0 °F (0 °C)
-1.8 °F (-1 °C)
-0.9 °F (-0.5 °C)
14
-3.6 °F (-2 °C)
0 °F (0 °C)
-3.6 °F (-2 °C)
-0.9 °F (-0.5 °C)
15
-5.4 °F (-3 °C)
0 °F (0 °C)
-5.4 °F (-3 °C)
-0.9 °F (-0.5 °C)
16
-7.2 °F (-4 °C)
0 °F (0 °C)
-7.2 °F (-4 °C)
-0.9 °F (-0.5 °C)
17
-9.0 °F (-5 °C)
0 °F (0 °C)
-9.0 °F (-5 °C)
-0.9 °F (-0.5 °C)
14) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to “External heater output” in Chapter 8-4.
Function number
Setting value
Setting description
Factory setting
66
00
-4.0 °F (-20 °C)
♦
01
-0.4 °F (-18 °C)
02
3.2 °F (-16 °C)
03
6.8 °F (-14 °C)
04
10.4 °F (-12 °C)
05
14.0°F (-10 °C)
06
17.6 °F (-8 °C)
08
24.8 °F (-4 °C)
- 71 -
9-2. Function settings by using remote controller
9. Function settings
DUCT TYPE
ADUH09-18LUAS1
DUCT TYPE
ADUH09-18LUAS1