2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function number
Setting value
Setting description
Factory setting
26
00
0 in.WG (0 Pa)
01
0.04 in.WG (10 Pa)
02
0.08 in.WG (20 Pa)
03
0.12 in.WG (30 Pa)
04
0.16 in.WG (40 Pa)
05
0.20 in.WG (50 Pa)
06
0.24 in.WG (60 Pa)
07
0.28 in.WG (70 Pa)
08
0.32 in.WG (80 Pa)
09
0.36 in.WG (90 Pa)
31
Standard (0.10 in.WG [25 Pa])
♦
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of the room temp. sensor - Correction temp. value
Example of correction:
When the temperature of the room temp. sensor is 78°F and the setting value is “03” (-2°F),
the corrected temp. will be 80°F (78°F - [-2°F]).
The temperature correction values show the difference from the Standard setting “00” (manufactur-
er’s recommended value).
Function number
Setting value
Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00
Standard setting
♦
01
No correction 0.0 °F (0.0 °C)
02
-1 °F (-0.5 °C)
More cooling
Less heating
03
-2 °F (-1.0 °C)
04
-3 °F (-1.5 °C)
05
-4 °F (-2.0 °C)
06
-5 °F (-2.5 °C)
07
-6 °F (-3.0 °C)
08
-7 °F (-3.5 °C)
09
-8 °F (-4.0 °C)
10
+1 °F (+0.5 °C)
Less cooling
More heating
11
+2 °F (+1.0 °C)
12
+3 °F (+1.5 °C)
13
+4 °F (+2.0 °C)
14
+5 °F (+2.5 °C)
15
+6 °F (+3.0 °C)
16
+7 °F (+3.5 °C)
17
+8 °F (+4.0 °C)
- 67 -
9-2. Function settings by using remote controller
9. Function settings