1-1. COOLING OPERATION
1-1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
The maximum frequency is limited in the range shown in Figure 1 based on the fan speed mode
and the outdoor temperature.
* If the room temperature is 2 degC higher than a set temperature,
the compressor operation frequency will attain to maximum frequency.
* If the room temperature is 2.5 degC lower than a set temperature, the compressor will be stopped.
* When the room temperature is b2 degC to -2.5 degC of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
minimum
frequency
maximum
frequency
AB*F18, 24
AR*F18, 24
AU*F18, 24
18Hz
113Hz
18Hz
113Hz
AR*A24LATU
AU*A24LBL
Outdoor air
temperature
A zone
B zone
C zone
D zone
E zone
F zone
Hi
Me
Lo
Quiet
A zone
113Hz
113Hz
85Hz
54Hz
75Hz
75Hz
54Hz
54Hz
54Hz
45Hz
45Hz
38Hz
34Hz
34Hz
34Hz
27Hz
113Hz
113Hz
80Hz
54Hz
66Hz
66Hz
54Hz
54Hz
54Hz
45Hz
45Hz
38Hz
34Hz
34Hz
34Hz
24Hz
B zone
C zone
AB*F18, 24
AR*F18, 24
AU*F18, 24
D-F zone
A zone
B zone
C zone
AR*A24LATU
AU*A24LBL
D-F zone
( Table 1 : Compressor Frequency Range )
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
01-01
Fan speed mode
When the room
temperature rises
When the room
temperature drops
36°C
32°C
21°C
12°C
2°C
34°C
30°C
19°C
10°C
0°C