8. CIRCUIT BOARD SETTING
Set the switch on the circuit board.
(1) Indoor unit addresses
Rotary switch (SW5) - - - Factory setting “0”
When connecting multiple indoor units to one refrigerant system, set the address at SW5 in sequence from 0.
(2) Refrigerant circuit address
Rotary switch (SW7) - - - Factory setting “0”
Rotary switch (SW8) - - - Factory setting “0”
In the case of multiple refrigerant systems, set SW7 and SW8 as shown in the Table 7 for each refrigerant system. Set to the same
refrigerant circuit address as the outdoor unit.
Example:
When SW8 is set to “1” and SW7 is set to “14”, the refrigerant circuit address will be “30”.
Table 7
Refrigerant
Rotary
Refrigerant
Rotary
Refrigerant
Rotary
Refrigerant
Rotary
Refrigerant
Rotary
circuit
Switch Setting
circuit
Switch Setting
circuit
Switch Setting
circuit
Switch Setting
circuit
Switch Setting
address
INDOOR UNIT
address
INDOOR UNIT
address
INDOOR UNIT
address
INDOOR UNIT
address
INDOOR UNIT
SW8
SW7
SW8
SW7
SW8
SW7
SW8
SW7
SW8
SW7
0
0
0
20
1
4
40
2
8
60
3
12
80
5
0
1
0
1
21
1
5
41
2
9
61
3
13
81
5
1
2
0
2
22
1
6
42
2
10
62
3
14
82
5
2
3
0
3
23
1
7
43
2
11
63
3
15
83
5
3
4
0
4
24
1
8
44
2
12
64
4
0
84
5
4
5
0
5
25
1
9
45
2
13
65
4
1
85
5
5
6
0
6
26
1
10
46
2
14
66
4
2
86
5
6
7
0
7
27
1
11
47
2
15
67
4
3
87
5
7
8
0
8
28
1
12
48
3
0
68
4
4
88
5
8
9
0
9
29
1
13
49
3
1
69
4
5
89
5
9
10
0
10
30
1
14
50
3
2
70
4
6
90
5
10
11
0
11
31
1
15
51
3
3
71
4
7
91
5
11
12
0
12
32
2
0
52
3
4
72
4
8
92
5
12
13
0
13
33
2
1
53
3
5
73
4
9
93
5
13
14
0
14
34
2
2
54
3
6
74
4
10
94
5
14
15
0
15
35
2
3
55
3
7
75
4
11
95
5
15
16
1
0
36
2
4
56
3
8
76
4
12
96
6
0
17
1
1
37
2
5
57
3
9
77
4
13
97
6
1
18
1
2
38
2
6
58
3
10
78
4
14
98
6
2
19
1
3
39
2
7
59
3
11
79
4
15
99
6
3