Trouble shooting 11
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 1 : Check rotation of Fan
Check Point 2 : Check ambient temp. around motor
OK
OK
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 12
Indoor Fan Motor abnormal
Indoor Unit Controller PCB Circuit
Indoor Fan Motor
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Control PCB failure
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
When the condition that actual frequency of Indoor Fan is
below 1/3 of target frequency is continued more than 56 seconds.
02-14
Check Point 3 : Replace Controller PCB
If Check Point 1- 2 do not improve the symptom, replace Controller PCB.