Installation configuration of individual connection
External heating device is installed individually. (No use of indoor unit fan)
Example of heating device:
- Floor heating device
On/Off
WARNING
•
DIP Switch 101-3 must be in the ON position when ducted electric heat application is be-
ing used.
DIP switch 101-3 is set in the ON position by default from the factory. When DIP
switch 101-3 is in the ON position and ducted electric heat application is not being used, cold
draft occurs due to fan delay off operation.
Operation
Condition
Heater off
DIP-SW101-3
On
• Heater is off as shown in following diagram of heating
temperature.
• Other than heating mode
• Error occurred
• Forced thermostat off
• Fan stop protection
Indoor unit fan
setting for
external heater
Enabled
DIP-SW101-3
Off
• Heater is off as shown in following diagram of heating
temperature.
• Other than heating mode
• Error occurred
• Forced thermostat off
Indoor unit fan
setting for
external heater
Disabled
SW101
CN47
CN65
• Design and install external heater appropriately with considering its protection.
External
heater
Indoor
unit
Supply air
Return air
• Inappropriate designing and installation of external heater may cause a fire by emitted heat from
the external heater.
• Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heat-
ing device.
- 46 -
8-4. Details of function
8. External input and output
DUCT TYPE
ADUH09-18LUAS1
DUCT TYPE
ADUH09-18LUAS1